Second Notice BLD | 4/23/2008 | 4/23/2008 | 4/24/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 2/13/2008 | 4/23/2008 | | DONE |
|
|
|
|
Permanent Occupancy | | | 2/13/2008 | | DONE |
|
|
|
|
BLD-Final | 2/1/2008 | 2/1/2008 | 2/1/2008 | P | PASS |
Dave Hannah
|
|
|
coby Phone #: ###-#### ok for perm occ
|
BLD-Final | 1/25/2008 | 1/25/2008 | 1/26/2008 | P | FAIL |
Dave Hannah
|
|
|
Jermey Malone, ###-#### ext 2hr fire wall for horz exit not to code and exit signs missing
|
BLD-Final | 1/24/2008 | 1/25/2008 | 1/25/2008 | A | DEFR |
Dave Hannah
|
|
|
Jermey Malone, ###-#### rescheduled to pm
|
BLD-Final | 1/23/2008 | 1/24/2008 | 1/24/2008 | P | CANC |
Mike Jordan
|
|
|
Jeremy Malone, Please call first ###-####
|
FIRE-Final Inspection | 1/23/2008 | 1/23/2008 | 1/23/2008 | P | PASS |
Forrest France
|
|
|
Noted one additional fire extinguisher to be posted as discussed due to excessive travel distances, provide approved door hardware or remove door at the SE call center area, items to be completed prior to structural final for verification at that time. Fire life safety for the permit scope area is acceptable pending completion of these two items.
|
BLD-Aging Inspection | 1/18/2008 | 1/18/2008 | 1/23/2008 | P | DONE |
Forrest France
|
|
|
Site inspection scheduled.
|
BLD-Aging Inspection | 1/15/2008 | 1/15/2008 | 1/18/2008 | P | DEFR |
Forrest France
|
|
|
Inspection scheduled.
|
BLD-Aging Inspection | 1/15/2008 | 1/15/2008 | 1/18/2008 | | DEFR |
Dave Hannah
|
|
|
needs fire sign offs sent to fire
|
BLD-Aging Inspection | 11/7/2007 | 11/7/2007 | 11/7/2007 | | DEFR |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 8/16/2007 | 8/16/2007 | 8/20/2007 | | DEFR |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 8/28/2006 | 8/28/2006 | 8/29/2006 | | DEFR |
Dave Hannah
|
|
|
waiting for fire final
|
BLD-Aging Inspection | 6/23/2006 | 6/23/2006 | 6/26/2006 | | DONE |
Forrest France
|
|
|
Project final pending fire alarm work c/n issued to NWFS.
|
BLD-Aging Inspection | 4/17/2006 | 4/17/2006 | 4/17/2006 | | DONE |
Forrest France
|
|
|
Pending completion of project related alarm permit c/n.
|
BLD-Aging Inspection | 1/19/2006 | 1/19/2006 | 1/20/2006 | | DEFR |
Forrest France
|
|
|
sent to fire
|
BLD-Aging Inspection | 11/15/2005 | 11/15/2005 | 11/16/2005 | | FAIL |
Dave Hannah
|
|
|
waiting for fir to sign off perm
|
BLD-Aging Inspection | 8/5/2005 | 8/5/2005 | 8/8/2005 | | DONE |
Forrest France
|
|
|
Pending completion and inspection of fire alarm work under permit FIR05-00048 with NW sales company per upgrade agreement.
|
BLD-Aging Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 8/2/2004 | 8/2/2004 | 8/2/2004 | | PASS |
Dave Hannah
|
|
|
|
Case Summary (BLD) | | | 7/27/2004 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 7/27/2004 | | DONE |
|
|
|
|
BLD-Final | 12/22/2003 | 12/22/2003 | 12/22/2003 | P | FAIL |
Dave Hannah
|
|
|
Joe; Phone #: ###-#### they quit at 3:30 for the day, thanks.Internet Inspection Request from: Aimee Hughes needs fire life safty sign offs 12/22/2003 2:15:22 PM
|
BLD-Framing/Rough-in | 11/14/2003 | 11/17/2003 | 11/17/2003 | P | PART |
Dave Hannah
|
|
|
Joe --- drop in ceiling --- before 3:00 please; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok to drop in pannels 11/17/2003 2:35:13 PM
|
FIRE-Conference | 11/14/2003 | 11/14/2003 | 11/14/2003 | A | DONE |
Rick Jackson
|
|
|
Talked to Sam Rogers about the requirements for horn/strobes on this floor and relayed to Jeremy Malone about the need to submit plans for this floor or obtain waiver from Dave MIller/Sam Rogers 11/14/2003 10:49:02 AM
|
BLD-Framing/Rough-in | 11/7/2003 | 11/10/2003 | 11/10/2003 | A | PART |
Jim Storey
|
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Annette Moore screww sch. ok on walls. 11/10/2003 12:55:25 PM
|
BLD-Framing/Rough-in | 10/31/2003 | 10/31/2003 | 10/31/2003 | P | PASS |
Dave Hannah
|
|
|
dick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to start covering walls 10/31/2003 3:34:09 PM
|
Inspection Record Card- Bld | | | 10/28/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/28/2003 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/28/2003 | | DONE |
|
|
|
|
Telephone call | | | 10/28/2003 | | DONE |
|
|
|
Spoke with Evelyn told permit is ready & fees
|
Issue PAID IN FULL permit | | | 10/28/2003 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/16/2003 | | 10/27/2003 | | PASS |
|
|
|
Drawings approved after resubmittal review.
|
Plan resubmittals received | | | 10/27/2003 | | DONE |
|
|
|
Received two copies of revised sheet E2.0 and one copy of A2.1. One copy of response letter and one letter about elevatore modernization. Routed to Carl W. kmm
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/27/2003 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 9/29/2003 | | 10/27/2003 | | PASS |
Carl Westfall
|
|
|
10/27/2003 14:34:28 CJW - activity updated through activity BLDA022 from case BLD03-02347.
|
Routing - FIRE | 10/10/2003 | | 10/15/2003 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 10/1/2003 | | 10/10/2003 | | |
|
|
|
Failed first IBC plan review. IBC plan review started October 9, 2003 and finished the next day. A response from the architect was required. See the plan review report.
|
Routing - PUBLIC WORKS | 9/29/2003 | | 10/1/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/29/2003 | | DONE |
|
|
|
Per Carl
|
Plan resubmittals received | | | 9/29/2003 | | DONE |
|
|
|
Received transmittal letter with one set of sheets A1.0,A2.0,A3.0,M1.0,M2.0,E1.0,E1.1,E2.0,E2.1 taken to Carl W
|
Application received | | | 9/26/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/26/2003 | | DONE |
|
|
|
|
Extend Permit 180 days | 8/20/2007 | 8/20/2007 | | P | |
Forrest France
|
|
|
|
Fee Review-notes | 9/26/2003 | 9/26/2003 | | | |
|
|
|
|