Second Notice BLD | 10/10/2005 | 10/10/2005 | 10/10/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 9/22/2005 | 10/10/2005 | | DONE |
|
|
|
|
BLD-Final | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | PASS |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok for perm occ
|
FIRE-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | PASS |
Troy Cobbley
|
|
|
FIre life safety finaled. The electrician needs to install two additional bulbs in emergency lights that will be shown to the structural inspector during his inspection.
|
Permanent Occupancy | | 9/22/2005 | 9/22/2005 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 9/22/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10742 issued 9-22-05 to the Idaho Youth Ranch, Hays House II.
|
PubWorks Occupancy Approval | 9/2/2005 | 9/2/2005 | 9/2/2005 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 9/2/05. G.Fitts
|
Print Occupancy Form | | | 8/11/2005 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 8/10/2005 | 8/10/2005 | 8/10/2005 | P | PASS |
Tom Arcoraci
|
|
|
ceiling grid inspection///jerry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
BLD-Aging Inspection | 7/7/2005 | 7/7/2005 | 7/14/2005 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 5/2/2005 | 5/3/2005 | 5/3/2005 | A | CANC |
Jim Sly
|
|
|
dry wall inspection please////jerry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Tom 408 said no drywall insp needed... no rated walls. 5/3/2005 11:00:34 AM
|
BLD-Energy code compliance | 4/20/2005 | 4/21/2005 | 4/21/2005 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Energy code compliance | 4/19/2005 | 4/20/2005 | 4/20/2005 | P | PASS |
Dave Hannah
|
|
|
jerry ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 4/13/2005 | 4/14/2005 | 4/14/2005 | P | PASS |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 3/2/2005 | 3/3/2005 | 3/3/2005 | A | PART |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to one side mech 3/3/2005 9:20:05 AM
|
BLD-Framing/Rough-in | 2/23/2005 | 2/24/2005 | 2/24/2005 | A | PART |
Dave Hannah
|
|
|
Jerry; Phone #: ###-#### Internet Inspection Request from: Jan Rice mec rooms framing ok told contractor that he needed to get all other trades r/i signed off and insulate thin call for an energy insp 2/24/2005 11:38:01 AM
|
BLD-Framing/Rough-in | 1/3/2005 | 1/4/2005 | 1/4/2005 | A | PART |
Tom Arcoraci
|
|
|
Jerry; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok to side ext 1/4/2005 9:56:16 AM
|
BLD-Framing/Rough-in | 12/17/2004 | 12/20/2004 | 12/20/2004 | A | PART |
Tom Arcoraci
|
|
|
Jerry; Phone #: ###-#### Internet Inspection Request from: Jan Rice partial roof nailing ok 12/20/2004 8:52:22 AM
|
BLD-Framing/Rough-in | 10/21/2004 | 10/22/2004 | 10/22/2004 | A | PART |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie WI[ OK 10/22/2004 9:19:01 AM
|
BLD-Footing | 10/13/2004 | 10/14/2004 | 10/14/2004 | P | PASS |
Jim Storey
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Footing | 10/8/2004 | 10/11/2004 | 10/11/2004 | A | PASS |
Tom Arcoraci
|
|
|
idaho youth ranch; Phone #: ###-#### Internet Inspection Request from: Barbara Moore wip ok 10/11/2004 8:58:32 AM
|
BLD-Foundation | 9/27/2004 | 9/28/2004 | 9/28/2004 | P | PART |
Lane Manuel
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
stemwalls @ remaining area, and column bases ok 9/28/2004 3:40:41 PM
|
BLD-Footing | 9/15/2004 | 9/17/2004 | 9/17/2004 | A | PASS |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wip ok 9/17/2004 8:50:55 AM
|
BLD-Foundation | 8/31/2004 | 9/1/2004 | 9/1/2004 | P | PASS |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore wip ok 9/1/2004 2:34:28 PM
|
BLD-Footing | 8/19/2004 | 8/20/2004 | 8/20/2004 | P | PART |
Tom Arcoraci
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles west wing ok 8/20/2004 4:23:57 PM
|
BLD-Aging Inspection | 7/28/2004 | 7/28/2004 | 7/28/2004 | | NR |
Tom Arcoraci
|
|
|
|
(F) Reprint permit | | | 4/29/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/28/2004 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 4/28/2004 | | DONE |
|
|
|
|
Telephone call | | | 4/7/2004 | | DONE |
|
|
|
talked to jerry hines to verify plans are ready & need a.c.h.d.
|
Routing - FIRE | 3/3/2004 | | 3/5/2004 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 3/5/2004 | | 3/5/2004 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/2004 | | PASS |
|
|
|
|
Print Occupancy Form | | | 3/5/2004 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 1/5/2004 | | 3/5/2004 | | PASS |
John Menard
|
|
|
3/5/2004 09:38:44 JCM - activity updated through activity BLDA022 from case BLD03-03049.
|
Routing - PLAN CHECK | 2/23/2004 | | 3/3/2004 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 3/3/2004 | | PASS |
|
|
|
Reviewed and approved resubmiited plan sheets and information. JCM
|
Plan resubmittals received | | | 2/25/2004 | | DONE |
|
|
|
Received three copies of revised sheets A2.1, A5.2, A5.5, M1.1, M3.1, M3.2, C1.2, P1.2 & E2.0F. One copy of respnse letter each to John M and Sam R. One copy of 1YR leeter of explanation and one copy of United Water Idaho letter on Fire Flow. Routed to John M. kmm
|
Routing - PUBLIC WORKS | 2/18/2004 | | 2/23/2004 | | PASS |
|
|
|
|
Routing - FIRE | 2/6/2004 | | 2/17/2004 | | FAIL |
|
|
|
Sprinkler, waterflow and delayed egress lock issues; review faxed to architect and attached.
|
Routing Off Site -Energy | 1/28/2004 | | 2/3/2004 | | PASS |
|
|
|
Contacted Ron O for energy review on resubmittal. kmm Received a copy of the energy approval via e-mail. JCM
|
Routing - PLAN CHECK | 1/29/2004 | | 2/2/2004 | | |
|
|
|
|
Routing - PLANNING Land Div | 2/2/2004 | | 2/2/2004 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 2/2/2004 | | |
|
|
|
E-mailed the architect a copy of the plan review comment list and cover letter requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 1/28/2004 | | 1/29/2004 | | PASS |
|
|
|
Contacted PDQ for outside engineering on resubs. kmm Received letter from consulting structural engineer approving resubmittals. JCM
|
Plan resubmittals received | | | 1/29/2004 | | DONE |
|
|
|
Received five copies of revised sheets C1.1, C1.2 and one copy of storm drain calculations, revised drainage report and geotechnical addendum. Routed to John M. kmm
|
Routing - Erosion and Sediment | 1/26/2004 | | 1/29/2004 | | PASS |
|
|
|
ESC approved with conditons attached to plans.
|
Routing - PUBLIC WORKS | 1/21/2004 | | 1/26/2004 | | FAIL |
|
|
|
Requires drainage plan revisions.
|
Plan resubmittals received | | | 1/23/2004 | | DONE |
|
|
|
Received three copies of revised sheets S1.0, A5.6 and three copies of response letter to Structural review comments. Routed to John M. kmm
|
Routing - PLAN CHECK | 1/16/2004 | | 1/21/2004 | | |
|
|
|
|
Plan resubmittals received | | | 1/20/2004 | | |
|
|
|
Received two copies of ESC plan, narrative, application and five copies of sheet C1.1 and drainage calcs.. Routed to John M. kmm
|
Routing - Erosion and Sediment | 1/12/2004 | | 1/15/2004 | | FAIL |
|
|
|
Plan designer not certified by Boise City. Plan does not meet requrements of BCC8-17 or EPA SWPPP requirements. Left voice mail with Mike Jones.
|
Plan resubmittals requested | | | 1/15/2004 | | |
|
|
|
Faxed the architect a copy of the plan review comment list from the consulting structural engineer requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 1/5/2004 | | 1/14/2004 | | FAIL |
|
|
|
Contacted PDQ to take plans to outside engingeering. kmm Received a comment list from the consulting structural engineer requesting revisions. JCM
|
Routing - PLAN CHECK | 1/8/2004 | | 1/12/2004 | | |
|
|
|
|
Routing Off Site - C.D.H | 1/7/2004 | | 1/8/2004 | | PASS |
|
|
|
Pat Walsh picked up plans for CDH review. kmm
|
Routing - PLAN CHECK | 1/7/2004 | | 1/7/2004 | | |
|
|
|
|
Routing - PLUMBING | 1/5/2004 | | 1/6/2004 | | PASS |
|
|
|
PROVIDE A FLOOR SINK AND INDIRECT PREP SINK IN KITCHEN WITH AIR GAP.
|
Routing Off Site -Energy | 12/31/2003 | | 1/6/2004 | | FAIL |
|
|
|
Contacted Ron O for energy review. kmm Received an e-mail from the energy review person requesting resubmittals. JCM
|
Plan resubmittals received | | | 1/5/2004 | | DONE |
|
|
|
Received two copies of ESC plan, narrative and application. Routed to John M. kmm
|
Routing - PLANNING | 1/2/2004 | | 1/5/2004 | | PASS |
|
|
|
CUP03-00012
|
Pending Assignment by JCM | 12/26/2003 | | 1/5/2004 | | DONE |
John Menard
|
|
|
1/5/2004 09:01:15 JCM - activity updated through activity BLDA166 from case BLD03-03049.
|
Routing - Erosion and Sediment | 12/31/2003 | | 1/2/2004 | | FAIL |
|
|
|
No ESC plan submitted. Informed P. Walsh ###-####
|
Routing - PUBLIC WORKS | 12/29/2003 | | 12/30/2003 | | FAIL |
|
|
|
Requires drainage plan revisions. Per Brian M. kmm
|
Routing - PLANNING Land Div | 12/26/2003 | | 12/29/2003 | | FAIL |
|
|
|
Need recorded deed with metes and bounds description describing parcel as one parcel. Also need tax parcel #.
|
Plans ACCEPTED BY PLAN CHECK | | | 12/29/2003 | | PEND |
|
|
|
Sheets S3.3 and S3.4 signed by engineer. Still waiting for ESC application, plan and narrative. CDH is required. Contacted Pat Walsh to pick up plans and take to Frank of CDH. kmm
|
Plans ACCEPTED BY PLAN TECH | | | 12/26/2003 | | FAIL |
|
|
|
Plans accepted by the front desk without ESC application, plans or narrative. Sheets S3.3 and S3.4 not signed. Notified Pat Walsh of this need. kmm
|
Plan routing begun/NEW & ADDTN | | | 12/26/2003 | | DONE |
|
|
|
|
Application received | | | 12/23/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/23/2003 | | |
|
|
|
|
Fee Review-notes | 12/23/2003 | 12/23/2003 | | | |
|
|
|
|