BLD-Final | 11/20/2017 | 11/21/2017 | 11/21/2017 | A | DONE |
Tony Young
|
|
|
|
DOC - Permit Finaled | 11/21/2017 | 11/21/2017 | 11/21/2017 | P | PASS |
Tony Young
|
|
|
done
|
Zoning Approval | 11/6/2017 | 11/6/2017 | 11/8/2017 | | PASS |
Sarah Schafer
|
|
|
|
BLD-Final | 11/6/2017 | 11/6/2017 | 11/6/2017 | P | NR |
Tony Young
|
|
|
Ward Phone #: ###-####
|
BLD-Final | 11/3/2017 | 11/3/2017 | 11/6/2017 | P | NR |
Tony Young
|
|
|
Ward Phone #: ###-####,, needs historical,, will need another T.I. permit for minor remodel
|
FIRE-Final Inspection | 11/1/2017 | 11/2/2017 | 11/2/2017 | A | PASS |
Troy Cobbley
|
|
|
life safety passed.
Pat Phone #: ###-####
|
FIRE-Final Inspection | 10/30/2017 | 10/31/2017 | 10/31/2017 | A | FAIL |
Troy Cobbley
|
|
|
The new fire extinguishers, although new, still require inspection tags and the previous corrections required exit discharge lighting that is not installed
|
BLD-Final | 10/23/2017 | 10/24/2017 | 10/24/2017 | P | NR |
Tony Young
|
|
|
Call half hour to meet // Ward Phone #: ###-####
|
FIRE-Final Inspection | 10/23/2017 | 10/24/2017 | 10/24/2017 | A | FAIL |
Jim Page
|
|
|
Provide exit light/emergency lighting in east vestibule to include exit discharge emergency lighting as shown on city approved drawings. Provide fire extinguishers with current inspection tags for basement level and level one, fire extinguishers must be mounted and in the path of common travel.
|
Fees Due Hold | 10/20/2017 | | 10/23/2017 | | DONE |
Brittany Hill
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/20/2017 | | DONE |
Christina Prado
|
|
|
Per Bob A. ok to re-issue to get FNL inspection & CO after 1 hr admin fee paid in full
|
Print Occupancy Form | | | 10/20/2017 | | DONE |
|
|
|
|
DOC - Permit Expired | 4/13/2010 | 4/13/2010 | 4/13/2010 | P | PASS |
Tony Young
|
|
|
|
BLD-Aging Inspection | 4/12/2010 | 4/12/2010 | 4/13/2010 | | FAIL |
Tony Young
|
|
|
expired
|
BLD-Aging Inspection | 11/20/2009 | 11/20/2009 | 11/27/2009 | | FAIL |
Tony Young
|
|
|
|
BLD-Aging Inspection | 8/21/2009 | 8/21/2009 | 8/28/2009 | | FAIL |
Tony Young
|
|
|
|
DOC - Permit Expired | 8/25/2009 | 8/25/2009 | 8/25/2009 | P | FAIL |
Tony Young
|
|
|
|
BLD-Conference | 12/23/2008 | 12/23/2008 | 12/23/2008 | P | FAIL |
Tony Young
|
|
|
see whats up w/ permit per 415 c/n posted to get finals performed
|
BLD-Aging Inspection | 9/8/2008 | 9/8/2008 | 9/10/2008 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 6/18/2008 | 6/18/2008 | 6/20/2008 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 11/23/2006 | 11/23/2006 | 11/24/2006 | | PASS |
Tony Young
|
|
|
|
BLD-Energy code compliance | 6/26/2006 | 6/27/2006 | 6/27/2006 | P | PASS |
Tony Young
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
BLD-Framing/Rough-in | 6/23/2006 | 6/26/2006 | 6/26/2006 | P | PASS |
Tony Young
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
BLD-Framing/Rough-in | 6/14/2006 | 6/15/2006 | 6/15/2006 | A | PART |
Dave Hannah
|
|
|
KEN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ext tower framing and sheeting ok to cover
|
BLD-Conference | 6/13/2006 | 6/14/2006 | 6/14/2006 | A | CANC |
Tony Young
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Foundation | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | PART |
Tony Young
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles front walls for entry,, mono w/ ftgs
|
BLD-Footing | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | PART |
Tony Young
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles close ftgs by front entry,, need tosee piers later,, will be monolithic
|
BLD-Footing | 5/31/2006 | 6/1/2006 | 6/1/2006 | P | NR |
Tony Young
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
BLD-Energy code compliance | 5/24/2006 | 5/24/2006 | 5/24/2006 | P | PART |
Tony Young
|
|
|
mike - inspect front exterior wall in lost river space; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles front wall ok to cover pending trades if any
|
BLD-Framing/Rough-in | 5/17/2006 | 5/17/2006 | 5/17/2006 | P | PART |
Tony Young
|
|
|
MIKE NOTE; PARTIAL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to insulate front wall area
|
BLD-Framing/Rough-in | 3/9/2006 | 3/10/2006 | 3/10/2006 | A | PART |
Tom Arcoraci
|
|
|
Mike -- for bathrooms partial final; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to use batrooms
|
BLD-Framing/Rough-in | 2/21/2006 | 2/21/2006 | 2/21/2006 | P | PART |
Dave Hannah
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to cover rest room
|
BLD-Framing/Rough-in | 1/24/2006 | 1/24/2006 | 1/24/2006 | P | PART |
Mike Jordan
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong. East restroom framing.
|
BLD-Aging Inspection | 1/20/2006 | 1/20/2006 | 1/20/2006 | | PASS |
Tony Young
|
|
|
|
Issue PAID IN FULL permit | | | 10/21/2005 | | |
|
|
|
|
Inspection Record Card- Bld | | | 10/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/18/2005 | | DONE |
|
|
|
|
Routing - PLANNING | 10/14/2005 | | 10/17/2005 | | PASS |
|
|
|
Approved per DRH05-00262.
|
Routing - PLAN CHECK | 10/17/2005 | | 10/17/2005 | | PASS |
|
|
|
Permit and plans approved and taken to front desk.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/17/2005 | | PASS |
|
|
|
|
Plan assigned to (JCB) | 9/8/2005 | | 10/17/2005 | | PASS |
|
|
|
10/17/2005 10:35:39 JCB - activity updated through activity BLDA022 from case BLD05-02431.
|
Routing - PLAN CHECK | 9/29/2005 | | 10/14/2005 | | PEND |
|
|
|
Plan review report e-mailed and faxed to architect. No response required. Some items have been red-lined on plans for clarification. Plans to route to the Planning Division again for review. When approved by the Planning Division the permit can be issued.
|
Telephone call | | | 10/13/2005 | | DONE |
|
|
|
Talked with structural engineer and she stated that the top chord of the cut trusses should have A35 connectors just to hold them in place. Most of the loading has been transferred down to the bottom chord with additional webs. She also stated that the exterior sheathing shall have panel edges/joints blocked. Will red-line on plans.
|
Plan resubmittals received | | | 10/13/2005 | | DONE |
|
|
|
Received 1 Transmittal Letter , & 2 Copys of sheet A1.0 Taken to Jason B.
|
Telephone call | | | 10/11/2005 | | DONE |
|
|
|
Called structural engineer to discuss/clarify some items. Some minor items will be red-lined. Additional calculations and summary information about items discussed will be faxed over to attach to the plans.
|
Plan resubmittals received | | | 10/10/2005 | | DONE |
|
|
|
Received 1 Special Inspections,1 Letter to Ward,& 4 Copys of sheet A2.0, & 2 Copys of sheet A4.0 Taken to Jason B.
|
Routing - PLANNING | 9/27/2005 | | 9/29/2005 | | FAIL |
|
|
|
Handicap parking space does not comply with condition 1a. Sent comments to Ward Schwider noting this, as well as option to obtain approval of the design from the A.D.A. Task Force.
|
Routing - Erosion and Sediment | 9/26/2005 | | 9/27/2005 | | PASS |
|
|
|
ESC waiver request approved with attached conditions.
|
Telephone call | | | 9/26/2005 | | DONE |
|
|
|
Talked with architect discussing issues needing to be addressed/shown on plans. He acknowledged and stated he would address and provide new resubmittal sheets.
|
Plan resubmittals requested | | | 9/26/2005 | | DONE |
|
|
|
Talked with architect on the phone to discuss issues needing to be addressed/shown on plans. Resubmittal plans required.
|
Plan Reviewer's activity | | | 9/23/2005 | | DONE |
|
|
|
Talked with Sam Rogers in Fire Dept. and he stated there was no need for a fire review. Fire Code issues to be field verified.
|
Telephone call | | | 9/23/2005 | | DONE |
|
|
|
Called and left message with architect concerning issues with the project. Would like to meet and discuss.
|
1st review completed | | | 9/23/2005 | | FAIL |
|
|
|
Failed in Planning, Erosion/Sediment Control, and with Plan Check.
|
Routing - PLAN CHECK | 9/16/2005 | | 9/23/2005 | | FAIL |
|
|
|
Called and left message with architect concerning would like to set up a meeting to go over several issues with the project. Plan resubmittals will be required. Plans to route to Erosion/Sediment Control for approval.
|
Routing - PLANNING | 9/13/2005 | | 9/16/2005 | | FAIL |
|
|
|
Site plan not drawn to scale. Cannot determine if handicap accessible parking space, ramp, and location comply with required dimensional standards. Handicap parking space needs to comply with A.D.A. requirements; applicant should contact A.D.A. task force for alternate design scenarios.
|
Plan resubmittals received | | | 9/16/2005 | | DONE |
|
|
|
Received ESC plan waiver request. Incerted into plan.
|
Plan resubmittals received | | | 9/15/2005 | | |
|
|
|
Received Erosion and Sediment Control Permit Application. Inserted into plan set.
|
Routing - Erosion and Sediment | 9/12/2005 | | 9/13/2005 | | FAIL |
|
|
|
No esc plan, plan waiver request or esc application submitted. Project will require a esc permit. Informed applicant.
|
Routing - PUBLIC WORKS | 9/8/2005 | | 9/12/2005 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/6/2005 | | |
|
|
|
|
Application received | | | 9/1/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/1/2005 | | DONE |
|
|
|
|
First Notice | 11/21/2017 | 11/21/2017 | | | |
Tony Young
|
|
|
|
Fee Review-notes | 9/1/2005 | 9/1/2005 | | | |
|
|
|
|