Permit Information
Permit NumberBLD05-00978
StatusFinaled
Name PETRA INC
Site Address 850 W GOWEN RD
Project NameNORCO
Customer Number 
ePlanReviewNo
Description
Norco Acetylene Compressing Plant - To construct a new 8,260 square foot, one story, steel framed industrial building to be used as an acetylene gas compressing plant and a 1,950 square foot, steel framed, roof covered dock and related site improvements. The acetylene plant will consist of a 1,360 sq. ft., equipment room, a 285 sq. ft. mechanical room, a 455 sq. ft. office space with single restroom and small break room, a 4,400 sq. ft. charging room and two 880 sq. ft. covered loading docks at the east and west sides of the charging room. This building will be fire sprinklered with the exception of Equipment Room #104 The remote 1,950 sq. ft. covered dock is being reviewed as an outside storage area for hazardous materials. All construction per the approved plans and attached comment list. JCM These buildings were modified to change the building structures from engineer steel to SPECK (pre-engineered steel structures).
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice BLD7/23/20077/23/20077/26/2007 DONE
First Notice has not been responded to.
Fee Review-notes4/12/20054/12/20057/26/2007 DONE
Routing - PLAN CHECK3/24/2006 7/26/2007 PASS
First Notice 7/12/20077/23/2007 DONE
Permanent occupancy  5/16/2007 DONE
Perm. Occ. Cert. # 11590 issued 5-16-07 to NORCO.
Permanent Occupancy 5/4/20075/4/2007 DONE
Details
FIRE-Final Inspection4/25/20074/26/20074/26/2007PPASS
DetailsForrest France
Items on correction notice have been completed, final fire life safety inspection passed.
Code Occupancy Approval4/24/20074/24/20074/24/2007PPASS
DetailsDena Gambrel
04-24-06 After speaking to Cody and looking at new plans submitted, Cody signed off on new plans. Final occupancy signed. O.K. to release bond.
BLD-Aging Inspection2/23/20072/23/20072/23/2007 DEFR
DetailsJim Storey
sent to cod only outstanding isue to final out project.
BLD-Aging Inspection12/18/200612/18/200612/20/2006 DEFR
DetailsJim Storey
BLD-Aging Inspection10/16/200610/16/200610/16/2006 DEFR
DetailsJim Storey
pending p&z
BLD-Aging Inspection8/14/20068/14/20068/14/2006 FAIL
DetailsJim Storey
pending others
BLD-Aging Inspection6/13/20066/13/20066/13/2006 PASS
DetailsJim Storey
BLD-Final4/12/20064/13/20064/13/2006PPART
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles temp ok pending plm/p&z /fire perm sign offs. is aproved as resbmitals on file with planreview with respect to will winslow.
Temporary occupancy  4/13/2006 DONE
Temp. Occ. Cert. # 5398 issued 4-13-06 to the Norco Acetylene Compressing Plant.
FIRE-Final Inspection4/6/20064/7/20064/7/2006APART
DetailsTroy Cobbley
Plant manager ken goicoechea and jim ross signed for and verified the piping pressure tests, verified piping type/compatibility, color code and marking of the piping, verification of the PNID, installation and calabration of critical equipment, high level lime/sump alarm, acetone tank (seismic bracing not required per IBC), generator relief valves, compressor pressure switch verified, pressure relief verified on the discharge piping, transmission belts are of the static conducting type, piping pressure test conducted per ANSI B31.3 per documentation, matrix provided. Per jim ross the sensors will be tested monthly until a history is set and then at the manufactures recommendations. I have either verified the paper documentation or have witness the above items visually. Per Dave Hanniman a temporary occupancy is ok pending the repair of the north east exit sign/emergency light. Fire extinguishers at the field dock are to be mounted as discussed.
FIRE-Final Inspection4/5/20064/6/20064/6/2006PDEFR
DetailsForrest France
Inspection to be completed 4/7
FIRE-Final Inspection3/31/20063/31/20063/31/2006PFAIL
DetailsTroy Cobbley
Need to final fire alarm permit and provide corrections as marked on the fire dept. plan review comments.
Code Occupancy Approval3/30/20063/30/20063/30/2006PFAIL
DetailsDena Gambrel
03-24-06 Failed site inspection. No rock mulch per plans. Doug needs to either have planner o.k. no mulch, get mulch installed or get a price for the cost and bond. A correction notice was left with Doug.
03-30-06 Phone call from Doug. They will bond. Amount of Bond will be $10,727.00.
BLD-Grading Inspection3/28/20063/28/20063/28/2006 DONE
inspection done by D.Erskine on 03/23/06
Additional plans submitted  3/27/2006 DONE
Received letter from Wil Winslow with location of acetylene detectors, providing his technical opinion that the locations are suitable for the intended use. Included two copies with the Electrical/Mechanical resubmitted plan set which has not yet been issued.
Routing - FIRE3/14/2006 3/24/2006 PASS
Resubmittal pertains mostly to electrical and mechanical. Fire approval subject to "red" annotations on sheet E2.1MP relative to revised location of VSES switches; E2.1F Fire Alarm revisions not approved; requires review under the FA permit.
BLD-Aging Inspection3/21/20063/21/20063/22/2006 PART
DetailsJim Storey
walked job and adressed out standing isues.
Routing - ELECTRICAL2/16/2006 3/14/2006 PASS
DetailsJim Schmer
motors are rated as Group "D" and have been approved, see attached documents (Norco Letter1.pdf) on electrical permit ele05-02145. JMS
Additional plans submitted  3/3/2006 PASS
P&I diagrams (two copies Sheets 11 and 12) submitted and reviewed in meeting today with Jim Ross, Norco Mgr and Lee Rice, PDS/Mech Supv. Plans stamped approved and issued for inclusion with previously issued construction plans and field inspection reference (one copy to records; one copy for onsite inspector reference).
Plan resubmittals received  2/16/2006 DONE
Received Norco Acetylene Comperssing Plant- Plan Revisions, & 3 copys of sheets M-1,M-2A,M-2B,M-3,M-4,M-5,E0.0,E1.0,E2.0,E2.1F,E2.1L,E2.1MP,E2.1P These re- submittals will be routed to Jim S. then to Sam R. these plans had been issued on 6-29-06
Plan Modification Accepted  1/25/2006 PASS
Alternate Design Request by architect to use Class 1 Div 2, Group D, electrical equipment in lieu of Class 1 Div 2 Group A, has been approved by Electrical inspector supervisor Jim Schmer, Fire Marshal Dave Hanneman and Sam Rogers, based upon substantiating letters from Norco, REXARC, and Will Winslow, as well as telephone verification from UL that no electrical equipment has been approved by UL for Class 1 Group A locations. All related correspondence is to be scanned in with approved plans.
BLD-Framing/Rough-in1/17/20061/17/20061/17/2006PNR
DetailsJim Storey
ceiling grid///doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceilling ok pending ele. need to verify fire stopping before aproval or provide access.
BLD-Other1/10/20061/11/20061/11/2006APART
DetailsJim Storey
fire caulk inspection///doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa need listing for fire stopping . cleanouts and max anular space 5 inches 2 2 1/2 steel pipe.
FIRE-Final Inspection1/3/20061/4/20061/5/2006APART
DetailsForrest France
Limited use approval granted with Sam Rogers permission for the covered outside dock structure ONLY. No use or occupancy allowed for the main building at this time.
FIRE-Final Inspection12/21/200512/22/200512/22/2005APART
DetailsForrest France
On site confrence to discuss requirements for use approval at the separate covered loading dock structure.
BLD-Framing/Rough-in11/22/200511/22/200511/22/2005PPASS
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa wall screw insp. ok ok to insulate.
BLD-Framing/Rough-in11/14/200511/15/200511/15/2005APART
DetailsJim Storey
doug ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD-Framing/Rough-in10/20/200510/21/200510/21/2005APART
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore recived engineering to insp. # 6 girt sheet meatal atchment to studs ok need to verify at nex insp that #12 sidding screws are not into studs and only into straping.
Receive PAYMENT IN FULL PRINT  10/19/2005 DONE
CHANGE STATUS TO (ISS)  10/11/2005 DONE
already issued in june
Inspection Record Card- Bld  10/11/2005  
Print Occupancy Form  10/11/2005 DONE
Telephone call  10/11/2005 DONE
called ###-#### and left voicemessage for Becky that permit is ready and fees
Plan assigned to (JCM)9/8/2005 10/10/2005 PASS
10/10/2005 15:49:09 JCM - activity updated through activity BLDA022 from case BLD05-00978.
Plan resubmittals received  10/10/2005 DONE
Received 3 Copys of sheets S0.1,S0.2,S1.1,S1.2,S1.3,S2.1,S3.1 Taken to John M.
Plan Reviewer's activity  10/10/2005 PASS
Reviewed and approved plan modification to change the building structures from engineered steel to pre-engineered steel structures (SPECK Buildings). JCM
PLANS/APPL TAKEN TO FRONT DESK  10/10/2005 DONE
BLD-Conference10/5/200510/6/200510/6/2005AFAIL
DetailsJim Storey
there is a plan modification for here in review because they are changing from a structural bldg to a pre-engineered bldg.///doug ###-####
Override - Parcel Holds  10/5/2005  
BLD-Other9/7/20059/8/20059/8/2005APART
DetailsMike Jordan
grout & cmu wall inspection///Doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Footing9/7/20059/8/20059/8/2005APASS
DetailsMike Jordan
pour at 10:30///doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Plan resubmittals requested  9/8/2005 DONE
E-mailed the architect requesting additional clarification on the structural portion of the building modification. JCM
Override - Parcel Holds1/1/19001/1/19009/7/2005  
grout inspection
Override - Parcel Holds1/1/19001/1/19009/7/2005  
footing inspection
Plan resubmittals received  9/6/2005  
Received (3) copies of sheet S0.1, S0.2, S1.2, S2.1, S3.1 and (3) copies of structural calcs. Routed to John M.
Plan resubmittals received  9/6/2005  
Received (3) copies of sheet S1.3. Routed to John M.
BLD-Foundation8/29/20058/30/20058/30/2005PPASS
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa slab at dock ok hair pins.
Override - Parcel Holds1/1/19001/1/19008/29/2005  
BLD-Foundation8/24/20058/25/20058/25/2005PPASS
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Override - Parcel Holds1/1/19001/1/19008/24/2005  
BLD-Foundation8/22/20058/23/20058/23/2005APASS
DetailsJim Storey
brian --will pour at 12:30??; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Override - Parcel Holds1/1/19001/1/19008/22/2005  
ok to do fd insp per jim storey
BLD-Footing8/17/20058/18/20058/18/2005APASS
DetailsJim Storey
late am please//doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
BLD-Footing8/17/20058/17/20058/17/2005PPART
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Override - Parcel Holds1/1/19001/1/19008/17/2005  
Plan Modification Accepted  8/17/2005  
Plan Modification Accepted - Changing from Structural Building to Pre-Engineered Building. Please call John M. with any questions.
BLD-Foundation8/15/20058/16/20058/16/2005APASS
DetailsJim Storey
wall//doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
BLD-Foundation8/9/20058/9/20058/9/2005PPASS
DetailsJim Storey
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD-Foundation8/5/20058/8/20058/8/2005PPASS
DetailsMike Jordan
grout pour and CMU block walls inspection///doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa. no joint reinforcement from 0 to 6 ft. elev. at east wall, fill bldg. Eng. waS NOTIFIED and will send RFI
BLD-Foundation8/4/20058/5/20058/5/2005APASS
DetailsMike Jordan
doug ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie. Interior stemwalls.
BLD-Footing7/28/20057/29/20057/29/2005APASS
DetailsJim Storey
Pouring at 10:00 am doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore comprest gas loading area ft ok to east side of site ok.
BLD-Footing7/21/20057/25/20057/25/2005PPART
DetailsJim Storey
& rebar inspection please////doug; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
(F) Reprint permit  6/30/2005  
Issue PAID IN FULL permit  6/29/2005 DONE
Plan assigned to (JCM)4/14/2005 6/23/2005 PASS
6/23/2005 13:24:06 JCM - activity updated through activity BLDA022 from case BLD05-00978.
Routing - FIRE6/17/2005 6/23/2005 PASS
DetailsBill Alexander
Routing - PLAN CHECK6/23/2005 6/23/2005 PASS
PLANS/APPL TAKEN TO FRONT DESK  6/23/2005 DONE
Permit Ready to Issue  6/23/2005 DONE
Print Occupancy Form  6/23/2005 DONE
Inspection Record Card- Bld  6/23/2005 DONE
Telephone call  6/23/2005 DONE
called architect told him permit is ready and fees
Routing Off Site - STRUCTURAL6/15/2005 6/21/2005 PASS
Received e-mailed letter from the consulting structural engineer approving the final resubmittals. JCM
Routing - PLAN CHECK6/13/2005 6/17/2005  
Plan resubmittals received  6/16/2005  
Received (2) copies of sheet A-1 and S2.1. Routed to John M.
Plan resubmittals received  6/14/2005  
Received (2) copies of sheet S0.1, S0.2, S1.1, S1.2 and S1.3. Also received (3) copies of structural calcs. Routed to John M.
Routing - FIRE6/8/2005 6/13/2005 FAIL
Extension of the explosion resistant walls and additional information regarding vent design is required. Revised review comments discussed with architect and Will Winslow and faxed to architect.
Routing - PLAN CHECK6/7/2005 6/8/2005 PASS
Plan resubmittals received  6/8/2005 DONE
Received 2 responses to plan review report, 2 Copys of sheets SP-1,A-1,A-2,A-3,A-4,A-5.1,A-6,A-9,M-5,E2.1L,E2.1P Taken to John M.
Plan Reviewer's activity  6/8/2005 PASS
Reviewed and approved resubmittals as submitted with plan review red lined corrections. JCM
Routing - PUBLIC WORKS6/6/2005 6/7/2005 PASS
Routing - PLAN CHECK5/16/2005 6/6/2005  
Plan resubmittals requested  5/19/2005 DONE
FAxed the architect a copy of the second comment list from the consulting structural engineer. JCM
Routing Off Site - STRUCTURAL5/13/2005 5/19/2005 FAIL
Called PDQ for pick up -- Received e-mailed comment list from consulting structural engineer requesting additional calculations. JCM
1st review completed  5/16/2005 FAIL
failed structural, plan check and fire.
Routing - FIRE5/6/2005 5/16/2005 FAIL
review faxed to architect. 6/8/2005 approved grading permit BLD05-01544.
Plan resubmittals received  5/12/2005 DONE
Resubmittals received and forwarded to John: 1 cover letter from architect, 1 plan review response letter from structural engineer, 3 structural calcs, and 3 copies of plan sheets S0.1, S0.2, S1.1, S1.2, S1.3, S2.1, S3.1 and S3.2.
Plan resubmittals requested  5/6/2005 DONE
Mailed the architect a copy of the plan review comment list requesting revisions. JCM
Routing - PLAN CHECK4/27/2005 5/6/2005 FAIL
John M.
Plan resubmittals requested  4/28/2005 DONE
Faxed the architect a copy of the comment list from the consulting structural engineer requesting revisions. JCM
Routing Off Site - STRUCTURAL4/19/2005 4/27/2005 FAIL
Called PDQ for pick up - Received an e-mailed copy of the comment list from the consulting structural engineer requesting revisions. JCM
Routing - PLANNING4/26/2005 4/27/2005 PASS
Sara S. DRH04-00233
Approved per DRH04-00233.
Routing - PLUMBING4/20/2005 4/26/2005 PASS
FS-1 at note 12 page P-2 can not tie to sanitary sewer vents. note 4 page P-2, vents must be 6" above flood level of fixture before connecting to other vents. 120 deg. max hot water to public lavs. lable all non potable water piping and hose bibs per UPC. use septic tank and pump chamber per grading plan.
Routing - Erosion and Sediment4/20/2005 4/20/2005 PASS
ESC plan approved with attached conditions.
Routing - PUBLIC WORKS4/15/2005 4/20/2005 PASS
Routing - PLANNING Land Div4/14/2005 4/15/2005 PASS
Approved. Parcel is over 5 acres in size.
Plans ACCEPTED BY PLAN TECH  4/14/2005  
Plan routing begun/NEW & ADDTN  4/14/2005  
Application received  4/12/2005  
Recd Pcfee & Taken To Pln CK  4/12/2005 DONE