Permit Information
Permit NumberBLD04-00031
StatusFinaled
Name CORTLAND MORGAN
Site Address 200 N 6TH ST
Project NameCENTRAL FIRE STATION
Customer Number 
ePlanReviewNo
Description
(MELTING POT - OLD CENTRAL FIRE STATION BLDG) This building is required to be fire sprinklered to allow an A-2 Occupancy, to allow the unprotected openings in the East wall, to allow the basement to be unenclosed, and for story increase. To create a 4,670 square foot restaurant on the first floor of an existing 2 story building. This project is a change of occupancy. The first floor has a total floor area of 4,900 square feet. Operations that produce grease laden vapors and/or produce smoke are not allowed within this tenant space except for limited operations as approved by the Fire Department. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, finishes, booths, an exterior landing at the North door, and a bar all per the approved drawings and the plan review report on file. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD5/20/20055/20/200512/9/2005 DONE
Second Notice has not been responded to.///Over a year old No final values
Second Notice BLD4/26/20054/26/20055/20/2005 DONE
First Notice has not been responded to.
First Notice 2/3/20054/26/2005 DONE
BLD-Aging Inspection8/18/20048/18/20048/18/2004 PASS
DetailsDave Hannah
BLD-Final6/16/20046/17/20046/17/2004PPASS
DetailsDave Hannah
rick-- ###-#### ok for perm occ 6/17/2004 3:19:51 PM
Permanent Occupancy 6/17/20046/17/2004 DONE
Details
Permanent occupancy  6/17/2004 DONE
Perm. Occ. Cert. # 10191 issued 6-17-04 to The Melting Pot.
FIRE-Final Inspection5/27/20045/28/20045/28/2004APASS
DetailsRick Jackson
rick; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Final5/27/20045/28/20045/28/2004PPART
DetailsTom Arcoraci
rick ###-#### ok for temp check tp holders in baths and exit sign in bar area 5/28/2004 2:57:46 PM
Temporary occupancy  5/28/2004 DONE
Temp. Occ. cert. # 5116 issued 5-28-04 tothe Melting Pot.
BLD-Conference5/25/20045/26/20045/26/2004APART
DetailsRuss Owen
bruce; Phone #: ###-#### Internet Inspection Request from: Annette Moore Contractor wanted some info on 2 doors, access issues, on the plan review comments there is a note that they are to comply with building code 1/4" min slope etc. 5/26/2004 1:49:59 PM
BLD-Framing/Rough-in5/21/20045/24/20045/24/2004PPASS
DetailsTom Arcoraci
rick; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie grid ok 5/24/2004 4:24:27 PM
FIRE-Conference5/24/20045/24/20045/24/2004PPART
DetailsRick Jackson
Met with Rick about items for final: need to test all emergency/exit signs for battery back-up; remove deadbolts from exit doors; provide occupant load sign; install fire extinguishers 5/24/2004 4:35:25 PM
BLD-Framing/Rough-in5/18/20045/19/20045/19/2004PPART
DetailsDave Hannah
rick ceiling inspect in kitchen; Phone #: ###-#### Internet Inspection Request from: Annette Moore ceiling in kitchen ok 5/19/2004 3:55:08 PM
BLD-Framing/Rough-in5/6/20045/6/20045/6/2004PPART
DetailsDave Hannah
tim; Phone #: ###-#### Internet Inspection Request from: Annette Moore new roof framing for air handler ok 5/6/2004 3:01:14 PM
BLD-Wall cover4/9/20044/12/20044/12/2004APART
DetailsTroy James
tim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
Provide 48" clearance at hallway between restrooms. Ok to cover walls other areas. 4/12/2004 10:08:15 AM
Inspection Record Card- Bld  3/15/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/10/2004 DONE
Print Occupancy Form  3/10/2004 DONE
Telephone call  3/10/2004 DONE
permit ready and fee due
Permit Ready to Issue  3/10/2004 DONE
Issue PAID IN FULL permit  3/10/2004 DONE
Plan assigned to (CJW)1/12/2004 3/10/2004 PASS
DetailsCarl Westfall
3/10/2004 16:02:01 CJW - activity updated through activity BLDA022 from case BLD04-00031.
Routing - FIRE3/6/2004 3/9/2004 PASS
acceptble per resubmittal
Routing - PLAN CHECK2/18/2004 3/6/2004 PASS
Drawings approved after resubmittal review.
Plan resubmittals received  3/1/2004 DONE
Received response letter, Plan review report with project information, two sets of sheets A1.1,A1.2,A4.2,M-1,M-2,M-3, taken to Carl W.
Plan resubmittals received  2/23/2004 DONE
Received additional information regarding cooking operations relative to grease emissions; replied to by letter faxed to submitter Jay Walden.
Plan resubmittals received  2/19/2004 DONE
Received via fax, one copy of plan review response to Carl W., one copy of fire alarm system installation memo and one memo reguarding handicap access to the patio dining. Routed to Carl W. kmm
Routing - PLUMBING2/18/2004 2/18/2004 PASS
backflow preventors must be within 5' of the floor, rout waste from hand sink at the bar to a floor sink, all indirect waste receptors must be kept out from under cabinets and equipment, pipe grease trap to a floor sink, cooler hub drain trap must be with in 5' of its vent, additional cross connection protection may be required, if an automatic soap dispensor is installed at the mop sink, provide a water supply for it.
Routing - PLAN CHECK2/17/2004 2/17/2004  
Routing - FIRE2/6/2004 2/14/2004  
Failed first IFC code. Sprinkler valving and water information required; review comments faxed to architect and attached.
Routing - PLAN CHECK1/20/2004 2/6/2004  
Failed first IBC plan reveiw. IBC plan review started February 2, 2004 and was finished February 6, 2004. A response from the archtiect was required. See the plan review report. A copy was E-mailed to the architect.
Plan resubmittals received  1/30/2004 DONE
Received four sets of sheets P-1,P2,P3,P4 taken to Carl W.
Plan resubmittals received  1/28/2004 DONE
Received via fax the details on plumbing routed to Ron G. Ron G wanted these details to go with the plans. Routed to Carl W on 2/10/04. kmm
Routing - PLUMBING1/20/2004 1/20/2004  
Failed first UPC review. drawings must meet the 2000 uniform plumbing code
Routing - PUBLIC WORKS1/12/2004 1/16/2004 PASS
Plans ACCEPTED BY PLAN TECH  1/13/2004 DONE
Received five copies of sheet E5.0 for energy lighting compliance. Routed to Carl W. kmm Per Jim Rogers, plans are to have ESC permit with waiver letter for the interior demo work, due to downtown proximity. kmm
Plans ACCEPTED BY PLAN TECH  1/12/2004 PEND
Called David Hiatt to let him know we needed energy compliance. Received fax letting us know that the energy sheets are to follow this fax.
No Planning review required per Marty Santoyo.
Application received  1/9/2004  
Recd Pcfee & Taken To Pln CK  1/9/2004  
Fee Review-notes1/9/20041/9/2004   
Routing - PLAN CHECK3/10/2004