(F) Reprint permit | | | 8/23/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/23/2006 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 7/5/2006 | | |
|
|
|
|
Third Notice BLD | 12/6/2005 | 12/6/2005 | 12/16/2005 | | DONE |
|
|
|
Second Notice has not been responded to.///Signed off 2004 permit per Jenifer & Rita
|
Second Notice BLD | 7/13/2005 | 7/13/2005 | 12/6/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
Telephone call | | | 8/27/2005 | | DONE |
|
|
|
fax over for final values
|
First Notice | | 5/11/2005 | 7/13/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 5/11/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10575 issued 5-11-05 to Starbucks Coffee.
|
Permanent Occupancy | | 5/10/2005 | 5/10/2005 | | DONE |
|
|
|
|
Temporary occupancy | | | 3/16/2005 | | DONE |
|
|
|
Temp. Occ. Cert. # 5222 issued 3-16-05 to Starbuck's Coffee.
|
BLD-Final | 3/10/2005 | 3/10/2005 | 3/10/2005 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 3/10/2005 at 11:10:30 AM. Contact: ###-####. final ok pending health dept sign off. 3/10/2005 3:22:33 PM
|
BLD-Conference | 2/16/2005 | 2/16/2005 | 2/16/2005 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 2/16/2005 at 8:24:29 AM. Contact: ###-####. need el ceilling aproval/ need vapor barrior above ceilling will check at final ok to drop ceilling upon ele aproval.
|
Issue PAID IN FULL permit | | | 1/13/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2005 | | DONE |
|
|
|
left mess for amanda oberg at ###-#### is ready
|
Inspection Record Card- Bld | | | 11/22/2004 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/22/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/22/2004 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 11/12/2004 | | 11/17/2004 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/17/2004 | | DONE |
|
|
|
Plans taken to permit desk on behalf of Carl Westfall by M. Southard
|
Plan assigned to (CJW) | 10/26/2004 | | 11/17/2004 | | PASS |
|
|
|
11/17/2004 16:53:35 MYS - activity updated through activity BLDA022 from case BLD04-02502.
|
Routing - FIRE | 11/9/2004 | | 11/12/2004 | | PASS |
|
|
|
|
1st review completed | | | 11/12/2004 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 10/28/2004 | | 11/9/2004 | | PASS |
|
|
|
The IBC plan review was started November 8, 2004 and was finished the next day. The drawings were approved with clarifications. See the plan review report.
|
Routing - PUBLIC WORKS | 10/26/2004 | | 10/28/2004 | | PASS |
|
|
|
|
Routing - PLUMBING | 10/28/2004 | | 10/28/2004 | | PASS |
|
|
|
Premise DCVA and thermal expansion required (not shown)
RP's required on exspresso machines, Plumbing contractor to have pre-final with Plumbing inspector when equipment is all in for possible others.
Route Water Heater PRV to floor sink (not w.h. pan)
approved per plan, notes and 2003 UPC
|
Application received | | | 10/25/2004 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/25/2004 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 10/25/2004 | | |
|
|
|
|
Fee Review-notes | 10/25/2004 | 10/25/2004 | | | |
|
|
|
|