Second Notice BLD | 5/20/2005 | 5/20/2005 | 5/24/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 4/19/2005 | 5/20/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 4/19/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10536 issued 4-19--05 to Hewlett-Packard, Bldg. #28 call center.
|
FIRE-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire life safety finaled
|
BLD-Final | 4/15/2005 | 4/18/2005 | 4/18/2005 | P | PASS |
Troy James
|
|
|
darrin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Permanent Occupancy | | 4/18/2005 | 4/18/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 4/14/2005 | 4/15/2005 | 4/15/2005 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide signage per IFC 608.6 and seismic bracing per 608.7
|
BLD-Final | 4/14/2005 | 4/15/2005 | 4/15/2005 | P | CANC |
Tony Young
|
|
|
darrin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore DARRIN CNCL
|
FIRE-Final Inspection | 4/13/2005 | 4/14/2005 | 4/14/2005 | P | FAIL |
Troy Cobbley
|
|
|
Need information about batteries and generator resubmitted per the fire dept review comments.
|
BLD-Framing/Rough-in | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | PASS |
Jim Sly
|
|
|
darrin-- ceiling grid; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st before insp M.G. W. Emerald L Kimball Conc tilt up on R. 4/5/2005 11:15:53 AM
|
BLD-Framing/Rough-in | 2/21/2005 | 2/22/2005 | 2/22/2005 | P | PART |
Lane Manuel
|
|
|
Scheduled by a contractor via Hello! on 2/21/2005 at 1:48:12 PM. Contact: ###-####.
walls ok for cover, both ends of bldg 2/22/2005 3:32:40 PM
|
Routing - FIRE | 2/15/2005 | | 2/15/2005 | | PASS |
|
|
|
"Delayed submittal" (requested in origianl Fire review) received from architect and J. Hatten HP, dated Jan 6, 2005, addressing the UPS battery room and emergency generator, is acceptable pending field verification. Revised comments attached to office plans and given to the permit desk. Rita will call the architect to pick up and attach to onsite plans.
|
Plan resubmittals received | | | 1/7/2005 | | DONE |
|
|
|
Received 3Transmittal Letters, 3 Battery info sheets, 3 Uninterrupitible power supply sheets & 3 Generator set books. Plans have been issued , These re-submittals taken to Sam Rogers as per his requist.
|
Permit Ready to Issue | | | 1/4/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 1/4/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 1/4/2005 | | DONE |
|
|
|
|
Telephone call | | | 1/4/2005 | | DONE |
|
|
|
Left message for Katie that permit is ready & fees///1/4/05 8:20am BAS
|
Issue PAID IN FULL permit | | | 1/4/2005 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 12/20/2004 | 12/20/2004 | 1/3/2005 | | PASS |
|
|
|
1/3/2005 11:21:52 DRS - activity updated through activity BLDA022 from case BLD04-02940.
|
Routing - FIRE | 12/28/2004 | | 1/3/2005 | | PASS |
|
|
|
Plans lack battery UPS and emergency generator information. Per discussion and agreement with architect, K. Butler, to facilitate their construction schedule, plans are approved on basis that the required information will be resubmitted as a plan modification for approval prior to the installation of the UPS and emergency generator system.
|
1st review completed | | | 1/3/2005 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 1/3/2005 | | 1/3/2005 | | PASS |
|
|
|
Approved as noted on plans and all attached plan review conditions of all reviewing agencies.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/3/2005 | | PASS |
|
|
|
To permit desk to issue permit.
|
Routing - PLANNING | 12/21/2004 | | 12/28/2004 | | PASS |
|
|
|
Per CZC04-232.
|
Routing - PLAN CHECK | 12/20/2004 | | 12/21/2004 | | PEND |
|
|
|
No resubmittals required. Routing to Planning, Sarah Schafer.
|
Plans ACCEPTED BY PLAN TECH | | | 12/20/2004 | | DONE |
|
|
|
|
Routing - Erosion and Sediment | 12/20/2004 | | 12/20/2004 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Plan routing begun/NEW & ADDTN | | | 12/20/2004 | | DONE |
|
|
|
|
Application received | | | 12/17/2004 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/17/2004 | | |
|
|
|
|
Fee Review-notes | 12/17/2004 | 12/17/2004 | | | |
|
|
|
|