Permit Information
Permit NumberBLD03-01060
StatusFinaled
Name DR DAVID MUNRO DDS
Site Address 222 N 2ND ST Unit: STE 303
Project NameANDERSON PLAZA
Customer Number 
ePlanReviewNo
Description
(DR DAVID MUNRO DDS - 3RD FLOOR) This building is NOT fire sprinklered. To remodel an existing 1,330 square foot office tenant space located on the 3rd floor of "Anderson Plaza Medical Building". Work is to include a restroom accessible to the disabled, interior nonbearing walls, millwork, interior finishes, and suspended ceilings all per approved drawings and plan review conditions on file. The existing 1-hr corridor shall be maintained. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/1/200310/3/200310/3/2003APASS
DetailsJim Storey
larry; Phone #: ###-#### Internet Inspection Request from: Annette Moore final ok card on site. 10/3/2003 10:39:49 AM
First Notice 10/3/200310/3/2003 DONE
Permanent Occupancy 10/3/200310/3/2003 DONE
Details
Permanent occupancy  10/3/2003 DONE
Perm. Occ. Cert. # 9832 issued 10-3-03 to Dr. David Munro on the 3rd floor of the Anderson Plaza bldg.
FIRE-Final Inspection9/30/200310/1/200310/1/2003APASS
DetailsRick Jackson
larry; Phone #: ###-#### Internet Inspection Request from: Annette Moore GC will have door hardware and smoke seal for structural inspector as it was just painted; penetrations in corridor wall require fire stopping 10/1/2003 3:02:08 PM
BLD-Framing/Rough-in9/30/200310/1/200310/1/2003APART
DetailsDave Hannah
larry; Phone #: ###-#### Internet Inspection Request from: Annette Moore ceiling grid needs spreader bars 10/1/2003 12:41:47 PM
FIRE-Final Inspection9/25/20039/25/20039/25/2003PFAIL
DetailsRick Jackson
larry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie penetrations reuire fire stopping; duct opening in corridor wall requires smoke/fire damper with detection to operate damper; hang fire extinguisher 9/25/2003 4:06:41 PM
Inspection Record Card- Bld  8/28/2003 DONE
BLD-Framing/Rough-in8/8/20038/8/20038/8/2003PPART
DetailsCarl Dependahl
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore...ok to cover walls, patch floor/clg & walls for 1hr const as req'd...continuous gypsum req'd 8/8/2003 2:51:14 PM
BLD-Conference8/5/20038/6/20038/6/2003APASS
DetailsCarl Dependahl
LARRY; Phone #: ###-#### Internet Inspection Request from: Darla Downs...1hr bldg, need patch gyp & firestop penetrations...may req fire damper at exh duct. ok to cover int partitions pending elec/plbg 8/6/2003 12:03:23 PM
Issue & PRINT permit  7/7/2003 DONE
Print Occupancy Form  7/3/2003 DONE
Telephone call  7/3/2003 DONE
permit ready
Routing - PLAN CHECK6/11/2003 7/2/2003 PASS
Drawings approved after resubmittal review.
PLANS/APPL TAKEN TO FRONT DESK  7/2/2003 PASS
Plan assigned to (CJW)5/15/2003 7/2/2003 PASS
DetailsCarl Westfall
7/2/2003 13:58:32 CJW - activity updated through activity BLDA022 from case BLD03-01060.
Plan resubmittals received  6/26/2003 DONE
Transmittal from Russ Powers, two sets of A2.0, A3.0, A3.1, A5.0, and taken to Carl.
Routing - FIRE6/9/2003 6/11/2003 PASS
Routing - PLAN CHECK5/22/2003 6/9/2003  
Failed first IBC review. IBC plan review started June 6, 2003 and finished June 9, 2003. A response from the architect was required. See the plan review report.
Routing - PLUMBING5/19/2003 5/21/2003 PASS
sht, P1.0, too many fixture units on a 2" waste line serving s-1, fs-1, b-1, cc-1, ss-1, ew-1, ls-1, incerase to 3". compressed air and vacuum only, no other medical gas systems.
Routing - PUBLIC WORKS5/15/2003 5/16/2003 PASS
Plans ACCEPTED BY PLAN TECH  5/12/2003 DONE
Application has a Mechanical value, does not have a mechanical plan.
Application received  5/8/2003  
Recd Pcfee & Taken To Pln CK  5/8/2003 DONE
Fee Review-notes5/8/20035/8/2003