Case Summary (BLD) | | | 12/15/2010 | | |
|
|
|
|
Second Notice BLD | 9/25/2006 | 9/25/2006 | 9/26/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 8/18/2006 | 9/25/2006 | | DONE |
|
|
|
|
Permanent occupancy | | | 8/18/2006 | | DONE |
|
|
|
Perm. Occ. Cert. # 11174 issued 8-18-06 to the Viziato Spa/Salon
|
Second Notice BLD | 7/7/2006 | 7/7/2006 | 7/7/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 6/19/2006 | 6/19/2006 | 7/7/2006 | | DONE |
Mike Jordan
|
|
|
|
BLD-Aging Inspection | 6/19/2006 | 6/19/2006 | 6/19/2006 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Finaled | 6/19/2006 | 6/19/2006 | 6/19/2006 | P | PASS |
Mike Jordan
|
|
|
life/safety has finaled. ok.
|
Permanent Occupancy | | 6/19/2006 | 6/19/2006 | | DONE |
|
|
|
|
BLD-Aging Inspection | 4/10/2006 | 4/10/2006 | 4/10/2006 | | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 4/10/2006 | 4/10/2006 | 4/10/2006 | A | DONE |
Mike Jordan
|
|
|
|
BLD-Final | 9/9/2005 | 9/9/2005 | 9/9/2005 | P | NR |
Mike Jordan
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Aging Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | | NR |
Tom Arcoraci
|
|
|
exp
|
BLD-Aging Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 | | PASS |
Tom Arcoraci
|
|
|
ok for final now that fire is finaled
|
FIRE-Final Inspection | 2/8/2005 | 2/8/2005 | 2/8/2005 | P | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 2/8/2005 12:26:24 PM
|
FIRE-Final Inspection | 2/3/2005 | 2/3/2005 | 2/3/2005 | P | PART |
Troy Cobbley
|
|
|
Scott; Phone #: ###-#### A temporary occupancy was given until the arrows are fixed in the exit sign in the spa or it has been turned. 2/3/2005 2:44:52 PM
|
FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|
FIRE-Final Inspection | 2/2/2005 | 2/2/2005 | 2/2/2005 | P | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light at the main entrance. Repair the exit sign at the north end of the back corridor. Install fire extinguisher at the front entrance. Turn the exit sign in the spa area to point the right way or delete arrow. 2/2/2005 3:38:19 PM
|
FIRE-Final Inspection | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | FAIL |
Rick Jackson
|
|
|
Fire sprinkler anti-freeze okay per test reports from Grinnel; need fire extinguishers; key lock at main exit; add exit signs per plans and relocate one; need to test exit signs and emergency lights for battery back-up 2/1/2005 3:05:39 PM
|
BLD-Final | 1/31/2005 | 1/31/2005 | 1/31/2005 | P | PART |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
Temp. C of O OK pending fire insp. temp. occ. approval. 1/31/2005 4:03:45 PM
|
BLD-Framing/Rough-in | 11/29/2004 | 11/29/2004 | 11/29/2004 | P | PART |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice
framing @ Interior "dome" ok per eng. design. 11/29/2004 1:41:38 PM
|
BLD-Framing/Rough-in | 11/17/2004 | 11/18/2004 | 11/18/2004 | P | FAIL |
Lane Manuel
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner
need to provide additional firestopping mat'l @ rear of space.
need rough fire sprinkler approval ? 11/18/2004 1:35:22 PM
|
BLD-Framing/Rough-in | 11/15/2004 | 11/16/2004 | 11/16/2004 | A | FAIL |
Jim Sly
|
|
|
Scott; Phone #: ###-#### Internet Inspection Request from: Jan Rice C/N posted. 11/16/2004 5:02:45 PM
|
BLD-Final | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | CANC |
Jim Storey
|
|
|
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Final | 10/26/2004 | 10/27/2004 | 10/27/2004 | A | CANC |
Jim Storey
|
|
|
brian --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIRE-Final Inspection | 10/27/2004 | 10/27/2004 | 10/27/2004 | P | FAIL |
Troy Cobbley
|
|
|
Tamper zone was set up as a trouble zone not a supervisory zone. Monitoring station did not receive all of the trouble signals. Need junction box at valve for the wire splices. 10/27/2004 4:02:38 PM
|
BLD - Request for Extension | 10/21/2004 | 10/22/2004 | 10/22/2004 | | PASS |
Tom Arcoraci
|
|
|
Still working on this project Kim Stark ###-####
|
BLD-Aging Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 | | NR |
Troy James
|
|
|
|
Issue PAID IN FULL permit | | | 2/19/2004 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 12/22/2003 | | 2/17/2004 | | PASS |
Carl Westfall
|
|
|
2/17/2004 08:38:30 CJW - activity updated through activity BLDA022 from case BLD03-02995.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2004 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/17/2004 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 2/17/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/17/2004 | | DONE |
|
|
|
|
Telephone call | | | 2/17/2004 | | DONE |
|
|
|
spoke with Justin Wall -- permit is ready. spoke with Chad Olsen -- permit is ready.
|
Routing - PUBLIC WORKS | 2/12/2004 | | 2/13/2004 | | DONE |
|
|
|
Sent back for recalculation of sewer fees.
|
Routing - PLAN CHECK | 1/20/2004 | | 2/12/2004 | | PASS |
|
|
|
(2-2-04) Failed second IBC plan review. Drawings on hold until resubmittals are received. Then send back to PW for sewer fee revisions. (2-12-04) The drawings were approved after the resubmittal review.
|
Plan resubmittals received | | | 2/10/2004 | | DONE |
|
|
|
Received letter of transmittal with two sets of sheets A-1.1,A-1.2,M1,M2,M3,M4,M5,M6,E1.0,E2.0,E3.0E4.0, taken to Carl W.
|
Telephone call | | | 2/2/2004 | | DONE |
|
|
|
Called the architect's representative, Justin Wall, and asked for the dressing room to be designed to be accessible to the disabled (or be deleted) and asked for revised plumbing, mechanical, and electrical drawings. Drawings on hold until resubmittals are received. Followed up our conversation with an E-mail to the architect.
|
Plan resubmittals received | | | 1/29/2004 | | DONE |
|
|
|
Received letter of transmittal with response letter attached and two sets of sheets CVR,A-1.2,A-1.3. Taken to Carl W.
|
Routing - PLUMBING | 1/20/2004 | | 1/20/2004 | | PASS |
|
|
|
1. building may require backflow protection and thermal expansion protection 2. water heater may require a pan with a drain
|
Routing - FIRE | 1/13/2004 | | 1/16/2004 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 12/30/2003 | | 1/13/2004 | | |
|
|
|
Failed first IBC plan review. IBC plan review started January 7, 2004 and was finished January 13, 2004. A response from the architect was required. See the plan review report. A copy was E-mailed to the architect.
|
Routing - PUBLIC WORKS | 12/26/2003 | | 12/30/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 12/17/2003 | | DONE |
|
|
|
|
Application received | | | 12/16/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/16/2003 | | |
|
|
|
|
Fee Review-notes | 12/16/2003 | 12/16/2003 | | | |
|
|
|
|