Case Summary (BLD) | | | 12/7/2007 | | DONE |
|
|
|
|
Third Notice BLD | 12/6/2005 | 12/6/2005 | 12/14/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 9/14/2005 | 9/14/2005 | 12/6/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 8/10/2005 | 9/14/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 8/9/2005 | 8/10/2005 | 8/10/2005 | A | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
Permanent occupancy UNPAID FEE | | | 8/10/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10686 issued 8-10-05 to Direct Mortgage.
|
FIRE-Final Inspection | 8/8/2005 | 8/9/2005 | 8/9/2005 | A | FAIL |
Troy Cobbley
|
|
|
ben ; Phone #: ###-#### The hvac units still will not go into heat mode for testing. Sample tubes have been fixed.
|
FIRE-Final Inspection | 8/3/2005 | 8/4/2005 | 8/4/2005 | A | FAIL |
Troy Cobbley
|
|
|
Duct detectors have been relocated. Of the three detectors only the one located on the south unit has the sample tube facing the correct direction and shut down properly. The other two's sample tube are incorrectly placed and the units would not go into heat mode.
|
FIRE-Final Inspection | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | CANC |
Troy Cobbley
|
|
|
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Final | 7/26/2005 | 7/29/2005 | 7/29/2005 | P | PASS |
Tom Arcoraci
|
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok for perm occ when fire signs perm occ
|
FIRE-Final Inspection | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given wit sam rogers permission until the three duct smoke detectors have been placed correctly and tested
|
FIRE-Final Inspection | 7/26/2005 | 7/27/2005 | 7/27/2005 | A | FAIL |
Troy Cobbley
|
|
|
Mount fire extinguishers as discussed. Change door hardware at restroom corridor to allow passage from corridor and along route as directed by exit signs. Test duct smoke detectors.
|
BLD-Energy code compliance | 6/1/2005 | 6/2/2005 | 6/2/2005 | A | PASS |
Mike Jordan
|
|
|
robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Issue PAID IN FULL permit | | | 3/10/2005 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 2/3/2005 | | 3/9/2005 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/9/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/9/2005 | | |
|
|
|
|
Inspection Record Card- Bld | | | 3/9/2005 | | |
|
|
|
|
Print Occupancy Form | | | 3/9/2005 | | DONE |
|
|
|
|
Telephone call | | | 3/9/2005 | | |
|
|
|
left mess for dave evans const at ###-#### is ready
|
Plan assigned to (JCM) | 9/30/2004 | | 3/9/2005 | | PASS |
|
|
|
3/9/2005 09:54:41 JCM - activity updated through activity BLDA022 from case BLD04-02272.
|
Routing - PLUMBING | 2/3/2005 | | 2/3/2005 | | PASS |
|
|
|
see bld04-02231 for review comments
|
Plan Reviewer's activity | | | 10/29/2004 | | PASS |
|
|
|
Reviewed and approved resubmittals. JCM
|
Plan resubmittals received | | | 10/26/2004 | | DONE |
|
|
|
Received two copies of revised sheet EN-1. Routed to John M.
|
Routing - FIRE | 10/8/2004 | | 10/13/2004 | | PASS |
|
|
|
|
1st review completed | | | 10/13/2004 | | FAIL |
|
|
|
failed plan check
|
Plan resubmittals requested | | | 10/8/2004 | | |
|
|
|
Mailed the applicant a copy of the plan review comment list requesting revisions. JCM
|
Routing - PLAN CHECK | 10/7/2004 | | 10/8/2004 | | FAIL |
|
|
|
|
Application received | | | 9/29/2004 | | |
|
|
|
|
Routing - PLAN CHECK | 10/13/2004 | | | | |
|
|
|
|