Letter of compliance | | | 12/30/2005 | | DONE |
|
|
|
Letter of Compliance issued 12-30-05.
|
BLD-Final | 11/29/2005 | 11/29/2005 | 12/1/2005 | P | PASS |
Dave Hannah
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
BLD-Aging Inspection | 11/21/2005 | 11/21/2005 | 11/21/2005 | | NR |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 9/19/2005 | 9/19/2005 | 9/20/2005 | P | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 9/19/2005 | 9/19/2005 | 9/19/2005 | P | FAIL |
Dave Hannah
|
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs handrail on ramp in basement
|
FIRE-Final Inspection | 9/14/2005 | 9/14/2005 | 9/14/2005 | P | PART |
Forrest France
|
|
|
A smoke door to separate the new breakroom from the exiting corridor was not installed as indicated on the scope of work, contractor says plans do not indicate this door, waiting on clarification from architect in regards to this issue.
|
FIRE-Final Inspection | 7/14/2005 | 7/15/2005 | 7/15/2005 | A | FAIL |
Forrest France
|
|
|
Clarify scope of work in regard to the installation of a new smoke door at exiting corridor from break room, fire sprinkler permit FIR04-00358 must be finaled prior to sign-off on building permit.
|
BLD-Framing/Rough-in | 5/4/2005 | 5/4/2005 | 5/4/2005 | P | PART |
Dave Hannah
|
|
|
ceiling inspection please///paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover main entry area holes around elev and stair tower patched
|
BLD-Aging Inspection | 5/2/2005 | 5/2/2005 | 5/3/2005 | | PASS |
Dave Hannah
|
|
|
work in progress
|
BLD-Framing/Rough-in | 5/2/2005 | 5/2/2005 | 5/2/2005 | P | PART |
Dave Hannah
|
|
|
paul///ceiling inspection on 1st floor lobby only please; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceiling grid is org so its ok but need to patch holes in stair tower and elev shaft above ceiling line
|
BLD-Framing/Rough-in | 2/24/2005 | 2/25/2005 | 2/25/2005 | P | PART |
Dave Hannah
|
|
|
Paul; Phone #: ###-#### Internet Inspection Request from: Jan Rice ceiling grid ok to drop in pannels 2/25/2005 3:23:19 PM
|
BLD-Framing/Rough-in | 2/15/2005 | 2/16/2005 | 2/16/2005 | A | PART |
Troy James
|
|
|
Paul-basement; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to cover walls only upon approval of all trades. 2/16/2005 9:32:25 AM
|
BLD-Framing/Rough-in | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | PART |
Dave Hannah
|
|
|
this is in the basement bathroom please///paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore restrooms in basement ok to cover 2/2/2005 1:55:00 PM
|
BLD-Conference | 1/20/2005 | 1/21/2005 | 1/21/2005 | A | CANC |
Dave Hannah
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Conference | 1/21/2005 | 1/21/2005 | 1/21/2005 | P | PART |
Dave Hannah
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ada restrooms in basement 1/21/2005 2:12:41 PM
|
BLD-Framing/Rough-in | 1/14/2005 | 1/14/2005 | 1/14/2005 | P | PART |
Dave Hannah
|
|
|
ceiling inspection please///paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to drop in pannels 1/14/2005 4:19:23 PM
|
BLD-Framing/Rough-in | 12/9/2004 | 12/10/2004 | 12/10/2004 | A | PART |
Dave Hannah
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice 1st floor bath room 12/10/2004 11:19:35 AM
|
BLD-Conference | 12/1/2004 | 12/1/2004 | 12/1/2004 | P | DONE |
Dave Hannah
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Jan Rice
|
BLD-Framing/Rough-in | 11/18/2004 | 11/18/2004 | 11/18/2004 | P | PART |
Dave Hannah
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ceiliong grid second floor bath rooms ok to drop in pannels 11/18/2004 3:19:21 PM
|
BLD-Framing/Rough-in | 11/5/2004 | 11/8/2004 | 11/8/2004 | P | PART |
Dave Hannah
|
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore restroom on second floor ok to cover 11/8/2004 2:41:47 PM
|
BLD-Foundation | 10/14/2004 | 10/14/2004 | 10/14/2004 | P | CANC |
Dave Hannah
|
|
|
ceiling grid-- mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 10/14/2004 | 10/14/2004 | 10/14/2004 | P | PART |
Dave Hannah
|
|
|
ceiling grid-- mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 3rd floor ok to drop in ceiling panels after elec sign off
|
BLD-Framing/Rough-in | 9/30/2004 | 10/1/2004 | 10/1/2004 | P | PART |
Dave Hannah
|
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 3rd floor bath rooms ok to cover after plumbing r/i 10/1/2004 2:05:41 PM
|
BLD-Aging Inspection | 8/17/2004 | 8/17/2004 | 8/17/2004 | | PASS |
Dave Hannah
|
|
|
wip 8/17/2004 9:28:54 AM
|
BLD-Conference | 6/5/2004 | 6/7/2004 | 6/7/2004 | A | DONE |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 6/5/2004 at 12:59:06 PM. Contact: ###-####.
|
BLD-Footing | 5/13/2004 | 5/17/2004 | 5/17/2004 | A | PART |
Dave Hannah
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes north side column ftgs ok they will also have spec inspe 5/17/2004 11:12:38 AM
|
BLD-Aging Inspection | 5/12/2004 | 5/12/2004 | 5/12/2004 | | DONE |
Dave Hannah
|
|
|
exps on 8/4 5/12/2004 7:27:43 AM
|
Issue PAID IN FULL permit | | | 2/11/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/27/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (DRS) | 8/1/2003 | | 1/6/2004 | | PASS |
Dan Stuart
|
|
|
1/6/2004 11:32:48 DRS - activity updated through activity BLDA022 from case BLD03-01830.
|
Routing - PLAN CHECK | 1/6/2004 | | 1/6/2004 | | PASS |
|
|
|
Approved as noted on plans, attached plan review comments of all agencies and recorded Letter of Agreement on property for five year time frame to fully sprinkler the building from the date of permit issuance. Copy attached to plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/6/2004 | | PASS |
|
|
|
To permit desk to process for issuing of building permit.
|
Telephone call | | | 1/6/2004 | | DONE |
|
|
|
Called Steve Christianson, LCA, to let him know the plans were approved by fire and have been taken to the permit desk for processing for building permit.
|
Inspection Record Card- Bld | | | 1/6/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/6/2004 | | DONE |
|
|
|
|
Telephone call | | | 1/6/2004 | | DONE |
|
|
|
left a message with Gus at Gorringe Brothers -- permit is ready.
|
Routing - PLAN CHECK | 10/6/2003 | | 12/22/2003 | | PEND |
|
|
|
Approved as noted and attached plan review comments and the Letter of Agreement for a five year time frame from date of permit issuance to have the building fully sprinklered.
|
Plan resubmittals received | | | 12/19/2003 | | |
|
|
|
Received two copies of reivsed sheets A2.08, A2.11, A2.12, A4.0, A4.1, E1.0, E2.1D, E2.1, E2.2D, E2.2, E3.0, and response letter. routed to Dan S. kmm
|
Telephone call | | | 10/6/2003 | | DONE |
|
|
|
telcon from Jeff at Eidam; explained my review comments relative to FA requirements. Faxed a copy to them for their review.
|
Routing - FIRE | 9/26/2003 | | 10/3/2003 | | FAIL |
|
|
|
Inadequate alarm and related information. Review comments faxed to architect
|
Plan resubmittals requested | | | 9/26/2003 | | FAIL |
|
|
|
FAXED TO STEVE CHRISTIANSEN
|
Meeting | | | 9/25/2003 | | DONE |
|
|
|
Met with Steve Christiansen, LCA, and Anna Lisby & Kent Oram of Idaho Central Credit Union. Discussion concerning 1) Making sure restroom stall doors are big enough to meet accessiblity requirements (32" clear width);
2) Letter of agreement in file under BLD01-00231 signed by Mr. Adams (last owner) & Tim Hogland (Building Official) agreeing to upgrade restrooms for accessibility compliance and smoke guard protection at all elevato openings, to be completed by Feb 2004. Mr. Oram or Ms. Lisby had never heard of the agreement. A copy was given to them;
3) The corridors throughout the building are not in compliance as 1-hour rated with openings, penetrations & glazing protected as noted in codes under which constructed and permits that have been issued. We discussed options for upgrade agreement proposal. Over a proposed period of time upgrade all corridor deficiencies (construction, doors, glazing, fire dampers, hardware) or sprinkler the builidng throughout over a to be proposed time frame that would elliminate the need for rated corridors.
We also noted that there appears to be an access panel in the third floor stair enclosure, NW stair, to access mechanical. Stair enclosure are to have no penetrations except by utilities specifically serving the enclosure only. They would check this out.
|
Routing - PLAN CHECK | 8/6/2003 | | 9/25/2003 | | FAIL |
|
|
|
ROUTING TO FIRE CODE ANALYST WHILE WAITING FOR RESPONSE FROM ARCHITECT.
|
Telephone call | | | 9/24/2003 | | DONE |
|
|
|
Call from Steve Chritiansen, Lombard Conrad Architects requesting a meeting with himself and two representative with Idaho Central Credit Union to discuss options for the lack of a rated corridor system. We agreed to 10 AM on Thursday, 9/25/03.
|
Routing - PLANNING | 8/5/2003 | | 8/6/2003 | | PASS |
|
|
|
Approve per DRH03-109.
|
Routing - Erosion and Sediment | 8/4/2003 | | 8/4/2003 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PUBLIC WORKS | 8/1/2003 | | 8/4/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/30/2003 | | DONE |
|
|
|
|
Application received | | | 7/29/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/29/2003 | | DONE |
|
|
|
|
Routing - FIRE | 12/23/2003 | | 1/5/2003 | | PASS |
|
|
|
Resubmittal acceptable.
|
Fee Review-notes | 7/29/2003 | 7/29/2003 | | | |
|
|
|
|