Third Notice BLD | 5/25/2007 | 5/25/2007 | 6/21/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 5/9/2007 | 5/9/2007 | 5/25/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 4/25/2007 | 5/9/2007 | | DONE |
|
|
|
|
Permanent occupancy | | | 4/25/2007 | | DONE |
|
|
|
Perm. Occ. Cert. # 11550 issued 4-25-07 to Jems Properties.
|
Permanent Occupancy | | 4/24/2007 | 4/24/2007 | | DONE |
|
|
|
|
BLD-Aging Inspection | 3/13/2007 | 3/13/2007 | 3/15/2007 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Final | 1/10/2007 | 1/11/2007 | 1/11/2007 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/10/2007 at 4:47:53 PM. Contact: ###-####. ok pending others
|
Temporary occupancy | | | 1/11/2007 | | DONE |
|
|
|
Temp. Occ. Cert. # 5511 issued 1-11-07 to Jems Properties.
|
FIRE-Final Inspection | 1/9/2007 | 1/10/2007 | 1/10/2007 | P | PASS |
Forrest France
|
|
|
SD have been relocated, life safety inspection passed.
|
FIRE-Final Inspection | 1/8/2007 | 1/9/2007 | 1/9/2007 | A | FAIL |
Forrest France
|
|
|
Relocate smoke alarms per NFPA 72 2002.
|
BLD-Aging Inspection | 1/4/2007 | 1/4/2007 | 1/4/2007 | | NR |
Tom Arcoraci
|
|
|
|
Print Occupancy Form | | | 12/11/2006 | | DONE |
|
|
|
|
BLD-Aging Inspection | 10/31/2006 | 10/31/2006 | 10/31/2006 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 8/31/2006 | 8/31/2006 | 8/31/2006 | P | PASS |
Tom Arcoraci
|
|
|
derek - call prior to meet there; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
BLD-Framing/Rough-in | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PASS |
Tom Arcoraci
|
|
|
DERICK; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Framing/Rough-in | 7/5/2006 | 7/6/2006 | 7/6/2006 | A | PASS |
Tom Arcoraci
|
|
|
DERRICK; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Aging Inspection | 4/12/2006 | 4/12/2006 | 4/12/2006 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Foundation | 2/9/2006 | 2/10/2006 | 2/10/2006 | A | PASS |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 2/9/2006 at 12:36:27 PM. Contact: ###-####.
|
BLD-Footing | 2/6/2006 | 2/7/2006 | 2/7/2006 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 2/6/2006 at 3:16:33 PM. Contact: ###-####.
|
BLD-Aging Inspection | 12/29/2005 | 12/29/2005 | 12/29/2005 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Footing | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 10/25/2005 at 9:38:32 AM. Contact: ###-####.
|
Issue PAID IN FULL permit | | | 9/27/2005 | | |
|
|
|
|
Inspection Record Card- Bld | | | 9/23/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/23/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2005 | | DONE |
|
|
|
tlk to brian cooper ###-#### that his permit and fees are ready to be picked up
|
Plan assigned to (M_P) | 3/29/2005 | 3/29/2005 | 9/22/2005 | | PASS |
|
|
|
9/22/2005 10:54:22 M_P - activity updated through activity BLDA022 from case BLD05-00804.
|
Routing - PLAN CHECK | 9/20/2005 | | 9/22/2005 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2005 | | DONE |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 9/22/2005 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 9/22/2005 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 9/19/2005 | | 9/20/2005 | | |
|
|
|
Routing to planning.
|
Routing - PLANNING | 9/19/2005 | | 9/19/2005 | | PASS |
|
|
|
|
Routing - FIRE | 9/1/2005 | | 9/19/2005 | | PASS |
|
|
|
resubmittal acceptable.
|
Routing - PLAN CHECK | 8/19/2005 | | 9/1/2005 | | |
|
|
|
Routing to fire.
|
Routing - PLAN CHECK | 8/10/2005 | | 8/19/2005 | | PEND |
|
|
|
Waiting for others to approve prior to issuing permit.
|
Plan resubmittals received | | | 8/11/2005 | | DONE |
|
|
|
Received 1 Transmittal, 2 United Water sheets, & 2 Copys of sheet A2.1 Taken to Mike P.
|
Routing - FIRE | 7/29/2005 | | 8/10/2005 | | FAIL |
|
|
|
2 of the 4 resubmittal comments were not addressed by architect; revised comments faxed to architect.
|
Plan resubmittals received | | | 8/5/2005 | | |
|
|
|
Received (2) copies of sheet A2.1, A2.4, A3.1, A3.2, A3.4, A4, A5, EM-1 and EM-2. Routed to Mike P.
|
Routing - PUBLIC WORKS | 7/29/2005 | | 7/29/2005 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 7/20/2005 | | 7/29/2005 | | FAIL |
|
|
|
2nd review failed sent correction report to architect requesting additional informaiton be submitted for further review prior to issuing permit.
|
Routing - PUBLIC WORKS | 7/18/2005 | | 7/20/2005 | | FAIL |
|
|
|
Where sanitary sewer lines connect to public sewer they must be a min. of 1 foot apart and be perpendicular to the main line. Contact Jim Pardy ###-####
|
Routing - PLAN CHECK | 5/27/2005 | | 7/18/2005 | | |
|
|
|
Routing to plumbing.
|
Routing - PLUMBING | 7/18/2005 | | 7/18/2005 | | PASS |
|
|
|
increase water service piping to 1 1/4". thermol expantion protection required.
|
Routing - PLAN CHECK | 7/18/2005 | | 7/18/2005 | | |
|
|
|
Routing to P.W.
|
Plan resubmittals received | | | 7/8/2005 | | DONE |
|
|
|
Received Transmittal & 2 Copys of sheets C1.1,A1,A2.1,A2.2,A3.1,A3,A3.2,A4,A5,EM-1,EM-2 Taken to Mike P
|
Routing - FIRE | 5/24/2005 | | 5/27/2005 | | FAIL |
|
|
|
review faxed to architect.
|
1st review completed | | | 5/27/2005 | | FAIL |
|
|
|
failed planning, public works, plumbing, plan check, and fire.
|
Case Summary (BLD) | | | 5/24/2005 | | |
|
|
|
|
Routing - PLAN CHECK | 5/4/2005 | | 5/23/2005 | | FAIL |
|
|
|
Plan review completed, sent correction report to architect requesting additional informaiton be submitted for further review prior to issuing permit.
Sent submittal letter to architect on 4/5/05 and had meeting with architect stating items which needed to be corrected prior to my review.
|
Plan Reviewer's activity | | | 5/20/2005 | | HOLD |
|
|
|
Sent submittal letter to architect and had meeting with architect stating items which needed to be corrected prior to my review.
|
Plan resubmittals received | | | 5/13/2005 | | DONE |
|
|
|
Received 2 Letters , 2 Design Criterias, 1 Response & 2 Copys of sheets A0,A2.1,A2.4,A3,A3.1,A3.4,A6,P-1,P-2,A4,A5,EM-1,EM-2 Taken to Mike P.
|
Routing - PLANNING | 4/19/2005 | | 4/20/2005 | | FAIL |
|
|
|
Failed for noncompliance w/ conditions of approval #2, 4, 5, 10.
|
Routing - PLUMBING | 4/14/2005 | | 4/19/2005 | | FAIL |
|
|
|
see bld05-00802 for comments
|
Routing - Erosion and Sediment | 4/13/2005 | | 4/14/2005 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PLANNING Land Div | 3/29/2005 | | 4/7/2005 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 4/5/2005 | | 4/5/2005 | | HOLD |
|
|
|
Sent submittal letter to architect and had meeting with architect stating items which needed to be corrected prior to my review.
|
Plan routing begun/NEW & ADDTN | | | 3/29/2005 | | |
|
|
|
|
Application received | | | 3/25/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/25/2005 | | |
|
|
|
|
Fee Review-notes | 3/25/2005 | 3/25/2005 | | | |
|
|
|
|
Routing - PUBLIC WORKS | 4/7/2005 | | | | FAIL |
|
|
|
Failed by Brian Murphy - Requires drainage plan revisions. Contact at ###-####
Failed by Jim Pardy - Each building requires an individual connection to a main line as defined by DEQ.
|
Routing Off Site - STRUCTURAL | 3/29/2005 | | | | |
|
|
|
Called PDQ for pick up
|