Second Notice BLD | 12/28/2005 | 12/28/2005 | 1/3/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 12/14/2005 | 12/28/2005 | | DONE |
|
|
|
|
Permanent Occupancy | | 12/14/2005 | 12/14/2005 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 12/14/2005 | | DONE |
|
|
|
Perm. Occ. Cert. # 10840 issued 12-14-05 to Thomas Hammer Coffee.
|
Temporary occupancy | | | 12/6/2005 | | DONE |
|
|
|
Temp. Occ. Cert. # 5335 issued 12-6-05 to Thomas Hammer Coffee.
|
BLD-Final | 12/1/2005 | 12/5/2005 | 12/5/2005 | P | PASS |
Dave Hannah
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok for perm occ
|
FIRE-Final Inspection | 11/29/2005 | 11/29/2005 | 11/29/2005 | A | PASS |
Forrest France
|
|
|
Fire life safety passed inspection.
|
FIRE-Final Inspection | 11/23/2005 | 11/28/2005 | 11/28/2005 | A | FAIL |
Forrest France
|
|
|
Fire life safety items appear satisfactory, however, the related fire sprinker permit work must be inspected and approved prior to life safety final.
|
BLD-Final | 11/16/2005 | 11/29/2005 | 11/28/2005 | P | CANC |
Dave Hannah
|
|
|
joel brown ###-#### Disp set to [CANC] by a contractor via Hello! on Nov 28 2005 11:41AM.
|
FIRE-Final Inspection | 11/23/2005 | 11/23/2005 | 11/23/2005 | P | CANC |
Forrest France
|
|
|
###-#### - joel No time available for this inspection today, to be rescheduled per conversation.
|
FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 | P | CANC |
Forrest France
|
|
|
|
BLD-Framing/Rough-in | 10/20/2005 | 10/21/2005 | 10/24/2005 | A | PASS |
Dave Hannah
|
|
|
jim stubbs; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to cover walls
|
BLD-Conference | 10/4/2005 | 10/5/2005 | 10/5/2005 | A | PASS |
Dave Hannah
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Conference | 10/5/2005 | 10/5/2005 | 10/5/2005 | P | PASS |
Dave Hannah
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Issue PAID IN FULL permit | | | 9/1/2005 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 8/30/2005 | | 8/30/2005 | | PASS |
|
|
|
connie
|
CHANGE STATUS TO (REV) | | | 8/30/2005 | | DONE |
|
|
|
changing plumbing
|
CHANGE STATUS TO (RDY) | | | 8/30/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 8/15/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/15/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2005 | | |
|
|
|
called architect (john price) ###-#### left message on voicemail permit its ready and fees.
|
Routing - FIRE | 8/3/2005 | | 8/12/2005 | | PASS |
|
|
|
Approved with conditions; review faxed to architect.
|
Plan assigned to (DRS) | 7/28/2005 | | 8/12/2005 | | PASS |
|
|
|
8/12/2005 14:47:56 DRS - activity updated through activity BLDA022 from case BLD05-01831.
|
1st review completed | | | 8/12/2005 | | FAIL |
|
|
|
failed Plan check and Public Works
|
Routing - PUBLIC WORKS | 8/12/2005 | | 8/12/2005 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/12/2005 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 8/12/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/12/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/8/2005 | | |
|
|
|
Received (3) copies of sheet A2.0, A2.2 and E2.1. Routed to Dan S.
|
Telephone call | | | 8/3/2005 | | DONE |
|
|
|
Called John Price concerning the door proposed for upgrade at the men's restroom on the second floor. This door needs to be a 60 minute assembly rather than the 45 minute shown. I also ask him about the restroom layout which differs from 2000 building plan on file. He said he drew the layout as it exists. He will also check the 2-hour shaft integrity for the north & south stair enclosures which show sideleight by the 1-1/2 hour doors into the enclosure. These should not be as shown. There is also a question on permits for Expressions T.I. of 2004 (BLD04-01353) and new tenant space for at east end of expressions (BLD00-03214) that have not been finaled and tenants do not have certificate of occupancy. This problem needs to be corrected.
|
Routing - PLAN CHECK | 7/12/2005 | | 8/3/2005 | | FAIL |
|
|
|
Clarifications coming from architect.Routing to fire code analyst for review.
|
Telephone call | | | 8/2/2005 | | DONE |
|
|
|
Call to John Price for clarifications on alternates. He said the alternate would be the scope of project. He is checking on outside air requirements and make-up air requirements for new hood and tenant use. I ask him to correct the electrical plan for energy code compliance because he had used the wrong factors and exceeded code requirements based on information provided. He will provide new sheets.
|
Plan assigned to (JCB) | 7/7/2005 | | 7/28/2005 | | DEFR |
|
|
|
Reassigned to Dan Stuart
|
Routing - PLUMBING | 7/11/2005 | | 7/12/2005 | | PASS |
|
|
|
per plans and 2003 upc
|
Routing - PUBLIC WORKS | 7/7/2005 | | 7/11/2005 | | FAIL |
|
|
|
Failed by Connie Baumgartner - ###-####
Need a menu to determine sewer fees.
|
Plans ACCEPTED BY PLAN TECH | | | 7/7/2005 | | |
|
|
|
|
Application received | | | 7/6/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/6/2005 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/12/2005 | | 8/12/2004 | | PASS |
|
|
|
Routing to permit desk.
|
Fee Review-notes | 7/6/2005 | 7/6/2005 | | | |
|
|
|
|