Permit Information
Permit NumberBLD04-00279
StatusFinaled
Name BENCHMARK CONSTRUCTION
Site Address 110 N CURTIS RD
Project NameHAZ-MAT HIGH-PILED STORAGE
Customer Number 
ePlanReviewNo
Description
Brico Of Idaho * Install Racking. To install building access through the east (back) wall into an existing tank storage area which will now go away (not be allowed) due to the a south containment wall being demolished. Also to install 7 new automatic and manual smoke heat vents in the High-Piled Combustible storage area of this facility. All per approved plans on file.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Letter of compliance  9/13/2004 DONE
Letter of Compliance issued 9-13-04.
FIRE-Final Inspection9/1/20049/2/20049/2/2004APASS
DetailsTroy Cobbley
Fire life safety finaled. Overspacing of the smoke heat vents was approved by Dave Miller on 9-1-04 as long as the approved smoke heat vents had been installed. Per the data sheets the smoke heat vents are approved. 9/2/2004 9:45:54 AM
BLD-Final9/1/20049/2/20049/2/2004PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 9/1/2004 at 4:55:00 PM. Contact: ###-####. ok for perm 9/2/2004 3:13:58 PM
BLD-Final8/30/20048/31/20048/31/2004PPART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 8/30/2004 at 8:19:48 PM. Contact: ###-####. needs fire ok 8/31/2004 3:32:43 PM
FIRE-Final Inspection8/30/20048/31/20048/31/2004AFAIL
DetailsTroy Cobbley
Space heat vents are overspaced. See review note "C". Provide data sheet for revised smoke heat vents. Manual type, as approved, was not installed. 8/31/2004 5:15:43 PM
BLD-Final8/30/20048/31/20048/30/2004ACANC
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 8/30/2004 at 5:14:16 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Aug 30 2004 8:18PM.
BLD-Final8/26/20048/27/20048/27/2004PNR
DetailsLane Manuel
Scheduled by a contractor via Hello! on 8/26/2004 at 3:27:09 PM. Contact: ###-####.
fire insp. has correction issues, and additional final insp. to do before bldg. dept. final 8/27/2004 3:22:24 PM
BLD-Footing8/20/20048/20/20048/20/2004PNR
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 8/20/2004 at 7:57:30 AM. Contact: ###-####.
BLD-Framing/Rough-in8/20/20048/20/20048/20/2004PNR
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 8/20/2004 at 7:58:14 AM. Contact: ###-####.
BLD-Final8/20/20048/20/20048/20/2004PNR
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 8/20/2004 at 7:58:59 AM. Contact: ###-####.
Issue PAID IN FULL permit  7/7/2004 DONE
Inspection Record Card- Bld  7/1/2004 DONE
Permit Ready to Issue  7/1/2004  
Telephone call  7/1/2004 DONE
left mess for trent koci at ###-#### that permit is ready
Routing - PLAN CHECK6/30/2004 6/30/2004 PASS
PLANS/APPL TAKEN TO FRONT DESK  6/30/2004 DONE
Plan assigned to (MLO)2/23/2004 6/30/2004 PASS
DetailsMike Otto
6/30/2004 09:39:20 MLO - activity updated through activity BLDA022 from case BLD04-00279.
Routing - FIRE6/28/2004 6/29/2004 PASS
DetailsBill Alexander
Routing - FIRE6/10/2004 6/15/2004 FAIL
DetailsBill Alexander
1. Lack "manual" part of the requirement for smoke heat venting.
2. Lack commodity type with maximum storage height requesting.

Called Trent Koci 10:25am, regarding "Tank Storage" access and he indicated that the "Tank Storage" is going away so end containmnet wall (for required back access door) is being demolished. Plan is redline corrected.

Faxed letter of requirements (attached).
Plan resubmittals received  6/7/2004 DONE
Received Transmittal Letter, 1 Set R-1 Taken to Mike Otto..
Routing - PLAN CHECK4/12/2004 4/12/2004 NR
Routing - FIRE4/7/2004 4/9/2004 FAIL
DetailsBill Alexander
1. Not met. The (warehouse) facility will require building access meeting the requirements of IFC Table 2306.6 or otherwise approval from the Fire Chief.
2. Did not provide manufacturer documentation on operations and listings of smoke heat vents.
3. Did not address maximum storage height of commodities.
4. Need updated HAZMAT inventory statement/analysis review due to added storage system.

Routing - PLAN CHECK4/7/2004 4/7/2004 PEND
need FD approval
Plan resubmittals received  4/6/2004 DONE
Received letter of transmittal with two cover letter, two copies of calculations for skylights, two copies of sheets R-1,R-2 taken to Mike O.
Routing - PLAN CHECK3/4/2004 3/5/2004 FAIL
IBC corrections in accordance with IFC review. Corrections faxed to applicant. MLO
Routing - FIRE3/3/2004 3/4/2004 FAIL
DetailsBill Alexander
A. Provide on the plan/s a standard and identifiable scale for dimensioning. (IFC 105.4.2)

B. This (warehouse) facility will require building access meeting the requirements of IFC Table 2306.6, which must be shown and associated with this building racking permit plans. Plans must include the whole unseperated warehouse along with outside building fire apparatus access. (IFC 105.4.2, 2301.3)

C. This (warehouse) facility will require smoke and heat removal meeting the requirements of IFC Table 2306.7, which must be shown and associated with this building racking permit plans. (IFC 105.4.2, 2301.3)

D. Provide on the plans the maximum storage height intending to incorporate in each or all racking (if similar) by identification. Fire sprinkler deflector's distance incorporating in this facility allow for a minimum 18" from top of any storage to deflector spacing. No storage shall be allowed above this minimum requirement. (NFPA 13:5-11.4.1).

E. Provide location of required fire extinguishers meeting requirements of IFC 2306.10 and 3403.2.1. Handle shall be mounted at 48" AFF. Extinguisher shall be conspicuously located where they will be readily accessible and immediately available in the event of fire or provided with identifiable signage which specifically identifies the extinguisher location.

F. Under delayed submittal and prior to installation, obtain a fire permit and approval after providing fire sprinkler plans, calculations and manufacturer data submittals meeting, but not limited too, the minimum requirements of IFC 2306.4, 2308. Submittals shall include, but may not be limited too the minimum requirements of NFPA 13 Chapter 14.
Plan Review Completed(1st rev)  3/4/2004 DONE
Routing - PLAN CHECK2/23/2004 3/3/2004 PEND
Pending Fire Code Review
Plans ACCEPTED BY PLAN TECH  2/23/2004 DONE
faxed over the certificate of value to get it signed.
Fee Review-notes2/20/20042/20/20042/20/2004 DONE
Application received  2/20/2004  
Recd Pcfee & Taken To Pln CK  2/20/2004 DONE