Second Notice BLD | 4/26/2005 | 4/26/2005 | 4/26/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 11/3/2004 | 4/26/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 11/3/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10349 issued 11-3-04 to st. Luke's Hospital.
|
BLD-Final | 10/28/2004 | 10/29/2004 | 10/29/2004 | A | PASS |
Dave Hannah
|
|
|
Hi Dave try me at ###-#### pager 3006 Thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok for perm occ 10/29/2004 10:15:56 AM
|
Permanent Occupancy | | 10/29/2004 | 10/29/2004 | | DONE |
|
|
|
|
BLD-Conference | 10/28/2004 | 10/28/2004 | 10/28/2004 | A | CANC |
Gary Ziegler
|
|
|
|
BLD-Final | 10/28/2004 | 10/28/2004 | 10/28/2004 | P | CANC |
Dave Hannah
|
|
|
Hi Dave, Try ###-#### pager # 3006 if I don't answer. thanks Phil ; Phone #: ###-#### Internet Inspection Request from: Phil Doble 10/27/2004 3:34:17 PM
|
BLD-Final | 10/27/2004 | 10/27/2004 | 10/27/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave, Try ###-#### pager # 3006 if I don't answer. thanks Phil ; Phone #: ###-#### Internet Inspection Request from: Phil Doble 10/27/2004 3:34:17 PM ok for temp but needs plumbing to go perm 10/28/2004 12:31:16 PM
|
FIRE-Final Inspection | 10/20/2004 | 10/21/2004 | 10/21/2004 | A | FAIL |
Rick Jackson
|
|
|
Doors on clean core remain automatic upon fire alarm activation; extinguishers need ABC rating 10/21/2004 11:25:50 AM
|
BLD-Final | 10/20/2004 | 10/20/2004 | 10/20/2004 | P | FAIL |
Dave Hannah
|
|
|
Hi Dave, We would like you to walk thru after Rick J. Thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble needs fire sign off 10/20/2004 4:42:05 PM
|
FIRE-Alarm Testing | 10/14/2004 | 10/14/2004 | 10/14/2004 | A | FAIL |
Rick Jackson
|
|
|
Well Rick they want one more stab at it thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble Complete rated doors; extinguishers; recheck all smoke/fire dampers for operation - started checking and several weren't operating properly and need access doors 10/14/2004 4:17:07 PM
|
FIRE-Alarm Testing | 10/12/2004 | 10/12/2004 | 10/12/2004 | A | FAIL |
Rick Jackson
|
|
|
Hi Rick, If you can't reach me try ###-#### ext. 3006 thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble See fire alarm permit 10/12/2004 12:34:36 PM
|
FIRE-Final Inspection | 10/12/2004 | 10/12/2004 | 10/12/2004 | A | FAIL |
Rick Jackson
|
|
|
HI Rick, Doug said he's ready.; Phone #: ###-#### Internet Inspection Request from: Phil Doble need to complete exit signs and emergency lights; complete rated doors 10/12/2004 12:35:19 PM
|
FIRE-Final Inspection | 10/5/2004 | 10/6/2004 | 10/6/2004 | A | FAIL |
Rick Jackson
|
|
|
Hi Rick, Larry G. Wants a final on alarm system. Thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble need to pass the fire alarm inspection 10/7/2004 9:27:34 AM
|
BLD-Framing/Rough-in | 9/27/2004 | 9/27/2004 | 9/27/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave, I think the boy's got right this time. The ceiling grid Phil ; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok to start dropping in ceiling panals 9/27/2004 3:15:14 PM
|
BLD-Other | 9/22/2004 | 9/22/2004 | 9/22/2004 | A | FAIL |
Dave Hannah
|
|
|
Hi Dave, the boys are ready for the grid ceilings. on both floors; Phone #: ###-#### Internet Inspection Request from: Phil Doble ceiling grid perm wires out of plumb and need to fire proof holes in fire walls 9/22/2004 10:03:49 AM
|
BLD-Framing/Rough-in | 9/22/2004 | 9/22/2004 | 9/22/2004 | P | CANC |
Dave Hannah
|
|
|
Hi Dave, the boys are ready for the grid ceilings. on both floors; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Other | 9/14/2004 | 9/14/2004 | 9/14/2004 | P | DONE |
Dave Hannah
|
|
|
Hi Dave, I would like you to look at fire caulking and grid ceilings thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Conference | 8/25/2004 | 8/25/2004 | 8/25/2004 | P | DONE |
Dave Hannah
|
|
|
Hi Dave, I think it's time for another walk thru it's going fast. Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Conference | 7/20/2004 | 7/21/2004 | 7/21/2004 | A | PART |
Dave Hannah
|
|
|
Hi Dave, I have to go to a safety awards thing at 10:45am so if you could drop by before that if not o well. today OR 15 cover last one . Phil one. v s ; Phone #: ###-#### Internet Inspection Request from: Phil Doble last or ok to cover 7/21/2004 10:02:28 AM
|
BLD-Conference | 7/14/2004 | 7/14/2004 | 7/14/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave, we have more shaft walls for you. thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Wall cover | 7/8/2004 | 7/8/2004 | 7/8/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave, I have two more shaft walls for you. thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble horz cieiling shaft and shaft wall reduction ok to cover 7/8/2004 4:24:37 PM
|
BLD-Conference | 6/30/2004 | 7/1/2004 | 7/1/2004 | A | PART |
Dave Hannah
|
|
|
Hi Dave we need you to look at the rated walls that will have hard lids attached to them in the OR's thank's Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok to install hard lides 7/1/2004 10:21:31 AM
|
BLD-Wall cover | 6/29/2004 | 6/29/2004 | 6/29/2004 | P | FAIL |
Troy James
|
|
|
Hi Dave we would like you to look at the shaft walls and fire caulk thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
Inspected repairs of existing shafts. No frame around new fire/smoke damper and angles each side. 1" shaft walls damaged, need to repair. Did not complete inspection, not ready. 6/29/2004 2:31:36 PM
|
BLD-Wall cover | 6/22/2004 | 6/22/2004 | 6/22/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave need you to look at the framing in the OR suites in A area thanks PHIL 1 pm. works best ; Phone #: ###-#### Internet Inspection Request from: Phil Doble 6/22/2004 1:38:29 PM hard ceilings in first 5 opp rms ok to cover 6/22/2004 1:39:25 PM
|
BLD-Conference | 6/17/2004 | 6/17/2004 | 6/17/2004 | A | DONE |
Dave Hannah
|
|
|
Good morning Dave I should take you for a tour because the job is going fast I don't want you to miss nothing thanks PHIL; Phone #: ###-#### Internet Inspection Request from: Phil Doble 6/17/2004 10:13:21 AM walked basement area needs smoke fire dampers 2hr wall and at shaft old morgue area 6/17/2004 10:18:18 AM
|
BLD-Framing/Rough-in | 6/3/2004 | 6/3/2004 | 6/3/2004 | P | PART |
Dave Hannah
|
|
|
Hi Dave the area is E Which is OR 1 you can come by any time Thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble walls ok but need to check repairs on shafts 6/3/2004 1:59:59 PM
|
BLD-Wall cover | 5/21/2004 | 5/24/2004 | 5/24/2004 | A | PASS |
Tom Arcoraci
|
|
|
Hi Dave want you to look at all corridor walls on grd. flr. surgery suites thanks phil ; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok to cover corr walls 5/24/2004 10:12:51 AM
|
BLD-Wall cover | 5/18/2004 | 5/18/2004 | 5/18/2004 | A | PART |
Dave Hannah
|
|
|
Dave, the area's to look at are all of C and area D rooms GEE110,GEE111,& corri GEE 009, GE001. thanks Phil ; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok to cover walls 5/18/2004 10:25:18 AM
|
BLD-Framing/Rough-in | 5/10/2004 | 5/11/2004 | 5/11/2004 | A | CANC |
Dave Hannah
|
|
|
Dave, Area B is ready for a cover inspection. thank's Phil.; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Framing/Rough-in | 5/11/2004 | 5/11/2004 | 5/11/2004 | P | PART |
Dave Hannah
|
|
|
Dave, Area B is ready for a cover inspection. thank's Phil.; Phone #: ###-#### Internet Inspection Request from: Phil Doble ok to cover walls 5/11/2004 3:27:24 PM
|
BLD-Wall cover | 4/29/2004 | 4/30/2004 | 4/30/2004 | A | PART |
Dave Hannah
|
|
|
Dave, I also have to have Rick Jackson look at the penetration's thanks PHIL ###-#### ; Phone #: ###-#### Internet Inspection Request from: Phil Doble op rooms five along southwall ok to cover 4/30/2004 10:52:55 AM
|
BLD-Wall cover | 4/16/2004 | 4/19/2004 | 4/19/2004 | A | NR |
Dave Hannah
|
|
|
Dave I gave you Greg Lowder's # it's a beeper #0993 I will be out Mon thank's Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Conference | 3/30/2004 | 3/30/2004 | 3/30/2004 | P | DONE |
Dave Hannah
|
|
|
Phil Doble st. Lukes constr. field Conference walk thru surgery suite's. ; Phone #: ###-#### Internet Inspection Request from: Phil Doble
|
BLD-Aging Inspection | 3/22/2004 | 3/22/2004 | 3/22/2004 | | PASS |
Dave Hannah
|
|
|
wip 3/22/2004 8:14:11 AM
|
BLD-Aging Inspection | 3/22/2004 | 3/22/2004 | 3/22/2004 | | PASS |
Dave Hannah
|
|
|
wip 3/22/2004 8:14:11 AM
|
CHANGE STATUS TO (R) | | | 12/22/2003 | | DONE |
|
|
|
|
Issue & PRINT to be Invoiced | | | 12/22/2003 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 10/13/2003 | | 12/19/2003 | | PASS |
Dan Stuart
|
|
|
12/19/2003 14:06:55 DRS - activity updated through activity BLDA022 from case BLD03-02465.
|
Received Certificate of Value | | | 12/19/2003 | | DONE |
|
|
|
Received new certificate of value of $3,246,245.00, reflecting the removal of value for separate permit requested under BLD03-03000. Also received Cert. of Value for BLD03-03000.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/19/2003 | | PASS |
|
|
|
To permit desk for issue.
|
Inspection Record Card- Bld | | | 12/19/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/19/2003 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 12/3/2003 | | 12/17/2003 | | PASS |
|
|
|
Inserted corrected plans into original submittals & created separate permit for work in GE104 & GE105 Waiting Room, BLD03-03000.
|
Plan resubmittals received | | | 12/16/2003 | | DONE |
|
|
|
Received three copies of letters to Dan S. with three sets of sheets G0.3,A2.1,A6.1,A7.2D,A8.1,M2.2,M2.3,M2.0,M2.2,M2.3 taken to Dan S.
|
Plan Review Completed(1st rev) | | | 12/3/2003 | | DONE |
|
|
|
|
Routing - FIRE | 12/2/2003 | | 12/3/2003 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 10/17/2003 | | 12/2/2003 | | FAIL |
|
|
|
Corrections required. Copy of plan review faxed and mailed to architect for re-submittal. Plans routed to fire code analyst for review.
|
Plan resubmittals requested | | | 12/2/2003 | | DONE |
|
|
|
Copy of plan review report faxed and mailed to architect for his response.
|
Routing Off Site -Energy | 10/14/2003 | | 10/24/2003 | | PASS |
|
|
|
Routed to Ron O. for review
|
Routing - PLUMBING | 10/14/2003 | | 10/17/2003 | | PASS |
|
|
|
1 trap per trap arm, no valves downstream of avb, PF-9, vacuum plant must be compatable with waste anesthetic gas, vents must be 6" above flood level prior to connectiog to other vents page M2.0A grids 40-E.5, verify flow requirements for 2 1/2" MA connection to existing 2" pageM2.0 grids 39-E.9.
|
Routing - PUBLIC WORKS | 10/13/2003 | | 10/14/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 10/13/2003 | | DONE |
|
|
|
|
Application received | | | 10/9/2003 | | |
|
|
|
|