Permit Information
Permit NumberBLD03-02763
StatusFinaled
Name NAPA AUTO PARTS
Site Address 160 N 16TH ST
Project NameNAPA AUTO PARTS
Customer Number 
ePlanReviewNo
Description
(NAPA AUTO PARTS) To remodel the north end of an existing building consisting of a 13,287 sq.ft. 1st floor and 8,987 basement per appproved plans and CZC03-00169. Work to include construction of interior partitions to create office area & exit access hallway though warehouse area, cutting new exit doorway through existing CMU wall, creating new landing on the exterior, remodeling restrooms to make accessible. A SEPARATE PERMIT AND ENGINEERING IS REQUIRED FOR RACKING OVER EIGHT FEET HIGH. Lighting and Hvac systems are not being altered. This building is fully fire sprinklered for area increase, any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#711-03) rmh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice BLD4/26/20054/26/20054/27/2005 DONE
First Notice has not been responded to.
First Notice 11/19/20044/26/2005 DONE
Permanent occupancy  11/19/2004 DONE
Perm. Occ. Cert. # 10364 issued 11-19-04 to Napa Auto Parts.
Permanent Occupancy 11/15/200411/15/2004 DONE
Details
BLD-Final11/15/200411/15/200411/15/2004PPASS
DetailsDave Hannah
Jeff; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner ok fo perm occ 11/15/2004 1:03:17 PM
FIRE-Final Inspection10/21/200410/21/200410/21/2004PPASS
DetailsRick Jackson
BLD-Aging Inspection8/2/20048/2/20048/2/2004 NR
DetailsTony Young
BLD-Final12/26/200312/29/200312/29/2003APART
DetailsDave Hannah
###-#### dave ok for temp occ ok for perm after fire and pz signs perm 12/29/2003 9:36:18 AM
FIRE-Final Inspection12/24/200312/26/200312/26/2003APART
DetailsTroy Cobbley
A temporary occupancy was given until the fire alarm plans are approved, installed and inspected 12/26/2003 10:00:10 AM
FIRE-Final Inspection12/23/200312/24/200312/24/2003ANR
DetailsRick Jackson
temp occupancy can be approved after fire alarm upgrade submittals are received and assigned an FIR permit number; all outstanding items have been corrected 12/24/2003 12:01:35 PM
BLD-Final12/23/200312/24/200312/24/2003ACANC
DetailsDave Hannah
BLD-Final12/22/200312/23/200312/23/2003PNR
DetailsDave Hannah
###-#### Tim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
FIRE-Final Inspection12/23/200312/23/200312/23/2003PNR
DetailsRick Jackson
TIM ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie all other items completed; awaiting alarm plans 12/23/2003 1:55:42 PM
FIRE-Final Inspection12/19/200312/19/200312/19/2003AFAIL
DetailsRick Jackson
main exit to be keyed both sides; door hardware on east and south exit doors; need ceiling tiles on second floor; repair exit sign located at hallway to second exit; attempted to locate fire sprinklering monitoring alarm panel - the owner believes the only panel is the ADT security panel that is monitoring the sprinkler system - the sprinkler monitoring system will require 24 hr battery back-up (note 4 on plan review); manual pull and smoke detector above panel and monitoring of the HVAC detectors in NAPA TI; there is one detector for HVAC shut down in the NAPA TI and there appears to be a total of three HVAC units in the TI space that would require detectors for unit shutdown 12/19/2003 10:17:01 AM
BLD-Final12/18/200312/18/200312/18/2003PNR
DetailsRuss Owen
Tim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes needs fire/life safety and zoning, went over some items with contractor that would need to be addressed. 12/18/2003 4:10:03 PM
Plan assigned to (R_H)11/14/2003 12/15/2003 PASS
Details
12/15/2003 10:21:03 RMH - activity updated through activity BLDA022 from case BLD03-02763.
Routing - PLAN CHECK12/11/2003 12/15/2003 DONE
Case Summary (BLD)  12/15/2003 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/15/2003 DONE
Inspection Record Card- Bld  12/15/2003 DONE
Print Occupancy Form  12/15/2003 DONE
Permit Ready to Issue  12/15/2003 DONE
Issue PAID IN FULL permit  12/15/2003 DONE
Routing - FIRE12/12/2003 12/12/2003 PASS
DetailsBill Alexander
Routing - PLAN CHECK12/8/2003 12/11/2003  
Routing - PLANNING12/11/2003 12/11/2003 PASS
Approved per CZC03-169.
Plan resubmittals received  12/10/2003 DONE
Received transmittal letter with a letter to Ron and two sets of sheets A1.0, A2.0 taken to Ron
Routing - FIRE12/5/2003 12/8/2003 FAIL
DetailsBill Alexander
Need information in regards to IFC 23, 27 and 34. Reference attached review comments.
Plan Review Completed(1st rev)  12/8/2003 DONE
Routing - PLAN CHECK11/19/2003 12/5/2003 FAIL
Faxed and mailed corrections to the architect on 12/5/03, Routed plans to the fire department same day.
Routing - PLANNING11/17/2003 11/19/2003 FAIL
Exterior does not comply with CZC03-169.
Routing - PUBLIC WORKS11/14/2003 11/17/2003 PASS
Plans ACCEPTED BY PLAN TECH  11/13/2003 DONE
Application received  11/12/2003  
Recd Pcfee & Taken To Pln CK  11/12/2003 DONE
Fee Review-notes11/12/200311/12/2003