Second Notice BLD | 8/11/2008 | 8/11/2008 | 9/4/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 7/10/2008 | 8/11/2008 | | DONE |
|
|
|
|
Office Staff conference/action | | | 7/10/2008 | | DONE |
Barbara Stitt
|
|
|
Per Dave Hannah ok to issue Certificate of occupancy as Fire Alam & Fire Sprinkler were both doc finaled 7-10-08 BAS
|
Permanent Occupancy | | | 7/10/2008 | | DONE |
Barbara Stitt
|
|
|
|
BLD-Final | 2/14/2005 | 2/14/2005 | 2/14/2005 | P | PASS |
Dave Hannah
|
|
|
Rock; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok for perm occ 2/14/2005 2:12:46 PM
|
BLD-Framing/Rough-in | 1/5/2005 | 1/6/2005 | 1/6/2005 | A | PASS |
Dave Hannah
|
|
|
rock; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 12/23/2004 | 12/23/2004 | 12/23/2004 | P | PART |
Dave Hannah
|
|
|
rock ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie mri walls and soffit ok to cover after elec r/i 12/23/2004 1:06:03 PM
|
Issue & PRINT to be Invoiced | | | 9/28/2004 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 9/24/2004 | | 9/27/2004 | | PASS |
|
|
|
Approved as noted and attached
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/27/2004 | | PASS |
|
|
|
Ready to process for issuing.
|
Inspection Record Card- Bld | | | 9/27/2004 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/27/2004 | | DONE |
|
|
|
|
Telephone call | | | 9/27/2004 | | DONE |
|
|
|
e-mailed curtis
|
Permit Ready to Issue | | | 9/27/2004 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 8/16/2004 | | 9/27/2004 | | PASS |
|
|
|
9/27/2004 07:32:47 DRS - activity updated through activity BLDA022 from case BLD04-01865.
|
Routing - FIRE | 9/22/2004 | | 9/24/2004 | | PASS |
|
|
|
Approved per resubmittal received today from archiect
|
Routing - PLUMBING | 9/21/2004 | | 9/22/2004 | | PASS |
|
|
|
Approved per plan and 2003 UPC and note on section 811.6 UPC to terminate Acid Waste Vent independantly.
|
Routing - PLAN CHECK | 9/22/2004 | | 9/22/2004 | | PEND |
|
|
|
Routing to fire code analyst.
|
Routing - PLAN CHECK | 9/20/2004 | | 9/21/2004 | | PEND |
|
|
|
hold for resubmittal of requested info per BLDG and Fire reviews.
(9/14/04) Received Sheet A0.2 & A0.3 in response to plan review report. No further resubmittals required.
(9/16/04) New plumbing sheet P1.0 & P1.1 provided in response to plumbing plan review.
|
Routing - FIRE | 9/10/2004 | | 9/20/2004 | | FAIL |
|
|
|
Resubmittal? No response to previous review comments. Unsuccessfully attemped to contact Gregg Ostrow, resident architect, to discuss by phone. Revised comments faxed to architect and Gregg Oster.
|
Plan resubmittals received | | | 9/16/2004 | | DONE |
|
|
|
Received Transmittal Letter, & 3 Sets of P1.0, P1.1 Taken to Dan S......
|
Plan resubmittals received | | | 9/14/2004 | | DONE |
|
|
|
Received letter of transmittal with response letter, room ventilation data sheets, three sets of sheets A0.2,A0.3 taken to Dan S.
|
Routing - PLAN CHECK | 9/2/2004 | | 9/9/2004 | | PEND |
|
|
|
Received hazardous materials data from SLRMC for lab area. Routing to fire code analyst for review.
|
Routing - FIRE | 8/30/2004 | | 9/3/2004 | | FAIL |
|
|
|
need haz mat and cryogenic info. Review faxed to architect.
|
Plan Review Completed(1st rev) | | | 9/2/2004 | | FAIL |
|
|
|
failed plumbing, plan check and fire.
|
Routing - PLAN CHECK | 8/25/2004 | | 8/30/2004 | | FAIL |
|
|
|
Resubmittals required. Routing to fire code analyst for review. Copy of plan review faxed and mailed to architect. DOCUMENTATION OF CODE COMPLIANCE INCOMPLETE AND FAILED PLUMBING.
|
Routing - PLUMBING | 8/18/2004 | | 8/25/2004 | | FAIL |
|
|
|
overflow and roof drains systems must be independent, no chemical vent shall intersect vents for other systems, provide an r.p. over a floor sink for the cw to the MRI emergency water switchover ststion. no indirect waste receptors are to be located below raised floor system.
|
Routing - PUBLIC WORKS | 8/16/2004 | | 8/18/2004 | | PASS |
|
|
|
|
Application received | | | 8/12/2004 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 8/12/2004 | | |
|
|
|
|
Fee Review-notes | 8/12/2004 | 8/12/2004 | | | |
|
|
|
|