Second Notice BLD | 4/26/2005 | 4/26/2005 | 4/27/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 6/3/2004 | 4/26/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 6/3/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10177 issued 6-3-04 to Micron Technology, Inc.
|
BLD-Final | 5/13/2004 | 5/14/2004 | 5/14/2004 | A | PASS |
Jim Storey
|
|
|
Jim...Rick will sign off am tomorrow...he has already looked at it...P&Z are supposed to come out am as well...Ill buzz you when that is done!; Phone #: ###-#### Internet Inspection Request from: Wayne Berry final ok 5/14/2004 10:51:32 AM
|
Code Occupancy Approval | 5/14/2004 | 5/14/2004 | 5/14/2004 | A | PASS |
Wm. Michael Meloy
|
|
|
Compliance met. 5/14/2004 11:12:55 AM
|
Permanent Occupancy | | 5/14/2004 | 5/14/2004 | | DONE |
|
|
|
|
Permanent Occupancy | | 5/14/2004 | 5/14/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 5/13/2004 | 5/13/2004 | 5/13/2004 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 5/13/2004 at 7:43:47 AM. Contact: ###-####. No card to sign - final okay 5/13/2004 2:32:52 PM
|
BLD-Conference | 5/6/2004 | 5/7/2004 | 5/7/2004 | A | PASS |
Jim Storey
|
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry wip ok 5/7/2004 10:51:02 AM
|
FIRE-Final Inspection | 4/12/2004 | 4/13/2004 | 4/13/2004 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/12/2004 at 1:29:17 PM. Contact: ###-####. Phased project - okay to use stairs 4/13/2004 11:20:16 AM
|
FIRE-Final Inspection | 4/9/2004 | 4/9/2004 | 4/9/2004 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/9/2004 at 6:13:35 AM. Contact: ###-####. door closures on stairs; floor covering; need to test the detectors for door release; expansion joint not installed 4/9/2004 9:29:41 AM
|
BLD-Final | 4/9/2004 | 4/9/2004 | 4/9/2004 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 4/9/2004 at 6:14:22 AM. Contact: ###-####. fire stop 1/1/2pipe 4/12/2004 12:33:21 PM
|
BLD-Final | 4/1/2004 | 4/2/2004 | 4/2/2004 | A | PART |
Jim Storey
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Darla Downs 2 nd floor ok restarooms. 4/2/2004 11:15:20 AM
|
FIRE-Final Inspection | 4/1/2004 | 4/1/2004 | 4/1/2004 | P | PART |
Rick Jackson
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Darla Downs okay to use second floor restrooms 4/1/2004 3:44:42 PM
|
BLD-Final | 4/1/2004 | 4/1/2004 | 4/1/2004 | P | CANC |
Jim Storey
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Darla Downs rolled over to am. 4/1/2004 4:27:36 PM
|
(F) Reprint permit | | | 3/26/2004 | | DONE |
|
|
|
|
BLD-Final | 3/24/2004 | 3/25/2004 | 3/25/2004 | A | PART |
Jim Storey
|
|
|
first floor men and womans restarm. ok for occ. use with progration of permited work. 3/25/2004 10:21:56 AM
|
BLD-Final | 3/23/2004 | 3/24/2004 | 3/24/2004 | A | NR |
Jim Storey
|
|
|
WAYNE; Phone #: ###-#### Internet Inspection Request from: Darla Downs rolled over to am. 3/24/2004 4:19:05 PM
|
Plan Reviewer's activity | | | 3/24/2004 | | PASS |
|
|
|
Reviewed and approved plan modification request to downgrade the one-hour corridor to nonrated construction at Corridor 100A per 200 IBC, TAble 1004.3.2.1. It has been determined that the currently installed sprinkler system does comply with IBC Section 903.3.1.1.
|
FIRE-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 | P | PART |
Rick Jackson
|
|
|
okay to use first floor restrooms only
|
BLD-Conference | 3/19/2004 | 3/22/2004 | 3/22/2004 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 3/19/2004 at 11:28:41 AM. Contact: ###-####. loand 117 a to wyane. 3/22/2004 10:48:53 AM
|
Plan resubmittals received | | | 3/22/2004 | | DONE |
|
|
|
Received a response letter, two sets of sheets A2.1,A2.2,A3.1 taken to John M.
|
BLD-Conference | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 3/19/2004 at 11:28:41 AM. Contact: ###-####. out of time. rolled over. 3/19/2004 4:41:45 PM
|
BLD-Conference | 3/10/2004 | 3/10/2004 | 3/10/2004 | P | PART |
Jim Storey
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Darla Downs pending resubmatal for reduction in rated corridor. pending info. 3/10/2004 3:50:48 PM
|
BLD-Framing/Rough-in | 3/5/2004 | 3/5/2004 | 3/5/2004 | P | PART |
Jim Storey
|
|
|
Call Joe Dalsoglio at Ext. 81086; Phone #: ###-#### Internet Inspection Request from: Dennis Holmes ok to cover shaft wall with 5/8 gyp. 3/5/2004 1:30:53 PM
|
BLD-Framing/Rough-in | 2/23/2004 | 2/23/2004 | 2/23/2004 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 6:39:41 AM. Contact: ###-####. rolled to pm. 2/23/2004 11:02:51 AM
|
FIRE-Sprinkler Rough-in | 2/23/2004 | 2/23/2004 | 2/23/2004 | P | PART |
Rick Jackson
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover hard lids on first floor restroom; need resubmittals per plan review notes 2/23/2004 1:41:43 PM
|
BLD-Framing/Rough-in | 2/23/2004 | 2/23/2004 | 2/23/2004 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/23/2004 at 6:39:41 AM. Contact: ###-####. walls ok for cover 1 st floor. 2/23/2004 4:17:45 PM
|
BLD-Conference | 2/5/2004 | 2/6/2004 | 2/6/2004 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/5/2004 at 2:22:32 PM. Contact: ###-####. exterior walls ok to insulate. 2/6/2004 10:16:20 AM
|
BLD-Footing | 2/2/2004 | 2/4/2004 | 2/4/2004 | P | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 2/2/2004 at 1:41:54 PM. Contact: ###-####. Talked to Mike Mitchell......MTI on site for Special insp. Will Re-call this insp in for 2/5 am 2/4/2004 12:15:53 PM
|
BLD-Framing/Rough-in | 2/3/2004 | 2/3/2004 | 2/3/2004 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/2/2004 at 1:41:32 PM. Contact: ###-####. wip 2/3/2004 3:59:08 PM
|
BLD-Framing/Rough-in | 2/2/2004 | 2/3/2004 | 2/3/2004 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/2/2004 at 1:41:32 PM. Contact: ###-####. cloned 2/3/2004 11:29:30 AM
|
BLD-Framing/Rough-in | 1/27/2004 | 1/30/2004 | 1/30/2004 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/27/2004 at 12:20:53 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 1/27/2004 | 1/29/2004 | 1/29/2004 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/27/2004 at 12:20:32 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 1/27/2004 | 1/28/2004 | 1/28/2004 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/27/2004 at 12:20:13 PM. Contact: ###-####. wip 1/28/2004 3:36:57 PM
|
BLD-Framing/Rough-in | 1/21/2004 | 1/26/2004 | 1/26/2004 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/21/2004 at 1:26:16 PM. Contact: ###-####. wip 1/26/2004 2:33:15 PM
|
BLD-Framing/Rough-in | 1/21/2004 | 1/26/2004 | 1/26/2004 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/21/2004 at 1:26:52 PM. Contact: ###-####. wall clip to beam justified and being reinstaled. 1/26/2004 11:08:07 AM
|
BLD-Framing/Rough-in | 1/21/2004 | 1/22/2004 | 1/22/2004 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/21/2004 at 1:25:57 PM. Contact: ###-####. exterior wall inprogess clip slip conection to be addressed. 1/22/2004 12:01:44 PM
|
BLD-Concrete | 12/19/2003 | 12/23/2003 | 12/23/2003 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/19/2003 at 9:26:11 AM. Contact: ###-####.
|
BLD-Concrete | 12/22/2003 | 12/22/2003 | 12/22/2003 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/19/2003 at 9:25:48 AM. Contact: ###-####. wip 12/22/2003 2:45:01 PM
|
BLD-Concrete | 12/19/2003 | 12/22/2003 | 12/22/2003 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/19/2003 at 9:25:48 AM. Contact: ###-####.
|
BLD-Concrete | 12/19/2003 | 12/19/2003 | 12/19/2003 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/19/2003 at 9:25:25 AM. Contact: ###-####. wip 12/19/2003 4:48:58 PM
|
BLD-Conference | 12/16/2003 | 12/17/2003 | 12/17/2003 | A | CANC |
Jim Storey
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes via phone call from wyane. 12/17/2003 8:42:10 AM
|
BLD-Footing | 12/11/2003 | 12/16/2003 | 12/16/2003 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/11/2003 at 3:36:49 PM. Contact: ###-####. wip 12/16/2003 1:43:49 PM
|
BLD-Footing | 12/11/2003 | 12/15/2003 | 12/15/2003 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/11/2003 at 3:36:09 PM. Contact: ###-####.
|
BLD-Footing | 12/11/2003 | 12/15/2003 | 12/15/2003 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/11/2003 at 3:36:29 PM. Contact: ###-####. wip slab on grade. 12/15/2003 1:13:35 PM
|
BLD-Conference | 12/10/2003 | 12/12/2003 | 12/12/2003 | P | PASS |
Jim Storey
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 2:00 pm 12/11/2003 9:59:34 AM
|
FIRE-Conference | 12/10/2003 | 12/12/2003 | 12/12/2003 | P | PART |
Rick Jackson
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with Wayne about occupying this project in phases 12/12/2003 4:07:13 PM
|
BLD-Footing | 12/11/2003 | 12/12/2003 | 12/12/2003 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/11/2003 at 3:35:52 PM. Contact: ###-####.wip 12/12/2003 3:17:25 PM
|
BLD-Footing | 12/5/2003 | 12/10/2003 | 12/10/2003 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/5/2003 at 2:13:05 PM. Contact: ###-####. wip 12/10/2003 9:17:55 AM
|
BLD-Footing | 12/5/2003 | 12/9/2003 | 12/9/2003 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/5/2003 at 2:10:40 PM. Contact: ###-####. wip 12/9/2003 10:31:38 AM
|
BLD-Footing | 12/5/2003 | 12/8/2003 | 12/8/2003 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/5/2003 at 2:12:46 PM. Contact: ###-####. reports pending. 12/8/2003 11:01:23 AM
|
Permit Ready to Issue | | | 12/4/2003 | | DONE |
|
|
|
|
Telephone call | | | 12/4/2003 | | DONE |
|
|
|
e-mailed Paul -- permit is ready.
|
Issue & PRINT to be Invoiced | | | 12/4/2003 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 11/20/2003 | 11/20/2003 | 12/2/2003 | | PASS |
John Menard
|
|
|
12/2/2003 09:43:35 JCM - activity updated through activity BLDA022 from case BLD03-02811.
|
Routing - PLAN CHECK | 12/2/2003 | | 12/2/2003 | | PASS |
|
|
|
|
Routing - FIRE | 11/26/2003 | | 12/2/2003 | | PASS |
Bill Alexander
|
|
|
|
Plan Review Completed(1st rev) | | | 12/2/2003 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/2/2003 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 12/2/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/2/2003 | | DONE |
|
|
|
|
Plan Review Completed(1st rev) | | | 12/2/2003 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 11/25/2003 | | 11/26/2003 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 11/26/2003 | | PASS |
|
|
|
Plans approved as submitted with attached comment list. JCM
|
Routing - PLUMBING | 11/21/2003 | | 11/21/2003 | | PASS |
|
|
|
per plans and 2000 upc
|
Routing - PUBLIC WORKS | 11/20/2003 | | 11/21/2003 | | PASS |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 11/20/2003 | | |
|
|
|
|
Application received | | | 11/18/2003 | | |
|
|
|
|
Fee Review-notes | 11/18/2003 | 11/18/2003 | | | |
|
|
|
|