BLD-Aging Inspection | 3/3/2008 | 3/3/2008 | 3/3/2008 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Expired | 3/3/2008 | 3/3/2008 | 3/3/2008 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | PASS |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 2/15/2007 at 1:26:11 PM. Contact: ###-####. ok for perm occ
|
FIRE-Final Inspection | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | PASS |
Forrest France
|
|
|
Corrections have been verified for completion, fire life safety inspeciton passed.
|
BLD-Final | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | FAIL |
Dave Hannah
|
|
|
ty; Phone #: ###-#### Internet Inspection Request from: Victoria Beall needs fire sign offs and smoke seals on doors
|
FIRE-Final Inspection | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | FAIL |
Forrest France
|
|
|
Post missing max. occupant load signs at two rooms in the new addition, provide approved hardware at the door to the SE day room as circled on approved plans.
|
FIRE-Final Inspection | 2/14/2007 | 2/14/2007 | 2/15/2007 | P | CANC |
Troy Cobbley
|
|
|
There was no time for inspection. Will need to reschedule.
|
FIRE-Conference | 7/25/2006 | 7/27/2006 | 7/27/2006 | A | DONE |
Forrest France
|
|
|
On site confrence to discuss project related fire alarm, cooking hood, and fire life safety work issues necessary to final BLD permits and establish an occupancy certificate. 60 day timeline for completion established with building manager and contractor.
|
Meeting | | | 7/27/2006 | | DONE |
|
|
|
On-site meeting held today with Dan Frazee, new maintenance Dir for Marquee Care, Dave Whiting with ADT, Sam Rogers and Forrest France to review status of fire alarm system. An existing system is installed essentially throughout both wings of the building but some modifications are required. They do not have plans of the existing system which Dave Whiting indicated was installed in 1998 under a permit by the City. The west wing, remodeled under BLD05-00849 which includes an Alzheimer's unit, is not occupied pending approval of the building permit, which is still contingent upon completion of alarm modifications. The west wing is fully occupied without a C of O which is part of the scope of BLD05-00849. Agreement was reached on a deadline of 60 days to complete the fire alarm work and obtain necessary final inspections to obtain a C of O for the entire facility. This is based on two weeks for alarm vendor to prepare plans and submit for a permit, two weeks for us to review and approve a permit, and 30 days to complete the installation work.
|
Case Summary (BLD) | | | 6/5/2006 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 6/2/2006 | | |
|
|
|
|
Attached Document | | | 6/2/2006 | | FAIL |
|
|
|
Received letter dated 6/1/06 requesting FD approval to occupy the newly remodeld area without fire alarm work being performed until 10/1/2006. Request denied. FD response letter is attached in Doc's as a PDF file; letter faxed to Mr. Rudd.
|
BLD-Framing/Rough-in | 2/2/2006 | 2/3/2006 | 2/3/2006 | A | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 2/2/2006 at 3:44:26 PM. Contact: ###-####. ceiling grid ok to cover
|
BLD-Conference | 1/31/2006 | 1/31/2006 | 2/1/2006 | P | PASS |
Dave Hannah
|
|
|
harvey -###-####
|
Plan resubmittals received | | | 12/30/2005 | | DONE |
|
|
|
Letter from architect and accompanying 8-1/2" x 11" drawings received and forwarded to Dan Stuart.
|
BLD-Framing/Rough-in | 12/22/2005 | 12/23/2005 | 12/23/2005 | A | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 12/22/2005 at 3:17:22 PM. Contact: ###-####.ceiling in corr ok
|
BLD-Framing/Rough-in | 11/9/2005 | 11/9/2005 | 11/10/2005 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 11/9/2005 at 10:48:13 AM. Contact: ###-####.lids in corr ok 2hr door needs 90 min grassing and smoke doors need 20 min
|
BLD-Framing/Rough-in | 9/20/2005 | 9/20/2005 | 9/21/2005 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/20/2005 at 9:33:11 AM. Contact: ###-####. mis framing north wing and nurses station ok to cover
|
BLD-Framing/Rough-in | 8/19/2005 | 8/19/2005 | 8/19/2005 | P | PART |
Dave Hannah
|
|
|
harvey ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie fire blocking on backside of corrodor walls
|
BLD-Framing/Rough-in | 8/1/2005 | 8/1/2005 | 8/1/2005 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 8/1/2005 at 8:41:07 AM. Contact: ###-####. steel studs in game room at entry ok to cover
|
Issue PAID IN FULL permit | | | 7/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 7/15/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 7/15/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/15/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/15/2005 | | DONE |
|
|
|
called told Armondo permit is ready and fees
|
Routing - FIRE | 7/8/2005 | | 7/14/2005 | | PASS |
|
|
|
resubmittal acceptable. Revised review comments faxed to architect.
|
Routing - PLAN CHECK | 7/14/2005 | | 7/14/2005 | | PASS |
|
|
|
To permit desk.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/14/2005 | | PASS |
|
|
|
To permit desk to issue.
|
Plan assigned to (DRS) | 3/31/2005 | | 7/14/2005 | | PASS |
|
|
|
7/14/2005 16:07:53 DRS - activity updated through activity BLDA022 from case BLD05-00849.
|
Routing - PLANNING | 7/8/2005 | | 7/8/2005 | | PASS |
|
|
|
Per note by Evelyn on Application cover sheet, there are no planning issues. Routing to fire.
|
Routing - PLAN CHECK | 5/17/2005 | | 7/8/2005 | | PEND |
|
|
|
Received and inserted new architectural, electrical, mechanical & plumbing plans with original plans. Routing plans to Planning then to fire code analyst for review.
|
Telephone call | | | 7/8/2005 | | DONE |
|
|
|
Called Gary Eichelberg to request certificate of value with all costs broken out, i.e. sprinkler modifications & alarm system modifications.
|
Plan resubmittals received | | | 6/30/2005 | | |
|
|
|
Received (2) copies of sheet A1.1, A1.2, A1.3, A2.1, A2.2, A2.3, A2.4, A2.5, A3.2, A6.1, M1.1, M2.1, M3.1, E1.0, E1.1, E2.0, E2.1 and E2.2. Routed to Dan S.
|
Routing - FIRE | 5/6/2005 | | 5/17/2005 | | FAIL |
|
|
|
faxed review to architect.
|
1st review completed | | | 5/17/2005 | | FAIL |
|
|
|
failed plan check and fire.
|
Plan resubmittals requested | | | 5/6/2005 | | DONE |
|
|
|
e-mailed and faxed copy of plan review report of items requiring correction to architect.
|
Routing - PLAN CHECK | 5/3/2005 | | 5/6/2005 | | FAIL |
|
|
|
e-mailed and faxed copy of plan review comments to architect for response.
|
Routing - Erosion and Sediment | 5/3/2005 | | 5/3/2005 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PLAN CHECK | 4/5/2005 | | 5/3/2005 | | PEND |
|
|
|
Received ESC plans applicable to this permit and existing permit, BLD02-00194. Routed to ESC for review.
|
Telephone call | | | 5/2/2005 | | DONE |
|
|
|
Called and talked with Gary Eichelberg, architect, concerning the required corridor width and minimum clear widths at doors across corridors as required in the 1961, 1967, 1997 UBC's and 2000 & 2003 IBC. Plans still show incorrect code compliance per original approved plans & code's under which designed and approved and current plans being reviewed. I wondered what had been done to doors to be changed under BLD02-00194 to bring into compliance. Gary did not know. Details on submitted sheets I am currently reviewing still show uncorrected details that failed during last plan review. Gary will check into what is being done in field and I will require plan resubmittals showing correct width's.
|
Plan resubmittals received | | | 4/7/2005 | | DONE |
|
|
|
Received Letter, Taken to Dan S.
|
Routing - PLUMBING | 4/1/2005 | | 4/5/2005 | | PASS |
|
|
|
per plans ans 2003 upc
|
Routing - PUBLIC WORKS | 3/31/2005 | | 4/1/2005 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/31/2005 | | |
|
|
|
|
Plan resubmittals received | | | 3/31/2005 | | DONE |
|
|
|
Received 3 Copys of sheets A1.3,A2.3,A3.2 Taken to Dan S.
|
Application received | | | 3/30/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/30/2005 | | DONE |
|
|
|
|
Fee Review-notes | 3/30/2005 | 3/30/2005 | | | |
|
|
|
|