Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD04-02362
StatusFinaled
Name RA SCHULTZ AND COMPANY
Site Address 3363 N COLE RD
Project NameCOLE VILLAGE
Customer Number 
ePlanReviewNo
Description
(ON THE SPOT CLEANERS - COLE VILLAGE) This building is fire sprinklered for building area increase. To remodel an existing 4,296 square foot tenant space for a dry cleaning business. This project is a change of Occupancy Classification. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, interior doors, an interior window, suspended ceiling, and interior finishes all per the approved drawings and the plan review report on file. Also, the existing 867 square foot mezzanine will be demolished under this permit. The fire sprinkler system serving this tenant space shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD5/20/20055/20/200512/9/2005 DONE
Second Notice has not been responded to.///Too old to collect information for Final values
Second Notice BLD4/26/20054/26/20055/20/2005 DONE
First Notice has not been responded to.
First Notice 2/25/20054/26/2005 DONE
BLD-Final2/24/20052/25/20052/25/2005APASS
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore OK for Perm Occ. 2/25/2005 8:12:23 AM
Permanent Occupancy 2/25/20052/25/2005 DONE
Details
Permanent occupancy UNPAID FEE  2/25/2005 DONE
Perm. Occ. Cert. # 10462 issued 2-25-05 to On the Spot Cleaners in Cole Village.
BLD-Final2/23/20052/24/20052/24/2005ANR
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Final2/18/20052/23/20052/23/2005PPART
DetailsJim Sly
Matt; Phone #: ###-#### or ###-#### jack Internet Inspection Request from: Jan Rice OK for Temp. 2/23/2005 3:55:39 PM
FIRE-Final Inspection2/22/20052/23/20052/23/2005ACANC
DetailsTroy Cobbley
Duplicate inspection. Finaled 2/22/2005 by 430 2/22/2005 12:41:14 PM
FIRE-Final Inspection2/18/20052/22/20052/22/2005APASS
DetailsTroy Cobbley
Life safety finaled 2/22/2005 12:18:47 PM
Plan Reviewer's activity  2/18/2005 DONE
Approved a minor change to the drawings. An interior door to the fire alarm panel room was eliminated. Confirmed approval with Sam R. and Mary F.
Plan resubmittals received  2/17/2005 DONE
Received Transmittal Letter, & 1 Copy of sheet A1.1 Taken to Carl W.
FIRE-Final Inspection2/14/20052/15/20052/15/2005AFAIL
DetailsTroy Cobbley
The existing corridor has been blocked off. Approved plans show door to be installed. Resubmit plans showing modifications. The exhaust ventilation system does not operate automatically. See IFC 1205.3 and IMC 502.5.2 2/15/2005 9:10:08 AM
FIRE-Final Inspection1/26/20051/27/20051/27/2005AFAIL
DetailsRick Jackson
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need resubmittals to show duct detectors on zone 8; need to test duct detectors as units did not shut down 1/27/2005 10:35:52 AM
FIRE-Conference1/27/20051/27/20051/27/2005APART
DetailsRick Jackson
Met with GC while testing the alarms - need sprinkler head in riser room; room created for fire alarm panel requires heat; complete fire alarm permit 1/27/2005 10:37:33 AM
BLD-Framing/Rough-in12/21/200412/22/200412/22/2004APASS
DetailsJim Sly
matt; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Permit Ready to Issue  12/3/2004  
Inspection Record Card- Bld  12/3/2004  
Print Occupancy Form  12/3/2004 DONE
Telephone call  12/3/2004 DONE
left mess with jeff likes at ###-#### that permit is ready
Issue PAID IN FULL permit  12/3/2004 DONE
Plan assigned to (CJW)10/8/2004 12/2/2004 PASS
12/2/2004 16:36:13 CJW - activity updated through activity BLDA022 from case BLD04-02362.
Routing - PLAN CHECK12/1/2004 12/2/2004 DONE
Sent back to Plumbing.
Routing - PLUMBING12/2/2004 12/2/2004 PASS
per plans and 2003 upc
Routing - PLAN CHECK12/1/2004 12/2/2004 DONE
PLANS/APPL TAKEN TO FRONT DESK  12/2/2004 DONE
Routing - FIRE11/26/2004 12/1/2004 PASS
resubmittal acceptable.
Routing - PLUMBING11/23/2004 11/26/2004 FAIL
need service sink per IBC minimum fixture requirements.
Routing - PUBLIC WORKS11/22/2004 11/23/2004 PASS
Routing - PLAN CHECK10/19/2004 11/22/2004 PASS
Drawings approved after 2nd review.
Plan resubmittals received  11/15/2004 DONE
Received letter of transmittal, memo, two safety data reports, two sets of sheets A3.1,M1.0,M2.0,M3.0,M4.0 Taken to Carl W.
Routing - FIRE10/15/2004 10/19/2004 FAIL
lacks Haz Mat classification, and details relative to Dry Cleaners per IFC Chapter 12. Review faxed to architect.
1st review completed  10/19/2004 FAIL
failed Public works, plumbing, plan check and Fire.
Routing - PLAN CHECK10/12/2004 10/15/2004 FAIL
Failed 1st IBC plan review. IBC plan review started October 14, 2004 and finished the next day. Resubmitted drawings were required. See the plan review report.
Routing - PLUMBING10/11/2004 10/12/2004 FAIL
provide a complete plumbing plan and show all requirements of boise city public works pretreatment.
Routing - PUBLIC WORKS10/8/2004 10/11/2004 FAIL
Will require plumbing plans. lw
Application received  10/7/2004  
Recd Pcfee & Taken To Pln CK  10/7/2004  
Plans ACCEPTED BY PLAN TECH  10/7/2004  
Fee Review-notes10/7/200410/7/2004