Second Notice BLD | 10/1/2007 | 10/1/2007 | 10/1/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
Second Notice BLD | 10/1/2007 | 10/1/2007 | 10/1/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 9/19/2007 | 10/1/2007 | | DONE |
|
|
|
|
First Notice | | 9/19/2007 | 10/1/2007 | | DONE |
|
|
|
|
Permanent Occupancy | | | 9/19/2007 | | DONE |
|
|
|
|
Third Notice BLD | 3/15/2006 | 3/15/2006 | 1/31/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Telephone call | | | 4/6/2006 | | |
|
|
|
lft vm for eugene ###-#### 1:51 pm regarding collister com church
|
Second Notice BLD | 3/1/2006 | 3/1/2006 | 3/15/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 2/3/2006 | 2/3/2006 | 3/1/2006 | | DONE |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/3/2006 | 2/3/2006 | 2/3/2006 | | DONE |
Tony Young
|
|
|
|
DOC - Permit Finaled | 2/3/2006 | 2/3/2006 | 2/3/2006 | P | PASS |
Tony Young
|
|
|
|
Case Summary (BLD) | | | 1/12/2006 | | |
|
|
|
|
BLD-Final | 9/29/2005 | 9/29/2005 | 9/29/2005 | P | DONE |
Tony Young
|
|
|
denis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see prior notes
|
BLD-Final | 9/28/2005 | 9/29/2005 | 9/29/2005 | A | PART |
Tony Young
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for perm. occ.,,, pending zoning/ landscape bond
|
Temporary occupancy | | | 9/29/2005 | | DONE |
|
|
|
Temp. Occ. Cert. # 5278 issued 9-29-05 to Collister Community Church.
|
FIRE-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 | P | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
FIRE-Final Inspection | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was not for a final but a conference on life safety. Items needing completed are the fire alarm permit to be finaled, need occupant load sign in the sanctuary and need the address posted on the building or out on Roland street on the sign post as discussed.
|
PubWorks Occupancy Approval | 9/21/2005 | 9/21/2005 | 9/21/2005 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 9/21/05. D.Erskine
|
Code Occupancy Approval Temp | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | FAIL |
Scott M.Brown
|
|
|
NEED BOND FOR $37,000, LAND SCAPE NOT IN.
|
BLD-Energy code compliance | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Tony Young
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie vestibule
|
BLD-Framing/Rough-in | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Tony Young
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie vestibule ok
|
BLD-Energy code compliance | 6/13/2005 | 6/14/2005 | 6/15/2005 | A | PASS |
Tony Young
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
BLD-Wall cover | 6/9/2005 | 6/10/2005 | 6/10/2005 | A | DONE |
Dave Hannah
|
|
|
ceiling also///dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
BLD-Wall cover | 6/9/2005 | 6/10/2005 | 6/10/2005 | A | PART |
Dave Hannah
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa insulation in sanctuary ok to cover framing at entry and restrooms ok to insulate
|
BLD-Framing/Rough-in | 6/7/2005 | 6/7/2005 | 6/7/2005 | P | PART |
Tony Young
|
|
|
DENNIS; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to insulate atrium walls and cover lid
|
BLD-Grading Inspection | 3/16/2005 | 3/17/2005 | 3/17/2005 | P | PART |
Tony Young
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Jan Rice
wip,,, slab 3/17/2005 3:49:34 PM
|
BLD-Foundation | 2/17/2005 | 2/18/2005 | 2/18/2005 | P | PART |
Tony Young
|
|
|
Stem walls inspection please///dennis ###-####
pending s i report 2/18/2005 3:31:23 PM
|
BLD-Footing | 2/17/2005 | 2/17/2005 | 2/17/2005 | P | PART |
Tony Young
|
|
|
Stem wall inspection also please////dennis ###-####
ok pending special inspector report 2/17/2005 1:49:58 PM
|
BLD-Footing | 2/10/2005 | 2/11/2005 | 2/11/2005 | A | PART |
Lane Manuel
|
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 1:32:13 PM. Contact: ###-####.
footings ok.
MTI to perform special insp./ cylinders. 2/11/2005 9:23:43 AM
|
BLD-Footing | 2/9/2005 | 2/10/2005 | 2/10/2005 | P | NR |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 2/9/2005 at 11:42:22 AM. Contact: ###-####.
|
Issue PAID IN FULL permit | | | 1/24/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/20/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 1/20/2005 | | |
|
|
|
|
Print Occupancy Form | | | 1/20/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 1/20/2005 | | |
|
|
|
|
Telephone call | | | 1/20/2005 | | DONE |
|
|
|
talked to wayne thoutess at ###-#### is ready & need the a.c.h.d.
|
Plan assigned to (MLO) | 9/15/2004 | | 1/20/2005 | | PASS |
|
|
|
1/20/2005 10:23:48 MLO - activity updated through activity BLDA022 from case BLD04-02139.
|
Routing - PLANNING | 1/19/2005 | | 1/19/2005 | | PASS |
|
|
|
Plans in compliance with CUP04-76 and DRH04-160. See previous DR sign-off by M.S. kg
|
Routing - PLANNING Land Div | 1/13/2005 | | 1/18/2005 | | PASS |
|
|
|
Record of Survey complete and single tax parcel number.
|
Routing - PLANNING | 1/6/2005 | | 1/13/2005 | | FAIL |
|
|
|
Record of survey to consolidate parcels needed and resolution of property line configuration at northeast corner.
|
Plan resubmittals received | | | 1/6/2005 | | DONE |
|
|
|
Received transmittal letter with two sets of sheets S-1.1,S-1.2,L-1.1 taken to Mike Otto. Resubs received by M.Otto at 12:15 PM 1/6/05
|
Routing - PLAN CHECK | 12/20/2004 | | 12/20/2004 | | PEND |
|
|
|
Routed to plan check.
|
Routing - PLANNING | 11/3/2004 | | 12/20/2004 | | FAIL |
|
|
|
Still working through ROS requirements and changes needed to site plan sheet S1.1, per CUP04-76 Mod1. kg
|
Routing Off Site - STRUCTURAL | 11/1/2004 | | 11/3/2004 | | PASS |
|
|
|
Contacted PDQ for outside delivery.
|
Routing - PLANNING Land Div | 11/1/2004 | | 11/2/2004 | | FAIL |
|
|
|
Must complete conditions of ROS04-00057. Which includes verification of construction of driveway and off-street parking, signing of Record of Survey by Planning Director and recordation, preparing Notice of Buildable Parcel documents which must be signed by Planning Director and recorded, then recording of deeds to establish new property lines.
|
Routing - PLAN CHECK | 11/1/2004 | | 11/1/2004 | | PASS |
|
|
|
|
Plan resubmittals received | | | 11/1/2004 | | DONE |
|
|
|
Received Transmittal Letter, Structural Response letter, 1 Geo-tech report, 2 Structural Calcs, 1 Set revised structural sheets A-1.2,A-2.1,A-2.2,A-6.2,A-6.3,A-7.4 2 Sets revised sheets A-1.1,A-1.2,A-2.1,A-2.2,A-3.1,A-3.2,A-4.1,A-5.1,A-6.2,A-6.3,A-7.4,P-2.0,M-2.0 Taken to Mike Otto...
|
Routing - FIRE | 10/21/2004 | | 10/26/2004 | | PASS |
|
|
|
Review faxed to architect for reference.
|
1st review completed | | | 10/26/2004 | | FAIL |
|
|
|
failed Planning Land Div, Planning, Plan check and Structural.
|
Routing - PLAN CHECK | 10/26/2004 | | 10/26/2004 | | PEND |
|
|
|
waiting for resubs
|
Routing - PLAN CHECK | 10/7/2004 | | 10/21/2004 | | FAIL |
|
|
|
corrections sent to architect
|
Routing Off Site - STRUCTURAL | 9/15/2004 | | 10/21/2004 | | FAIL |
|
|
|
Called PDQ for pick up..... Corrections sent to architect MLO
|
Routing - PLANNING | 9/23/2004 | | 10/7/2004 | | FAIL |
|
|
|
KAREN G. Failed. Plans not in compliance with CUP04-00076 and Mod. Need to complete ROS too.
MARTY S. DRH04-00160
|
Routing - PLUMBING | 9/22/2004 | | 9/23/2004 | | PASS |
|
|
|
urinals in assembly occupancies are 5 f.u.s each, increase 2" horizontal waste to 3" to 1st urinal then to 2".
|
Routing - PUBLIC WORKS | 9/16/2004 | | 9/22/2004 | | PASS |
|
|
|
|
Routing - Erosion and Sediment | 9/22/2004 | | 9/22/2004 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PLANNING Land Div | 9/15/2004 | | 9/16/2004 | | FAIL |
|
|
|
Need to complete ROS04-00057.
|
Plans ACCEPTED BY PLAN TECH | | | 9/15/2004 | | |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 9/15/2004 | | |
|
|
|
|
Application received | | | 9/14/2004 | | |
|
|
|
|