Second Notice BLD | 4/26/2005 | 4/26/2005 | 4/26/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 11/7/2003 | 4/26/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 11/7/2003 | 11/7/2003 | 11/7/2003 | A | PASS |
Jim Storey
|
|
|
Finaled by inspector at 11/7/2003 10:24:51 AM
|
FIRE-Final Inspection | 11/6/2003 | 11/6/2003 | 11/6/2003 | P | PASS |
Rick Jackson
|
|
|
|
BLD-Other | 9/8/2003 | 9/9/2003 | 9/9/2003 | A | PASS |
Steven Webb
|
|
|
jeff Pallet racking inspect ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
(F) Reprint permit | | | 8/27/2003 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 8/26/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/26/2003 | | |
|
|
|
permit ready and fees due
|
Permit Ready to Issue | | | 8/26/2003 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 8/26/2003 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/21/2003 | | 8/25/2003 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 8/25/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/25/2003 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 8/13/2003 | | 8/25/2003 | | PASS |
|
|
|
8/25/2003 15:09:10 RMH - activity updated through activity BLDA022 from case BLD03-01944.
|
Routing - FIRE | 8/22/2003 | | 8/22/2003 | | PASS |
Bill Alexander
|
|
|
|
Routing - FIRE | 8/19/2003 | | 8/21/2003 | | FAIL |
Bill Alexander
|
|
|
A. Plan lacks actual high piled storage area incorporating within this facilities tenant space. Area of storage is measured 15'-0" beyond the racks and/or to 1-hour fire resistive separation walls.
B. Floor plan (Page 03), of racking layout has no scale. Correct scaled plans is required to verify actual High Piled Storage Area to 15'-0" beyond or to 1-hour fire separation.
C. Provide Class of Commodity/s intended to store.
D. Provide the actual storage height (top of storage) of commodity.
E. Provide elevation of the roof.
F. Provide elevation of bottom cord of roof support system.
G. Provide information (size/location/type/actuation/temperature) of any roof smoke/heat vents installed within the area addressed in item "A" above.
H. Provide/show any curtain boards located within the area addressed in item "A" above.
I. Include outside door accesses, which should be dimensioned.
|
Plan Review Completed(1st rev) | | | 8/21/2003 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/13/2003 | | 8/19/2003 | | |
|
|
|
Routed plans to Fire first to expedite permit.
|
Plans ACCEPTED BY PLAN TECH | | | 8/13/2003 | | DONE |
|
|
|
|
Plan routing begun/TENANTS | | | 8/13/2003 | | |
|
|
|
|
Application received | | | 8/12/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 8/12/2003 | | |
|
|
|
|
Fee Review-notes | 8/12/2003 | 8/12/2003 | | | |
|
|
|
|