BLD-Aging Inspection | 11/7/2006 | 11/7/2006 | 11/7/2006 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 7/28/2006 | 7/28/2006 | 8/3/2006 | | FAIL |
Tony Young
|
|
|
|
BLD-Aging Inspection | 4/24/2006 | 4/24/2006 | 4/25/2006 | | FAIL |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/20/2006 | 2/20/2006 | 2/22/2006 | | FAIL |
Tony Young
|
|
|
|
FIRE-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 | P | FAIL |
Troy Cobbley
|
|
|
Address on suite does not match permit. Submit change of address. Provide fire alarm permit for the two new duct smoke detectors that need tied into the fire alarm system. 2/7/2005 4:26:56 PM
|
FIRE-Final Inspection | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 2/1/2005 at 9:37:46 AM. Contact: ###-####. There are two AHU's over 2,000 cfm that will require duct detectors for unit shut down 2/1/2005 4:06:54 PM
|
BLD-Final | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | PASS |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 2/1/2005 at 9:38:26 AM. Contact: ###-####.
|
(F) Reprint permit | | | 1/26/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 12/28/2004 | | DONE |
|
|
|
Acidentally changed status////12/28/04 BAS
|
Inspection Record Card- Bld | | | 12/28/2004 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 11/8/2004 | 11/8/2004 | 12/14/2004 | | PASS |
|
|
|
12/14/2004 09:31:56 DRS - activity updated through activity BLDA022 from case BLD04-02782.
|
Permit Ready to Issue | | | 12/7/2004 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/7/2004 | | DONE |
|
|
|
|
Telephone call | | | 12/7/2004 | | DONE |
|
|
|
Spoke with Pat from Thornton Oliver Keller and left a message for David Blodgett that permit is ready & fees///12/07/04 9:45am BAS
|
Issue PAID IN FULL permit | | | 12/7/2004 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/6/2004 | | PASS |
|
|
|
To permit desk to issue.
|
Routing - FIRE | 11/26/2004 | | 12/6/2004 | | PASS |
|
|
|
|
1st review completed | | | 12/6/2004 | | FAIL |
|
|
|
failed plan check.
|
Routing - PLAN CHECK | 12/6/2004 | | 12/6/2004 | | PASS |
|
|
|
Approved as noted and attached.
|
Waiting for Cert. of Value | | | 11/26/2004 | | FAIL |
|
|
|
Need separate application & certificate of value for suite 162, "Vanilla Finish".
|
Routing - PLAN CHECK | 11/8/2004 | | 11/26/2004 | | FAIL |
|
|
|
Need separate application and certificate of value for new tenant space being created by division of existing space into two spaces and for new access door & electrical to be done.
|
Application received | | | 11/26/2004 | | |
|
|
|
|
Telephone call | | | 11/26/2004 | | DONE |
|
|
|
Call to David Blodgett, Rudeen & Associates, to see if he had prepared and sent over a separate application for Vanilla Finish" Suite 162 with a C.V. and a modified C.V. for "Bikram Yoga", suite 160, for two new tenant spaces from one existing space. Jason Blais had previoulsy talked with Mr. Blodgett concerning separate applications and permit for two spaces.
|
Plans ACCEPTED BY PLAN CHECK | | | 11/8/2004 | | DONE |
|
|
|
|