Permit Information
Permit NumberBLD04-03026
StatusFinaled
Name CUSTOMIZED HAIR
Site Address 928 W MAIN ST
Project NameIDANHA-BASEMENT
Customer Number 
ePlanReviewNo
Description
(CUSTOMIZED HAIR - IDANHA BASEMENT) The fire sprinkler system is used, under the provisions of the 1994 UCBC, to allow this building to be 10 feet and 2 stories too tall AND to be over area. To remodel a 928 square foot basement area to be used as a hair salon. Work is to include interior nonbearing walls, wall furring, interior windows, interior doors, small window openings in an existing masonry wall, and interior finishes all per the approved drawings and the plan review report on file. Within the remodel area, the fire sprinker system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD12/6/200512/6/200512/14/2005 DONE
Second Notice has not been responded to.///singed off 2004 permit per Jenifer & Rita
Second Notice BLD7/13/20057/13/200512/6/2005 DONE
First Notice has not been responded to.
First Notice 5/18/20057/13/2005 DONE
BLD-Final5/18/20055/18/20055/18/2005PPASS
DetailsDave Hannah
jim --pending fire fn ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for perm occ
FIRE-Final Inspection5/18/20055/18/20055/18/2005 PASS
DetailsForrest France
Fire and Life Safety finaled
Permanent Occupancy 5/18/20055/18/2005 DONE
Details
Permanent occupancy  5/18/2005 DONE
Perm. Occ. Cert. # 10584 issued 5-18-05 to Customized Hair in the basement of the Idanha Bldg.
BLD-Final5/16/20055/16/20055/16/2005PNR
DetailsDave Hannah
jim; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa needs fire life safty sign off
FIRE-Conference5/12/20055/12/20055/12/2005PDONE
DetailsForrest France
Site visited to check status of building permit work. Some correction notice items not yet complete such as mount provided fire ext. Discovered tenant has moved in and is open for business without sign off or CO. Informed Sam Rogers of the situation.
FIRE-Final Inspection5/3/20055/4/20055/4/2005 FAIL
DetailsForrest France
It appears that portions of the fire alarm system have been installed or modified without a permit. Advised GC to stop all FA work until a FA permit and approved plans have been obtained. Need to post street address. Provide a fire ext. with current tag (none provided). Main exit must have approved hardware- see note #6 on plan review (key lock from outside only, no key availae to verify egress operation when locked). Two fire sprinkler heads are painted in the main entry stairway. Could not gain access to verify current inspection tag on sprinkler riser.
BLD-Framing/Rough-in3/7/20053/8/20053/8/2005APASS
DetailsDave Hannah
cover inspection please///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Plan Reviewer's activity  3/7/2005 PASS
Approved revised drawings. At "Plan Review" Desk for Mr. Campbell.
Plan resubmittals received  3/4/2005 DONE
Revised sheets submitted. 2 copies of Sheet A2.0.
BLD-Framing/Rough-in3/2/20053/3/20053/3/2005AFAIL
DetailsDave Hannah
For cover inspection please///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore after talking with george they need to resubmit plans to carl w showing changes and how they are going to keep th fire ratings 3/3/2005 10:03:32 AM
BLD-Framing/Rough-in3/2/20053/2/20053/2/2005PFAIL
DetailsDave Hannah
For cover inspection please///jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore used wood studs plans call for steel need to talk with george 3/3/2005 10:01:21 AM
Inspection Record Card- Bld  1/27/2005 DONE
Permit Ready to Issue  1/27/2005 DONE
Telephone call  1/27/2005 DONE
tlk john price ###-#### and jim campbell ###-#### that permit and fees are ready to be picked up
Print Occupancy Form  1/27/2005 DONE
Issue PAID IN FULL permit  1/27/2005 DONE
Routing - PLUMBING1/24/2005 1/26/2005 PASS
per resubmitted plans dated 1/26/05 and 2000 upc
Plan resubmittals received  1/26/2005 DONE
Received Transmittal & 2 Copys of sheets M1.0 , M2.0 Taken to Bill V.
Routing - PLAN CHECK1/26/2005 1/26/2005  
PLANS/APPL TAKEN TO FRONT DESK  1/26/2005 D0NE
Plan assigned to (CJW)12/29/2004 1/26/2005 PASS
1/26/2005 13:00:54 CJW - activity updated through activity BLDA022 from case BLD04-03026.
Routing - PLAN CHECK1/21/2005 1/24/2005  
Sent back to Plumbing.
1st review completed  1/21/2005 FAIL
failed plumbing
Routing - FIRE1/14/2005 1/21/2005 PASS
Routing - PLANNING1/11/2005 1/14/2005 PASS
Approved with the attached e-mail that shows the location of the intake vent in the soffit of the entry area. The intake vent shall not be visible on the facade.
Plan resubmittals received  1/12/2005 DONE
Accepted 8 1/2" x 11" resubmitted sheets intended to address Plumbing's concerns. Will route back to plumbing when plans are available.
Routing - PLUMBING1/7/2005 1/10/2005 FAIL
hair sinks are 2 fixture unit fixtures, 1 1/2" horizontal waste, 2 fixture unit loading max. only one sink on 1 1/2" waste line. condensate pump must be sized to accept full discharge of t&p line. provide information on pump and sump. 1 1/2" waste to station #5 sink must not berun above floor across access to utility room. vent system is undersized. indirect waste receptor may not be installed inside a wall . note on detail 2 M2.0.
Routing - PLAN CHECK1/3/2005 1/7/2005 PASS
The IBC plan review was started on January 6, 2005 and was finished the next day. The drawings were approved with clarifications. See the plan review report.
Routing - PUBLIC WORKS12/29/2004 1/3/2005 PASS
Application received  12/28/2004