Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberBLD03-01974
StatusExpired
Name USTICK SHOPPING CENTER FIRE REPAIR
Site Address 6505 W USTICK RD
Project NameUSTICK SHOPPING CENTER
Customer Number 
ePlanReviewNo
Description
(Formal & Bridal)(Phase 2)(Fire repair) (Vanilla Finish) * To repair damage to building caused by a fire. Work to include installation of a new 3 hour fire walls with parapets, to divide the building into two areas. The east side is approximately 9,000 sq.ft. and the west side is approximately 6,900 sq.ft. construct a new 3 hour fire barrier wall around the storage areas in the back, installation of interior walls are being constructed to divide this building into four separate tenant spaces, replace existing roof framing with trusses where located on the approved plans, install new electrical wiring, mechanical system, suspended ceiling and new facade across the front of the building. All construction per the approved plans and attached comment list. NOTE: This permit is for a VANILLA FINISH only. Separate permits and and Certificate of Occupancies must be obtained for any additional work performed and before any tenent spaces can be occupied. MJP PC#488-03 DRH03-00102
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection11/7/200611/7/200611/7/2006 PASS
DetailsTom Arcoraci
DOC - Permit Expired11/7/200611/7/200611/7/2006PPASS
DetailsTom Arcoraci
BLD-Aging Inspection9/6/20069/6/20069/6/2006 NR
DetailsTom Arcoraci
BLD-Aging Inspection7/6/20067/6/20067/6/2006 DEFR
DetailsTom Arcoraci
cod issues
BLD-Aging Inspection2/20/20062/20/20062/21/2006 NR
DetailsTom Arcoraci
BLD-Aging Inspection12/19/200512/19/200512/19/2005 NR
DetailsTom Arcoraci
BLD-Aging Inspection10/17/200510/17/200510/17/2005 CANC
DetailsTom Arcoraci
CHANGE STATUS TO (ISS)  8/31/2005 DONE
Re-open per Tom Arcoraci////8/31/05 BAS
(F) Reprint permit  8/29/2005 DONE
Print Occupancy Form  8/26/2005 DONE
BLD-Aging Inspection8/15/20058/15/20058/15/2005 CANC
DetailsTom Arcoraci
DOC - Permit Expired8/15/20058/15/20058/15/2005PPASS
DetailsTom Arcoraci
BLD-Aging Inspection6/8/20056/8/20056/8/2005 PASS
DetailsTom Arcoraci
talked to john will get finals
BLD-Aging Inspection4/4/20054/4/20054/4/2005 NR
DetailsTom Arcoraci
FIRE-Final Inspection9/29/20049/30/20049/30/2004APASS
DetailsTroy Cobbley
Fire lfie safety passed 9/30/2004 9:13:49 AM
FIRE-Final Inspection9/27/20049/28/20049/28/2004AFAIL
DetailsTroy Cobbley
Relocate duct smoke detectors above return air round duct and provide sample tubes. This is for spaces 6421 and 6423. 9/28/2004 10:03:54 AM
BLD-Final8/30/20048/31/20048/31/2004PPART
DetailsTom Arcoraci
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore needs fire and code enf sign off for lc 8/31/2004 3:00:37 PM
FIRE-Final Inspection8/30/20048/31/20048/31/2004AFAIL
DetailsTroy Cobbley
Duct detectors are mounted in wrong locations. Gas was not turned on yet to the HVAC units. Test duct detectors. Repair emergency light in east end tenant space. 8/31/2004 2:47:06 PM
FIRE-Final Inspection8/26/20048/26/20048/26/2004PFAIL
DetailsTroy Cobbley
Inspection was actually a conference with the owner. We went over life/safety requirements which included door hardware, emergency lighting, exit signs, rated doors and smoke seals. Plan reviewer missed the exit discharge lighting so I notified the owner it would be require (plan reviewer verified this), also additional walls have been built in two of the tenant spaces. Per plan reviewer its structurals call on resubmittals 8/26/2004 4:23:58 PM
BLD-Aging Inspection8/2/20048/2/20048/2/2004 NR
DetailsTom Arcoraci
BLD-Framing/Rough-in6/1/20046/2/20046/2/2004APASS
DetailsTom Arcoraci
John; Phone #: ###-#### or ###-#### Internet Inspection Request from: Aimee Hughes
BLD-Framing/Rough-in6/1/20046/1/20046/1/2004PCANC
DetailsTroy James
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Conference2/11/20042/11/20042/11/2004PDONE
DetailsSteven Webb
Issued c/n. ESC permit is required plus other items including rp needed on job. Complete all items on notice by the end of the day 2/15/04. 2/11/2004 2:16:16 PM
Plan assigned to (M_P)8/18/20038/18/200311/26/2003 PASS
DetailsMike Phillips
11/26/2003 08:34:14 M_P - activity updated through activity BLDA022 from case BLD03-01974.
Routing - PLAN CHECK9/11/2003 11/26/2003 PASS
PLANS/APPL TAKEN TO FRONT DESK  11/26/2003 DONE
Print Pending Permit.LaserJet4  11/26/2003  
Case Summary (BLD)  11/26/2003  
Inspection Record Card- Bld  11/26/2003 DONE
Permit Ready to Issue  11/26/2003  
Telephone call  11/26/2003 DONE
talked to bill to verify plans are ready
Issue PAID IN FULL permit  11/26/2003 DONE
Plan resubmittals received  10/24/2003 DONE
Received three copies of revised sheets SD1, A1, A1a, A4.1, A4.2, A5, A6, A7, G and three copies of reviesed struct. calcs. Routed to Mike P. kmm
Routing - FIRE9/2/2003 9/10/2003 PASS
Approved subject to compliance with IBC plan review comments and satisfactory IFC inspection by the PDS Fire inspector. Vanilla finish-no occupancy allowed
Routing - PLAN CHECK8/27/2003 9/3/2003 FAIL
PLan review completed, copy of plan review report mailed to architect requesting additional information be submitted for further review prior to issuing permit.
Routing - PLUMBING8/25/2003 8/27/2003 PASS
1. existing water heaters may require a pan with a drain 2. may require thermal expansion protection 3. building will require premise backflow protection
Routing - PLANNING8/20/2003 8/22/2003 PASS
Approved per DRH03-102.
Routing - PUBLIC WORKS8/19/2003 8/20/2003 PASS
Routing - PLANNING Land Div8/18/2003 8/19/2003 PASS
Approved. Parcel created prior to 1965 as documented by recorded warranty deed.
Plans ACCEPTED BY PLAN TECH  8/18/2003 DONE
Accepted per Mike Phillips. kmm
Plan routing begun/TENANTS  8/18/2003 DONE
Application received  8/14/2003  
Recd Pcfee & Taken To Pln CK  8/14/2003  
Fee Review-notes8/14/20038/14/2003