Permit Information
Permit NumberBLD05-00597
StatusFinaled
Name DOWNTOWN STORAGE
Site Address 510 S 11TH ST
Project NameDOWNTOWN STORAGE
Customer Number 
ePlanReviewNo
Description
(DOWNTOWN STORAGE)(RACKING) To install steel storage racking exceeding 8' in height in a 6,705 sq. ft. area on the second floor in an existing storage building per approved plans and engineering. This is a Scope of Work Permit. A Letter of Completion is to be issued when done. NOTE: This building is fully fire sprinklered for area increase. JCB
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/15/20056/15/20056/15/2005PPASS
DetailsDave Hannah
ok for issuing L/C
FIRE-Final Inspection6/15/20056/15/20056/15/2005PCANC
DetailsForrest France
Duplicate inspection, already completed and passed in the AM.
FIRE-Final Inspection6/14/20056/15/20056/15/2005APASS
DetailsForrest France
Fire life safety finaled.
DOC - Permit Finaled6/15/20056/15/20056/15/2005PPASS
DetailsDave Hannah
FIRE-Final Inspection6/9/20056/9/20056/9/2005PFAIL
DetailsForrest France
Need current annual inspection on fire sprinkler system, provide sign at shaftway, fire ext. and its location sign must correspond.
BLD-Final6/8/20056/9/20056/9/2005APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 6/8/2005 at 9:22:59 AM. Contact: ###-####. evrey thing ok but needs sprk and L/F Finals
Issue PAID IN FULL permit  4/15/2005 DONE
Inspection Record Card- Bld  4/14/2005 DONE
Permit Ready to Issue  4/14/2005 DONE
Telephone call  4/14/2005 DONE
tlk to bill schenner ###-#### that permit and fees are ready to be picked up
Routing - FIRE4/11/2005 4/13/2005 PASS
DetailsBill Alexander
Routing - PLAN CHECK4/13/2005 4/13/2005 PASS
Permit and plans approved and taken to front desk.
PLANS/APPL TAKEN TO FRONT DESK  4/13/2005 PASS
Plan assigned to (JCB)3/15/2005 4/13/2005 PASS
4/13/2005 13:25:21 JCB - activity updated through activity BLDA022 from case BLD05-00597.
Routing - PLAN CHECK3/25/2005 4/11/2005 PEND
Received resubmittals required by Fire Dept. Plans to route to Fire Dept. for review of resubmittals. When approved by Fire Dept. permit can be issued.
Plan resubmittals received  4/8/2005 DONE
Received 1 Fire Code Review, 3 Hydraulic calcs, 2 Small Copys if sheet 1 of 1 , & 3 Copys of sheet FP1.0 Taken to Jason B.
Routing - FIRE3/23/2005 3/25/2005 FAIL
DetailsBill Alexander
Fire protection calculations do not meet requirements of NFPA 13, Chapter 14.
a. ROOF design is being verified for: .20/1500-ft/2 and head spacing of 98-ft/2 spacing. This will require more than 9 sprinklers operating for the most demanding/remote area of operation? Provide clarification, corrections and resubmit.

b. Average spacing of sprinklers for 9 heads operating would be average 166+ ft/2, which exceeds the maximum allowance of 130-ft/2 for standard spray sprinklers? Provide clarification, corrections and resubmit.

c. No dimensioned or scalable section view of the structure provided for verification of commodity height and ceiling/roof clearance. Fire Sprinkler Cover Sheet addresses a ceiling height of 13'-5". Storage height is reported to be 12'-4". This would be a clearance of 1'-1" (13") and does not meet the clearance for standard spray sprinklers (deflector to top of storage) of 18"? Provide clarification, corrections and resubmit.
1st review completed  3/25/2005 FAIL
DetailsBill Alexander
Failed in Fire.
Routing - PLAN CHECK3/15/2005 3/23/2005 PEND
When approved by Fire Department, permit can be issued. Plans to route to Fire Department for review.
Plans ACCEPTED BY PLAN TECH  3/9/2005  
Had Bill A. from Fire- look at plans before submittal.
Application received  3/8/2005  
Recd Pcfee & Taken To Pln CK  3/8/2005 DONE