Case Summary (BLD) | | | 3/15/2004 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 3/15/2004 | | |
|
|
|
|
Case Summary (BLD) | | | 3/15/2004 | | DONE |
|
|
|
|
Permanent Occupancy | | 9/5/2003 | 9/5/2003 | | DONE |
|
|
|
|
FIRE-Final Inspection | 9/5/2003 | 9/5/2003 | 9/5/2003 | P | PASS |
Rick Jackson
|
|
|
JIM; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
First Notice | | 9/5/2003 | 9/5/2003 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 9/5/2003 | | DONE |
|
|
|
Perm. Occ. cert. #9788 issued 9-5-03 to Amalgamated Sugar Company.
|
FIRE-Final Inspection | 9/3/2003 | 9/4/2003 | 9/4/2003 | A | FAIL |
Rick Jackson
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore one detector didn't shut down the AHU on north side 9/4/2003 4:00:50 PM
|
BLD-Final | 9/3/2003 | 9/4/2003 | 9/4/2003 | A | PASS |
Jim Storey
|
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore final ok 9/5/2003 3:18:39 PM
|
FIRE-Final Inspection | 9/2/2003 | 9/3/2003 | 9/3/2003 | A | NR |
Rick Jackson
|
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore will be rescheduled - they are having trouble with the detectors for AHU shutdown 9/3/2003 3:54:26 PM
|
BLD-Final | 9/2/2003 | 9/3/2003 | 9/3/2003 | A | NR |
Jim Storey
|
|
|
Jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIRE-Final Inspection | 8/27/2003 | 8/29/2003 | 8/29/2003 | A | FAIL |
Rick Jackson
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Marc Lileks the east half of the building is not used by this tenant but may be used in the future and the exit system in this area must have exit signs/emergency lighting as it is not separated from the west half; exit doors to openable from the inside without special knowledge; air handler systems over 2000 cfm to have detectors for unit shutdown per plan review notes and will be installed per UMC 608 as no new mechanical work was part of this permit 8/29/2003 9:54:38 AM
|
BLD-Final | 8/27/2003 | 8/29/2003 | 8/29/2003 | P | FAIL |
Jim Storey
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Marc Lileksfire exit isues. no insp. until fire aproval. 8/29/2003 4:48:41 PM
|
BLD-Framing/Rough-in | 8/14/2003 | 8/15/2003 | 8/15/2003 | A | PASS |
Jim Storey
|
|
|
Mike ###-#### Mike ###-#### c/n made ok. 8/15/2003 4:30:46 PM
|
BLD-Framing/Rough-in | 8/12/2003 | 8/13/2003 | 8/13/2003 | A | FAIL |
Russ Owen
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. posted c/n not per plan floor plan chages require resubmital. 8/13/2003 5:20:13 PM
|
Inspection Record Card- Bld | | | 8/6/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/6/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/6/2003 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 7/15/2003 | | 8/5/2003 | | PASS |
|
|
|
8/5/2003 09:45:29 RMH - activity updated through activity BLDA022 from case BLD03-01681.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/5/2003 | | DONE |
|
|
|
|
Routing - FIRE | 7/30/2003 | | 8/4/2003 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 7/16/2003 | | 7/30/2003 | | PEND |
|
|
|
No corrections required by building department review, Permit pending fire department review, Routed to fire department on 7/30/03.
|
Routing - PUBLIC WORKS | 7/15/2003 | | 7/16/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/14/2003 | | PASS |
|
|
|
plans not fully dimensioned.
|
Application received | | | 7/11/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/11/2003 | | |
|
|
|
|
Fee Review-notes | 7/11/2003 | 7/11/2003 | | | |
|
|
|
|