Permit Information
Permit NumberBLD04-00709
StatusFinaled
Name CM COMPANY
Site Address 925 N CLOVERDALE RD
Project Nameboise valley adventist school
Customer Number 
ePlanReviewNo
Description
To construct a new 17,175 sq. ft. single story, Type VB, fully fire sprinklered gyminasium & class addition. The addition is considered as a separate building with a 2 hour fire wall separating the existing Type V1hr building. Other work includes all site improvements, paving and landscaping. All work is per approved plans and attachments. Fire sprinklers are used for area in the addition and the existing building shall also be fire sprinklered to satisfy IFC fire flow requirements.
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD8/18/20068/18/20062/5/2007 DONE
Second Notice has not been responded to.
Second Notice BLD7/7/20067/7/20068/18/2006 DONE
First Notice has not been responded to.
First Notice 5/22/20067/7/2006 DONE
BLD-Final5/22/20065/22/20065/22/2006PPASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 5/22/2006 at 7:34:06 AM. Contact: ###-####. Ok for perm occ. Reveiwed letter from arch. deleating 2hr walls, letter from special insp. agency and letter freom structural engineer aproving non conformances with special insp. Actuall insp. performed by Jim Sly.
Permanent Occupancy 5/22/20065/22/2006 DONE
Details
Permanent occupancy  5/22/2006 DONE
Perm. Occ. Cert. # 11034 issued 5-22-06 to the Boise Valley Adventist School.
FIRE-Final Inspection5/18/20065/19/20065/19/2006PPASS
DetailsTroy Cobbley
life safety finaled
BLD-Aging Inspection4/14/20064/14/20064/17/2006 NR
DetailsTroy Cobbley
I received a phone call from CM Company today and the lady stated that the door locks would be blanked off.
FIRE-Final Inspection1/11/20061/12/20061/12/2006AFAIL
DetailsTroy Cobbley
The cut sheet that was provided for the thumbturn locks was for "Falcon" but the manufacture of the locks is "CorbinRusswin". Need the correct cut sheet.
CHANGE STATUS TO (ISS)  1/3/2006 DONE
Still needs finals from building and fire.rad
FIRE-Final Inspection12/29/200512/30/200512/30/2005AFAIL
DetailsTroy Cobbley
Provide data sheets to prove thumbturn dead bolts are ADA approved
Third Notice BLD12/7/200512/7/200512/16/2005 DONE
Second Notice has not been responded to.///Signed off 2004 permit per Jenifer & Rita
Second Notice 11/16/200512/7/2005 DONE
First Notice 10/26/200511/16/2005 DONE
Permanent Occupancy 10/26/200510/26/2005 DONE
Details
Permanent occupancy  10/26/2005 DONE
Perm. Occ. Cert. # 10783 issued 10-26-05 to the Boise Valley Adventist School.
BLD-Final10/21/200510/21/200510/21/2005PNR
DetailsJim Sly
BLD-Final8/25/20058/26/20058/26/2005ACANC
DetailsJim Sly
call for access///dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
BLD-Final8/26/20058/26/20058/26/2005PPART
DetailsJim Sly
dan -call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
OK for Temp.....Per PDS approval Cert #5264 C/N Architect to submit letter omitting 1 hr walls, Need final letter from Eng, Need final Affidavit from specail insp agency.
Telephone call  8/26/2005 DONE
Approved for TOC by Fire Marshal D. Hanneman, based on fire/ life safety inspection conducted by F. France today and discussion of D. Hanneman with Jackie Phelps, CM construction company. Correction list left on site by F. France; all items to be completed a soon as practicable.
Temporary occupancy  8/26/2005 DONE
Temp. Occ. Cert. # 5264 issued 8-26-05 to Boise Valley Adventist School.
FIRE-Final Inspection8/18/20058/18/20058/18/2005PFAIL
DetailsTroy Cobbley
Final the fire sprinkler permit. Provide occupant load signs per review note #27. Provide one additional extinguisher in the northwest corner of the gym. Provide exit discharge lighting as discussed at each exit from the new building per building review comments note #46. Provide signage for fire access as shown on sheet A1.0
FIRE-Final Inspection8/15/20058/16/20058/16/2005PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/15/2005 at 2:11:25 PM. Contact: ###-####.
PubWorks Occupancy Approval8/10/20058/10/20058/10/2005 DONE
Drainage project found complete, no inspections requested. Signed permanent occupancy 8/10/05. G.Fitts
Code Occupancy Approval8/9/20058/9/20058/9/2005PPASS
DetailsScott M.Brown
FINAL SIGNED OFF
BLD-Conference8/8/20058/8/20058/8/2005PPASS
DetailsJim Sly
Scheduled by a contractor via Hello! on 8/8/2005 at 8:49:08 AM. Contact: ###-####.
Discussed Req for final.
BLD-Final6/17/20056/17/20056/17/2005PCANC
DetailsJim Sly
ed; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Inspection cancelled from web by: Marsha Smylie
BLD-Framing/Rough-in5/20/20055/23/20055/23/2005APART
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/20/2005 at 3:05:25 PM. Contact: ###-####. Glenn Robnett Architect.... wants Grid design catagory C. 5/23/2005 10:13:05 AM
BLD-Framing/Rough-in5/23/20055/23/20055/23/2005PPART
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/23/2005 at 9:56:33 AM. Contact: ###-####. Grid OK...may check for spacer bars at final. 5/23/2005 3:44:32 PM
BLD-Other5/19/20055/20/20055/20/2005AFAIL
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/19/2005 at 2:50:12 PM. Contact: ###-####. Architect to verify ceiling grid standard (25-2) or Per 2000 UBC 803.8.1.1 ASTM 635 636. Plans are contradicting. 5/20/2005 4:08:36 PM
BLD-Conference5/13/20055/13/20055/13/2005PPART
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/13/2005 at 8:40:24 AM. Contact: ###-####. Grid above stage appears OK. 5/13/2005 1:49:45 PM
BLD-Framing/Rough-in4/25/20054/25/20054/26/2005PPART
DetailsDave Hannah
inspect sheetrock shaft joist space area inside floor ok
BLD-Framing/Rough-in4/22/20054/25/20054/25/2005ANR
DetailsTroy James
Scheduled by a contractor via Hello! on 4/22/2005 at 1:39:44 PM. Contact: ###-####.
BLD-Framing/Rough-in4/21/20054/21/20054/21/2005PPART
DetailsTroy James
Scheduled by a contractor via Hello! on 4/21/2005 at 8:13:47 AM. Contact: ###-####. interior partition wall and shaft ok, informed contractor to complete rated assembly at joist space before sheetrocking lid 4/21/2005 4:03:16 PM
BLD-Framing/Rough-in3/2/20053/3/20053/3/2005PPART
DetailsTroy James
Scheduled by a contractor via Hello! on 3/2/2005 at 1:04:35 PM. Contact: ###-####. roof sheathing nailing ok east entry area 3/3/2005 2:32:07 PM
BLD-Footing9/30/200410/1/200410/1/2004APART
DetailsLane Manuel
Scheduled by a contractor via Hello! on 9/30/2004 at 1:56:13 PM.
partial footings/ to receive MTI special insp. notes 10/1/2004 10:26:28 AM
(F) Reprint permit  9/20/2004  
Issue PAID IN FULL permit  9/17/2004 DONE
Routing - PLANNING7/22/2004 7/23/2004 PASS
Plan assigned to (MLO)4/14/2004 7/23/2004 PASS
DetailsMike Otto
7/23/2004 13:25:38 MLO - activity updated through activity BLDA022 from case BLD04-00709.
Routing - FIRE7/23/2004 7/23/2004 PASS
resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  7/23/2004 DONE
Inspection Record Card- Bld  7/23/2004 DONE
Print Occupancy Form  7/23/2004 DONE
Permit Ready to Issue  7/23/2004 DONE
Telephone call  7/23/2004 DONE
permit ready and fee due
Plan resubmittals received  7/22/2004 DONE
Received transmittal letter with three copies of revised sheet A1.0, one copy of united water fire flow sheet.taken to Mike O.
Routing - PLANNING4/26/2004 7/21/2004 PASS
Carl Miller CUP04-00029, Pending approval w/o appeal, May 13th
Meeting  7/15/2004 DONE
Met with Glenn Roginette, reviewed resubmittal plan deficiencies and requirements relating to FD access, hydrant flows, and fire sprinklers. Revised review comments were faxed to architect today, based on this discussion.
Routing - FIRE7/12/2004 7/14/2004 FAIL
resubmitted plans did not include a cover letter nor identify compliant FD access roadways. Set up meeting with architect to discuss tomorrow (7/15). No revision to previoulsy issued review comments will be made until after this meeting.
Routing - PLAN CHECK7/12/2004 7/12/2004 PASS
Plan resubmittals received  7/12/2004 DONE
rec. three copies of sheets A2.4, A2.6 and A6.0
Routing Off Site - STRUCTURAL7/1/2004 7/9/2004 PASS
Called PDQ for pick-up...
Routing - PLAN CHECK6/24/2004 7/2/2004 FAIL
contacted architect regarding missing items. MLO
Plan resubmittals received  6/23/2004 DONE
Received Transmittal Letter, 3 Structural Calcs , 3 Sets with C1.0,C2.0 , C3.0 , C4.0, C5.0, A1.1, A2.0 , A2.1, A2.3, A2.6, A5.1, A7.0, S1.0, S2.0, S2.1, S2.2, S3.0, S3.1 Taken to Mike Otto
Meeting  6/10/2004 DONE
plans went to fire for meeting with architect. MLO
Meeting  6/10/2004 DONE
11:10am, met with Architect relating to address review in detail for:
FD required access for South side of this facility w/dimentioning
Access road load construction w/dimentioning
Hydrant and Fire Sprinkler Supply issues
Correlating plans (Architectural and Civil)

Plans taken back to "Plan Review" (JWA)
Plan Review Completed(1st rev)  6/8/2004 DONE
Failed:
Plan Check,
Fire,
Structural
Routing - PLAN CHECK6/8/2004 6/8/2004  
Routing - FIRE6/4/2004 6/8/2004 FAIL
DetailsBill Alexander
Requires the following:
1. Provide the information required by the IBC Plan Reviewer, Mike Otto, specifically all items which relate with the IFC.

2. Fire Hydrants. Plan A1.1 requires correction to match civil drawings per relocated hydrant moved from the south side of the proposed structure.

3. Fire Department access. It appears that one existing fire hydrant located on the south side of this structure is located in an area where access does not meet IFC requirements, per these the plans provided. Provide an approved Fire Department vehicular access road/s provided to within 150'-0" of all exterior portions of this building or obtain written approval from the Fire Marshal that access is not required per IFC 503.1.1(1). Provide revised plans that clarify meeting minimum access requirements to the required south side hydrant and still maintaining limits to dead-ends or a required turnaround per IFC 503.1.1. Approval must be obtained in writing from the Fire Marshal of plan acceptance as shown.

4. Access Road Surfaces. Provide construction clarification of fire access road on A2.0. Fire apparatus access roadways shall be constructed and maintained as follows. Fire apparatus access roadways shall be concrete or paved surfaces, except as otherwise noted or approved, whose pavement section is constructed in accordance with ACHD standards. Fire apparatus access roadways constructed with alternative surfaces must meet the following criteria: (1) the roadway surface must structurally support 70,000 pounds gross vehicle weight and 24,000 pounds per axle; (2) the roadway surface must be visible to the driver, as must all signage as prescribed by the Fire Marshal; (3) the roadway surface must withstand the action of weather and the elements, as such, gravel, crushed rock or aggregate, or other loose fill, whether the fill is compacted or not, and turf block or grass-crete type products are not acceptable as a permanent fire apparatus access roadway; (4) fire department access roadways shall not be a combination of surface materials, such as paving strips with grass center lanes; (5) Fire access roadways shall be kept clear of snow, debris, and other obstructions; and (6) written approval must be obtained from the Boise City Fire Marshal prior to construction of fire apparatus access roadways with alternate surfaces. (BMC 7-01-28, 503.2.3) Note: All gates, public or private streets, individual or common driveways, or dedicated emergency vehicle access lanes, etc., which are considered "fire department access" shall be: a minimum of 20'-0" width, 48'-0" outside turning radius and 28'-0" inside radius, with 13 feet 6 inches overhead clearance, with no dead ends over 150 feet unless an approved turnaround is provided. (IFC 503)

5. Fire Hydrant/Fire Sprinkler Supplies. It is prohibited for underground water supply lines with a single point of connection to supply both fire hydrants and fire suppression systems. Looped supply lines that are supplied from two points of connection shall be allowed for hydrants and fire suppression system supplies. Provide correct clarification of water supply to the new fire sprinkler riser located on the East side of the structure on FP1.0. (BMC 7-01-46, 508.6)
Routing Off Site - STRUCTURAL4/14/2004 6/4/2004 FAIL
Contacted PDQ for outside delivery. corrections sent to architect
Routing - PLAN CHECK5/26/2004 6/4/2004 FAIL
corrections sent to architect
Plan resubmittals requested  6/4/2004 DONE
IBC and structural review corrections
Plan resubmittals received  5/26/2004 DONE
Received transmittal letter with one set of as build drawings, three sets of architectural drawings inserted by architect, taken Mike O.
Plan resubmittals requested  5/18/2004 DONE
IBC items, final building configuration required for review and original county approved copy required to complete review.
Routing - PLAN CHECK5/12/2004 5/18/2004 HOLD
went over corrections with architect on phone and faxed list to same. Plans are on hold until additional items are submitted. MLO
Routing - PLUMBING5/12/2004 5/12/2004 PASS
per plans and 2000 upc.
Telephone call  5/3/2004 DONE
telcom from Carl Geigher w/ EHM Engr's Re: United Water indication to him that the water system was not approved. 4 fire hydrants on this site; apparently private, not serviced or approved by United Water. I advised him of our requirement for FHs to be non-private and under control and maintenance of United Water. He will contact John Lee at United Water to determine more details of their requirements.
Routing - Erosion and Sediment4/26/2004 4/26/2004 PASS
ESC approved with attached conditions.
Routing - PUBLIC WORKS4/16/2004 4/21/2004 PASS
Routing - PLANNING Land Div4/14/2004 4/15/2004 PASS
Site is over 5 acres in size.
Plans ACCEPTED BY PLAN TECH  4/14/2004 DONE
Plan routing begun/NEW & ADDTN  4/14/2004 DONE
Application received  4/9/2004  
Recd Pcfee & Taken To Pln CK  4/9/2004  
Fee Review-notes4/9/20044/9/2004   
Routing - Erosion and Sediment4/21/2004   FAIL
No RP listed on permit application.