Third Notice BLD | 1/8/2007 | 1/8/2007 | 3/1/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Telephone call | | | 2/7/2007 | | DONE |
|
|
|
lft vm with erin regarding the cofv for 2 permit on one - needs to be on 2 separate cofv - I called and left ms 1/29 and calling again 2/7 3:30 pm
|
Second Notice BLD | 12/27/2006 | 12/27/2006 | 1/8/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 10/6/2006 | 12/27/2006 | | DONE |
|
|
|
|
Permanent Occupancy | | 10/6/2006 | 10/6/2006 | | DONE |
|
|
|
|
Permanent occupancy | | | 10/6/2006 | | DONE |
|
|
|
Perm. Occ. Cert. # 11237 issued 10-6-06 to Peterson Autoplex - Body Shop.
|
Code Occupancy Approval | | | 9/27/2006 | | PASS |
|
|
|
FINAL SIGNED AND RELEASE OF BOND
|
BLD-Aging Inspection | 8/10/2006 | 8/10/2006 | 8/10/2006 | | PASS |
Mike Jordan
|
|
|
wip on elec. final.
|
BLD-Final | 6/1/2006 | 6/2/2006 | 6/2/2006 | P | PART |
Mike Jordan
|
|
|
charlie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. ok for temp. occ. Will be ok for perm occ once others have finaled.
|
FIRE-Final Inspection | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
Temporary occupancy | | | 6/2/2006 | | DONE |
|
|
|
Temp. Occ. Cert. # 5409 issued 6-2-06 to the Peterson Autoplex.
|
FIRE-Final Inspection | 5/31/2006 | 6/1/2006 | 6/1/2006 | A | FAIL |
Troy Cobbley
|
|
|
Too early to do fire life safety inspection since fire alarm and fire sprinkler sprinkler permits are not ready for inspection. I went over the life safety comments with Erin and Charlie.
|
Code Occupancy Approval Temp | | | 5/24/2006 | | FAIL |
|
|
|
NEEDS TO BOND FOR LANDSCAPE, CURBING, FENCE, PAINT TOTAL BOND IS $120,000. WHEN RECIEVED I CAN SIGN TEMP OCCUPANCY.
|
BLD-Other | 5/17/2006 | 5/17/2006 | 5/17/2006 | P | PASS |
Mike Jordan
|
|
|
CHARLIE nOTE: GRIDING CEILING; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Framing/Rough-in | 4/18/2006 | 4/19/2006 | 4/19/2006 | A | PASS |
Mike Jordan
|
|
|
charlie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Interior steel stud walls.
|
BLD-Foundation | 1/10/2006 | 1/11/2006 | 1/11/2006 | A | PASS |
Mike Jordan
|
|
|
charlie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie. Stemwalls at north south and west ends.
|
BLD-Foundation | 1/10/2006 | 1/10/2006 | 1/10/2006 | P | CANC |
Mike Jordan
|
|
|
charlie ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie//per Charlie cancel inspection 1/10/06 12:00pm LEG
|
BLD-Foundation | 1/5/2006 | 1/6/2006 | 1/6/2006 | P | PART |
Jim Storey
|
|
|
and re-bar///requests early pm///tom; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa pwsi
|
BLD-Footing | 1/4/2006 | 1/5/2006 | 1/5/2006 | A | PART |
Mike Jordan
|
|
|
tom please do re-bar & footing inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. Footing on grid line 1. wip
|
BLD-Footing | 12/14/2005 | 12/15/2005 | 12/15/2005 | A | PART |
Jim Sly
|
|
|
tom ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Footing at North and West wall OK Pending special insp (MTI) tests and approvals.
|
BLD-Foundation | 12/13/2005 | 12/14/2005 | 12/14/2005 | A | PASS |
Mike Jordan
|
|
|
footing & foundation on screen wall only please////tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. Stemwall for screen wall at south end of lot.
|
(F) Reprint permit | | | 11/21/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/18/2005 | | |
|
|
|
|
(F) Reprint permit | | | 11/18/2005 | | |
|
|
|
|
Case Summary (BLD) | | | 11/17/2005 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/17/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/17/2005 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/17/2005 | | DONE |
|
|
|
David Moe called and I told him permit is ready and fees
|
Plan assigned to (MLO) | 8/31/2005 | | 11/17/2005 | | PASS |
|
|
|
11/17/2005 09:33:23 MLO - activity updated through activity BLDA022 from case BLD05-02381.
|
Routing - FIRE | 11/16/2005 | | 11/16/2005 | | PASS |
|
|
|
Plans sent to fire by others therefore not including responses sent to MLO for fire. MLO
Resubmittal acceptable. Revised review faxed to architect. SLR.
|
Routing - FIRE | 11/1/2005 | | 11/15/2005 | | FAIL |
|
|
|
No responses to fire review comments were with routed plans. Sent revised review comments to architect.
waiting for fire review comments prior to routing to fire MLO 10/24/2005
|
Routing - PUBLIC WORKS | 10/31/2005 | | 11/1/2005 | | PASS |
|
|
|
Brian Murphy ready to review.
|
Routing - PLAN CHECK | 10/31/2005 | | 10/31/2005 | | PASS |
|
|
|
|
Plan resubmittals received | | | 10/27/2005 | | DONE |
|
|
|
Received 1 transmittal letter, 1 memo to Sam R. 1 response to Sam R. 1 note to Trent Loci, & 2 copys of sheet A1.1 taken to Mike Otto
|
Routing Off Site - STRUCTURAL | 10/19/2005 | | 10/27/2005 | | PASS |
|
|
|
|
Plan resubmittals received | | | 10/24/2005 | | |
|
|
|
Received (2) copies of sheet A1.1and A10.1 with transmittal sheet. Routed to Mike O.
|
Routing - PLAN CHECK | 10/24/2005 | | 10/24/2005 | | PEND |
|
|
|
pending structural approval
|
Plan resubmittals requested | | | 10/19/2005 | | DONE |
|
|
|
IBC correction
|
Plan resubmittals received | | | 10/13/2005 | | DONE |
|
|
|
Received 1 Transmittal Letter, 1Memorandum,1 Multi -span Contrete Beam,1 Memo, & 3 Copys of sheets G1.1, A1.1,A5.1,A8.1,A10.1,S0.1,S5.1,E1.0,E1.1,E1.1A,E1.2,E1.3 Taken to Mike Otto.
|
1st review completed | | | 10/10/2005 | | FAIL |
|
|
|
failed Public works, structural, plan check and fire.
|
Routing - PLAN CHECK | 10/10/2005 | | 10/10/2005 | | PEND |
|
|
|
|
Routing - FIRE | 9/16/2005 | | 10/10/2005 | | FAIL |
|
|
|
review comments discussed with architect, Nova Verta, and Jane Rosen; review faxed to Architect.
|
Routing - PLAN CHECK | 9/12/2005 | | 9/16/2005 | | FAIL |
|
|
|
corrections sent to architect
|
Plan resubmittals requested | | | 9/16/2005 | | DONE |
|
|
|
IBC corrections
|
Routing Off Site - STRUCTURAL | 8/31/2005 | | 9/14/2005 | | FAIL |
|
|
|
Called PDQ for pick up sent corrections to architect
|
Plan resubmittals requested | | | 9/14/2005 | | DONE |
|
|
|
structural corrections
|
Routing - PLANNING | 9/8/2005 | | 9/12/2005 | | PASS |
|
|
|
DRH05-00063 Sara S. Approved per DRH05-00063
CUP05-00013 Susan R. I failed the review as I'm waiting for a letter from the S slough stating that the building can encroach into their easement. I'm moving plan on for others to review while I wait for the letter. Everything else looks fine. Fax was received 9/12 and plans were passed.
|
Routing - PLUMBING | 9/6/2005 | | 9/8/2005 | | PASS |
|
|
|
approved per plan and note.
|
Routing - PUBLIC WORKS | 8/31/2005 | | 9/6/2005 | | FAIL |
|
|
|
Failed by Brian Murphy, requires drainage plan revision. Contact at ###-####
|
Routing - Erosion and Sediment | 9/6/2005 | | 9/6/2005 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Plans ACCEPTED BY PLAN TECH | | | 8/31/2005 | | |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 8/31/2005 | | |
|
|
|
|
Routing - PLANNING Land Div | 8/31/2005 | | 8/31/2005 | | PASS |
|
|
|
Approved. Site is over 5 acres in size.
|
Application received | | | 8/29/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 8/29/2005 | | |
|
|
|
|
Routing - PLAN CHECK | 10/14/2005 | | 10/19/2004 | | FAIL |
|
|
|
contacted architect regarding minor corrections
|
Fee Review-notes | 8/29/2005 | 8/29/2005 | | | |
|
|
|
|