Case Summary (BLD) | | | 11/25/2008 | | |
|
|
|
|
BLD-Aging Inspection | 7/1/2004 | 7/1/2004 | 7/1/2004 | | DONE |
Troy James
|
|
|
|
DOC - Permit Expired | 7/1/2004 | 7/1/2004 | 7/1/2004 | A | PASS |
Troy James
|
|
|
Expired by inspector at 7/1/2004 9:56:13 AM
|
Letter of compliance | | | 10/7/2003 | | DONE |
|
|
|
Letter of Compliance # 24125 issued 10-7-03.
|
BLD-Final | 9/11/2003 | 9/12/2003 | 9/12/2003 | A | PASS |
Dave Hannah
|
|
|
KEN; Phone #: ###-#### Internet Inspection Request from: Marc Lileks ok for perm occ 9/12/2003 10:32:47 AM
|
BLD-Final | 9/11/2003 | 9/11/2003 | 9/11/2003 | P | FAIL |
Jim Storey
|
|
|
need fire stopping at sink. 9/11/2003 2:29:21 PM
|
FIRE-Final Inspection | 9/10/2003 | 9/10/2003 | 9/10/2003 | P | PASS |
Rick Jackson
|
|
|
ken; Phone #: ###-#### Internet Inspection Request from: Darla Downs ratged door wasn't latching but will have it ready for structural inspector 9/10/2003 2:08:17 PM
|
BLD-Final | 9/10/2003 | 9/10/2003 | 9/10/2003 | P | CANC |
Dave Hannah
|
|
|
ken; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIRE-Final Inspection | 9/8/2003 | 9/9/2003 | 9/9/2003 | A | FAIL |
Rick Jackson
|
|
|
KEN; Phone #: ###-#### Internet Inspection Request from: Marc Lileks extinguisher needed and closure on rated door 9/9/2003 8:38:59 AM
|
BLD-Framing/Rough-in | 9/4/2003 | 9/5/2003 | 9/5/2003 | A | PART |
Tony Young
|
|
|
KEN TO INSPECT FIRE WALL ; Phone #: ###-#### Internet Inspection Request from: Darla Downs
f/w ok, need to verify ceiling grid end wires at final 9/5/2003 12:30:48 PM
|
BLD-Wall cover | 9/5/2003 | 9/5/2003 | 9/5/2003 | P | PART |
Tony Young
|
|
|
firewall, ken
see prior notes 9/5/2003 1:48:50 PM
|
BLD-Framing/Rough-in | 8/21/2003 | 8/22/2003 | 8/22/2003 | A | PASS |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 8/21/2003 | 8/21/2003 | 8/21/2003 | P | CANC |
Dave Hannah
|
|
|
KEN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Inspection Record Card- Bld | | | 8/21/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/21/2003 | | DONE |
|
|
|
|
Plan assigned to (MLO) | 7/29/2003 | | 8/20/2003 | | PASS |
Mike Otto
|
|
|
8/20/2003 15:19:16 MLO - activity updated through activity BLDA022 from case BLD03-01799.
|
Routing - PLAN CHECK | 8/18/2003 | | 8/20/2003 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/20/2003 | | |
|
|
|
|
Routing - FIRE | 8/13/2003 | | 8/18/2003 | | PASS |
|
|
|
resubmittal acceptable
|
Plan resubmittals received | | | 8/14/2003 | | DONE |
|
|
|
Transmittal letter from Erstad Thornton Arch with two revised copies A2.11 taken to Mike O.
|
Routing - PLAN CHECK | 8/8/2003 | | 8/13/2003 | | PEND |
|
|
|
8/8 sent fax to architect about missing shaft fire-resistive assembly. MLO 8/14 Architect changing plans for shaft at chemical hood resubmittals required. Fax sent MLO
|
Routing - PLANNING | 8/7/2003 | | 8/8/2003 | | PASS |
|
|
|
Pass: 0 exterior changes & not adding any structures or sq. footage. AKT
|
Plan resubmittals received | | | 8/8/2003 | | DONE |
|
|
|
Received one copy of response letter addressed to Sam Rogers and two copies of a list of Microchemistry Chemicals. Routed to Mike O. kmm
|
Routing - PLUMBING | 8/6/2003 | | 8/7/2003 | | PASS |
|
|
|
per plans and 2000 upc, verify existing waste will handle discharge from lab sinks.
|
Routing - FIRE | 7/31/2003 | | 8/6/2003 | | FAIL |
|
|
|
Additional info on haz mat's including science kit materials, exhaust hood and the LP system are required. Review comments faxed to and discussd with architect (Richard).
|
Plan resubmittals received | | | 8/6/2003 | | DONE |
|
|
|
Received two copies of revised sheets a2.11 and one copy of response letter and transmittal. Routed to Mike O. kmm
|
Plan resubmittals requested | | | 7/31/2003 | | DONE |
|
|
|
IBC corrections
|
Routing - PLAN CHECK | 7/30/2003 | | 7/31/2003 | | FAIL |
|
|
|
corrections sent to architect
|
Routing - PUBLIC WORKS | 7/29/2003 | | 7/30/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/25/2003 | | DONE |
|
|
|
|
Application received | | | 7/24/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/24/2003 | | |
|
|
|
|
Fee Review-notes | 7/24/2003 | 7/24/2003 | | | |
|
|
|
|