Second Notice BLD | 9/20/2005 | 9/20/2005 | 10/5/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 8/8/2005 | 9/20/2005 | | DONE |
|
|
|
|
Permanent occupancy | | | 8/8/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10678 issued 8-8-05 to Park Place Mtg.
|
FIRE-Conference | 8/4/2005 | 8/5/2005 | 8/5/2005 | A | PASS |
Forrest France
|
|
|
Fire life safety passed inspection.
|
BLD-Final | 8/4/2005 | 8/5/2005 | 8/5/2005 | A | PASS |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 8/4/2005 at 10:44:12 AM. Contact: ###-####. ok for perm occ
|
Permanent Occupancy | | 8/5/2005 | 8/5/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 8/1/2005 | 8/2/2005 | 8/2/2005 | A | FAIL |
Forrest France
|
|
|
Repair exit sign (failure to illuminate under backup power source), provide approved door hardware at the main entry/exit door to tenant space-manual thumbturn is not allowed, provide one 2A10BC fire extinguisher within tenant space along a normal path of travel with current inspection tag and the handle mounted no higher than 48" AFF, provide emergency light at hallway adjacent to the break room.
|
BLD-Framing/Rough-in | 7/6/2005 | 7/7/2005 | 7/7/2005 | A | PASS |
Dave Hannah
|
|
|
Don, ###-#### ok to cover
|
Issue PAID IN FULL permit | | | 6/24/2005 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 6/22/2005 | 6/22/2005 | 6/23/2005 | | PASS |
|
|
|
6/23/2005 09:27:57 RMH - activity updated through activity BLDA022 from case BLD05-01671.
|
Case Summary (BLD) | | | 6/23/2005 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 6/21/2005 | | 6/23/2005 | | PASS |
|
|
|
|
Routing - FIRE | 6/23/2005 | | 6/23/2005 | | PASS |
|
|
|
Field verify
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/23/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/23/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/23/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/23/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/23/2005 | | DONE |
|
|
|
lft vm with marvin meyer ###-#### that permit and fees are ready to be picked up
|
1st review completed | | | 6/23/2005 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/22/2005 | | |
|
|
|
|
Application received | | | 6/21/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/21/2005 | | |
|
|
|
|
Fee Review-notes | 6/21/2005 | 6/21/2005 | | | |
|
|
|
|