Permit Information
Permit NumberBLD05-02390
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC8660
ePlanReviewNo
Description
Micron Building #2 - C8660 - Remodel Stocker Room for RDA Tools. To construct approximately 19 lineal feet of cleanroom wall panels and egress door to divide Stocker room 107A into two rooms. One room will be approximately 386 sf. and the other will be 141 sf.. this permit also includes related electrical and mechanical modifications. This work is being done on the first floor of Builidng #2 at grid lines 10 and C.9&C.2. All construction per the approved plans. JCM

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice BLD10/27/200510/27/200512/6/2005 DONE
First Notice has not been responded to.
First Notice10/13/200510/13/200510/27/2005 DONE
DetailsJim Storey
BLD-Final10/12/200510/13/200510/13/2005APASS
DetailsJim Storey
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
DOC - Permit Finaled10/13/200510/13/200510/13/2005PPASS
DetailsJim Storey
BLD-Final10/12/200510/12/200510/12/2005PCANC
DetailsJim Storey
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
FIRE-Final Inspection10/11/200510/11/200510/12/2005PPASS
DetailsTroy Cobbley
Life safety finaled
FIRE-Final Inspection9/12/20059/13/20059/13/2005APART
DetailsForrest France
No final until associated fire alarm and fire sprinkler permits have been reviewed and inspected. Witnessed functionality and location of alarm devices today per agreement from Sam Rogers. Also noted that one sprinkler is overspaced at 140 sq. ft.
Issue & PRINT to be Invoiced  9/12/2005 DONE
Plan assigned from Web8/29/20059/8/20059/9/2005 DONE
DetailsJohn Menard
Plan assigned to (JCM)9/8/2005 9/9/2005 PASS
9/9/2005 09:45:01 JCM - activity updated through activity BLDA022 from case BLD05-02390.
Routing - FIRE9/8/2005 9/9/2005 PASS
Approved per on site review 9/8/05 subject to building plan annotation to increase 24" door to 36". Sprinkler plans not ready for review; discussed with designer; new plan to be prepared; will be ready next week for review.
Plan Reviewer's activity  9/9/2005 PASS
Reviewed and approved plans with red ined requirement for minimum width egress door of 36 inches. JCM
1st review completed  9/9/2005 PASS
PLANS/APPL TAKEN TO FRONT DESK  9/8/2005 DONE
Application received  8/29/2005 DONE
This permit was created on the web by Paul Marcolina
Third Notice BLD12/6/200512/6/2005   
Second Notice has not been responded to.