Permit Information
Permit NumberBLD05-02432
StatusFinaled
Name DEVCON CONSTRUCTION INC
Site Address 794 W BROAD ST
Project NameTULLY'S BODO 7
Customer Number 
ePlanReviewNo
Description
(TULLY'S - BODO BLDG #7 - 1ST STORY) This building is fire sprinklered for fire area and to allow the multitheater complex. To construct a restaurant within and existing 1,252 square foot tenant space located on the ground floor of BODO Building #7. Work is to include two restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, millwork, and finishes. A license is required from the City Clerk for the sidewalk seating area. The tenant shall contact the City Clerk's office directly for approval. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. This project was NOT approved by the Planning Division. None of the exterior work is approved. According to Jenifer Gilliland, Building Division Manager, a permanent Certificate of Occupancy will not be given until design review issues are resolved. **CJW**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD6/14/20066/14/20068/16/2006 DONE
Second Notice has not been responded to.
Second Notice BLD5/25/20065/25/20066/14/2006 DONE
First Notice has not been responded to.
First Notice 4/6/20065/25/2006 DONE
Permanent occupancy  4/6/2006 DONE
Perm. Occ. Cert. # 10978 issued 4-6-06 to Tully's.
BLD-Final4/4/20064/5/20064/5/2006PPASS
DetailsDave Hannah
paul fishley; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok for perm occ
FIRE-Final Inspection4/4/20064/5/20064/5/2006APASS
DetailsTroy Cobbley
Related alarm and sprinkler permits are approved, life safety finaled.
Permanent Occupancy 4/5/20064/5/2006 DONE
Details
BLD-Other2/9/20062/9/20062/9/2006 DONE
Temp. Occ. Cert. # 5319 extended for 90 days per Jenifer thru 5-22-06
Routing - PLANNING12/29/2005 12/2/2005 PASS
Passed per approved DR.
FIRE-Final Inspection11/22/200511/23/200511/23/2005PPART
DetailsForrest France
Items on the correction notice issued 11/22 have been completed, final pending alarm resubmittals for device address changes and shell permit finals for alarm and sprinkler.
BLD-Final11/22/200511/23/200511/23/2005PPART
DetailsDave Hannah
Forest will sign-off arround 1:00 pm. Please come to inspect shortly after. Thanks. Internet Inspection Request from: Alex Monge ok for temp occ ok to go perm after others go perm and shell is cc
BLD-Final11/22/200511/23/200511/23/2005ANR
DetailsDave Hannah
Please call when you arrive. Internet Inspection Request from: Alex Monge
Temporary occupancy  11/23/2005 DONE
Temp. Occ. Cert. # 5319 issued 11-23-05 to Tully's in the BODO, Bldg. # 7.
FIRE-Final Inspection11/22/200511/22/200511/22/2005PFAIL
DetailsForrest France
Lower the height of the provided fire extinguisher to 48" AFF, provide missing sprinkler escutcheon, remove tape from heads in the restrooms, provide additional emergency light in the back room as discussed.
FIRE-Final Inspection11/21/200511/21/200511/21/2005PNR
DetailsForrest France
The related fire alarm permit must be inspected and approved prior to life safety final.
BLD-Final11/16/200511/21/200511/21/2005ANR
DetailsTom Arcoraci
Internet Inspection Request from: Alex Monge
FIRE-Final Inspection11/16/200511/21/200511/21/2005ANR
DetailsForrest France
The related fire alarm permit work must be inspected and approved prior to life safety inspection and final.
FIRE-Sprinkler Rough-in11/7/200511/7/200511/7/2005PCANC
DetailsForrest France
Wrong inspection type called in by the general contractor, was intended for the sprinkler permit.
Plan Reviewer's activity  11/3/2005 DONE
Modified permit description and comments for clarity.
BLD-Wall cover10/31/200510/31/200511/1/2005PPASS
DetailsDave Hannah
Please call Dennis Harter. Internet Inspection Request from: Alex Monge ok to cover wall ok to cover ceiling after fire proofing is patched
BLD-Wall cover10/20/200510/24/200510/24/2005APART
DetailsDave Hannah
Cover-up inspection at Tully's. Early AM please. Internet Inspection Request from: Alex Monge hard lid and walls ok but need all other trades signed of do not cover
BLD-Wall cover10/20/200510/21/200510/24/2005APART
DetailsDave Hannah
Cover-up inspection at Tully's. Early AM please. I mistakenly scheduled you for Monday. Sorry. Internet Inspection Request from: Alex Monge ok to cover top 6ft of walls
Routing - PLAN CHECK10/14/2005 10/17/2005 DONE
Permit to be issued, per direction from Jenifer Gilliland. Approval of the project by the Planing Division was deferred until later. A permanent Certificate of Occupancy will not be given until design review issues are resolved. (note modified for clarity on 11-3-05)
PLANS/APPL TAKEN TO FRONT DESK  10/17/2005 DONE
Inspection Record Card- Bld  10/17/2005 DONE
Print Occupancy Form  10/17/2005 DONE
Permit Ready to Issue  10/17/2005 DONE
Telephone call  10/17/2005 DONE
called Sylvester Ramirez ###-#### and left voicemessage that permit is ready and fees
Issue PAID IN FULL permit  10/17/2005 DONE
Plan assigned to (CJW)9/9/2005 10/17/2005 PASS
10/17/2005 08:58:30 CJW - activity updated through activity BLDA022 from case BLD05-02432.
Routing - PLANNING10/13/2005 10/14/2005 FAIL
The applicant has not received DR approval for the requested items. The application is being processed under DRH05-00362.
Routing - FIRE10/12/2005 10/13/2005 PASS
resubmittal acceptable.
Routing - PLAN CHECK10/5/2005 10/12/2005 PASS
Drawings approved after resubmittal review.
Plan resubmittals received  10/11/2005  
Received (2) copies of sheet E1.1, E1.2 and E1.3. Routed to Carl W.
Plan resubmittals received  10/10/2005 DONE
Received 2 Copys pf sheet M1.0 Taken to Carl W.
Routing - FIRE10/4/2005 10/5/2005 FAIL
Fire review comment #1 regarding exiting discrepancies were not resolved by plan revisions or addressed in a response.
Routing - PLAN CHECK10/4/2005 10/4/2005  
Sent to Fire.
Routing - PLUMBING9/30/2005 10/4/2005 PASS
provide a floor sink at the beverage station per original plans if equipment requires. provide unit shutoff valve on water supply.
Routing - PLAN CHECK9/15/2005 9/30/2005 FAIL
One items still not resolved. Sent drawings back to Plumbing.
Plan resubmittals received  9/28/2005  
Received (2) copies of sheet A1.1, A5.0, A6.0, M1.0 and P1.0. Routed to Carl W.
Routing - PLAN CHECK9/13/2005 9/15/2005 FAIL
The IBC plan review was started on September 14, 2005 and was finished the next day. Revised drawings were required. See the plan review report.
Routing - FIRE9/15/2005 9/15/2005 FAIL
Review faxed to architect.
1st review completed  9/15/2005 FAIL
Review failed plumbing, plan check and fire.
Routing - PLUMBING9/12/2005 9/13/2005 FAIL
Need revised plumbing plan showing floor sinks and waste and vent piping to meet health dept., 2003 UPC and Idaho plumbing code for indirect waste connections in kitchen.
Routing - PUBLIC WORKS9/9/2005 9/12/2005 PASS
Plans ACCEPTED BY PLAN TECH  9/6/2005  
Application received  9/1/2005  
Pending Assignment by MYS9/1/2005 9/1/2005 DONE
Recd Pcfee & Taken To Pln CK  9/1/2005  
Fee Review-notes9/1/20059/1/2005   
Routing - PLAN CHECK12/2/2005