Case Summary (BLD) | | | 3/24/2015 | | DONE |
|
|
|
|
Second Notice BLD | 9/13/2007 | 9/13/2007 | 9/13/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 8/23/2007 | 9/13/2007 | | DONE |
|
|
|
|
Permanent Occupancy | | | 8/23/2007 | | DONE |
|
|
|
|
BLD-Final | 8/2/2007 | 8/2/2007 | 8/3/2007 | P | PASS |
Dave Hannah
|
|
|
ok for perm occ
|
FIRE-Final Inspection | 8/2/2007 | 8/2/2007 | 8/2/2007 | P | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
Meeting | | | 7/27/2007 | | DONE |
|
|
|
Per onsite meeting 7/27/07, Deputy Chief Dave Hanneman, Fire Marshal, approved standpipes in stairwells only, as acceptable to serve the horizontal exit separating section 1and Section 2.
|
BLD-Final | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | NR |
Dave Hannah
|
|
|
daryl Phone #: ###-#### need fire doors at horz exit fixed and stand pipe issue resolved and ok from fire on alarms and spinklers
|
Case Summary (BLD) | | | 7/20/2007 | | |
|
|
|
|
Code Occupancy Approval | | | 7/19/2007 | | DONE |
|
|
|
Meets plan requirements
|
BLD-Final | 5/1/2007 | 5/1/2007 | 5/1/2007 | P | PART |
Dave Hannah
|
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok for temp occ
|
FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 | P | NR |
Forrest France
|
|
|
daryl - fire life safety - as early as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 | | PART |
|
|
|
Approved for TOC.
|
Temporary occupancy | | | 5/1/2007 | | DONE |
|
|
|
Temp. Occ. Cert. # 5576 issued 5-1-07 to the Cityside Lofts.
|
BLD-Final | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | FAIL |
Dave Hannah
|
|
|
Darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt needs other trades finaled
|
BLD-Framing/Rough-in | 1/23/2007 | 1/24/2007 | 1/24/2007 | A | DONE |
Dave Hannah
|
|
|
darrel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Framing/Rough-in | 1/22/2007 | 1/23/2007 | 1/24/2007 | A | DONE |
Dave Hannah
|
|
|
darrel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Framing/Rough-in | 1/8/2007 | 1/9/2007 | 1/9/2007 | A | PART |
Dave Hannah
|
|
|
darrell ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith first floor corrador ok to cover
|
BLD-Energy code compliance | 12/29/2006 | 12/29/2006 | 1/2/2007 | P | PASS |
Dave Hannah
|
|
|
Daryl; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett first and second floor
|
BLD-Energy code compliance | 12/20/2006 | 12/20/2006 | 12/20/2006 | P | PART |
Dave Hannah
|
|
|
Daryl; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok to cover second floor appartments
|
BLD-Framing/Rough-in | 12/14/2006 | 12/15/2006 | 12/15/2006 | A | PART |
Dave Hannah
|
|
|
daryl ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to insulate 1st and 2nd floor
|
BLD-Framing/Rough-in | 12/6/2006 | 12/6/2006 | 12/7/2006 | P | NR |
Dave Hannah
|
|
|
daryl ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Framing/Rough-in | 11/29/2006 | 11/30/2006 | 11/30/2006 | A | PART |
Dave Hannah
|
|
|
darrell ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover third floor
|
BLD-Energy code compliance | 11/22/2006 | 11/24/2006 | 11/24/2006 | A | PART |
Dave Hannah
|
|
|
DARRELL; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover third floor room walls
|
BLD-Framing/Rough-in | 11/17/2006 | 11/20/2006 | 11/20/2006 | A | PART |
Dave Hannah
|
|
|
Darrel; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to insulate the third floor
|
BLD-Other | 11/14/2006 | 11/15/2006 | 11/15/2006 | A | PART |
Dave Hannah
|
|
|
darrell Note: drywall; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles first layer of rock 4thand 5th flr
|
BLD-Energy code compliance | 11/7/2006 | 11/8/2006 | 11/8/2006 | A | PART |
Dave Hannah
|
|
|
daryl ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover 4th floor rooms only
|
BLD-Framing/Rough-in | 11/1/2006 | 11/2/2006 | 11/2/2006 | A | PART |
Dave Hannah
|
|
|
Daryl; Phone #: ###-#### Internet Inspection Request from: Letitia Gallop ok to insulate the 4th and 5th floor units
|
BLD-Conference | 7/13/2006 | 7/17/2006 | 7/17/2006 | A | PASS |
Dave Hannah
|
|
|
meet dixie at 9 am Internet Inspection Request from: Barbara Buckley walked project with dixie and mec contractor
|
BLD-Conference | 6/8/2006 | 6/9/2006 | 6/9/2006 | A | DONE |
Dave Hannah
|
|
|
request per Dixie for her and Troy to do a conference
|
BLD-Conference | 6/8/2006 | 6/9/2006 | 6/9/2006 | A | DONE |
Troy James
|
|
|
request per Dixie for her and Troy to do a conference
|
Issue PAID IN FULL permit | | | 3/23/2006 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/20/2006 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/17/2006 | | DONE |
|
|
|
|
Plan assigned to (M_P) | 10/4/2005 | 10/4/2005 | 3/16/2006 | | PASS |
|
|
|
3/16/2006 16:08:12 M_P - activity updated through activity BLDA022 from case BLD05-02750.
|
Routing - PLAN CHECK | 3/7/2006 | | 3/16/2006 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/16/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 3/16/2006 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 3/16/2006 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 3/16/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/8/2006 | | |
|
|
|
Received 1 copy of Plan review response letter, 1 copy of revised Supplemental Structure calcs for metal decks, 3 copies of the following- A1.1, A8.0, A9.0, A10.0, A10.2, M1.0, M1.1, M1.2, M1.3, E1.0, E2.0, E3.0, E4.0, E5.0, E6.0, E7.0, E8.0 and taken to Mike P.
|
Routing - PLAN CHECK | 2/10/2006 | | 3/7/2006 | | FAIL |
|
|
|
Second review failed, talked to architect and requested additional plans to be submitted to clarify items discussed in our meeting. Further review required prior to issuing permit.
|
Routing - PLUMBING | 3/7/2006 | | 3/7/2006 | | PASS |
|
|
|
no changes
|
Routing Off Site - STRUCTURAL | 2/21/2006 | | 3/3/2006 | | PASS |
|
|
|
No further reveiw requried by outside engineering firm.
Called Action Couriers for pick up
|
Routing - PLANNING | 2/7/2006 | | 2/9/2006 | | PASS |
|
|
|
Approved.
|
Routing - PLAN CHECK | 11/4/2005 | | 2/7/2006 | | |
|
|
|
Routing to Planning.
|
Plan resubmittals received | | | 1/30/2006 | | |
|
|
|
Received 8 page response letter to review comments, project start up for special inspections package, 2 revised cert of values, response to Architecture review from Treasure valley Engineers letter and 5 pages of calcs, ans 3 pages of each A0.3,A1.0,A1.1,A2.0, A2.1, A2.2, A2.3, A2.4, A2.5, A3.0, A3.1, A3.2, A3.3, A3.4, A3.5, A3.6, A3.7, A3.8, A3.9, A3.10, A3.11, A3.12, A3.13, A3.14, A3.15, A3.16, A3.17, A3.18, A3.19, A3.20, A3.21, A6.1, A6.2, A6.3, A6.4, A6.5, A8.0, A8.1, A9.0, A10.0, A10.1, A10.2, A10.3, M1.0, M1.1, E1.0, E2.0, E3.0, E4.0, E5.0, E6.0, E7.0, E8.0; Taken to Mike Phillips
|
Plan resubmittals received | | | 12/16/2005 | | DONE |
|
|
|
Received 1 response , & 3 copys of sheets A2.6,A10.0,M1.0,M1.1,M1.2,M1.3 taken to Mike P.
|
Routing Off Site - STRUCTURAL | 11/23/2005 | | 12/14/2005 | | FAIL |
|
|
|
Second review failed e-mailed comments to architect.
|
1st review completed | | | 11/4/2005 | | FAIL |
|
|
|
FAILED BY PLANNING, PLAN CHECK AND MECHANICAL.
|
Routing - FIRE | 10/20/2005 | | 11/2/2005 | | PASS |
|
|
|
10/28/05 - Plans routed to FV.
|
Routing - PLAN CHECK | 9/2/2005 | | 10/20/2005 | | FAIL |
|
|
|
Plan review complete, sent correction report to architect requesting additional information be submitted for further review prior to issuing permit.
|
Routing - MECHANICAL | 10/20/2005 | | 10/20/2005 | | FAIL |
|
|
|
ROUTED OFF SITE to ICC Plan Review Services for mechanical plan review. (msouthard)
10/20/05 - Received plan review from ICC and sent copy to John Price.
|
Plan Reviewer's activity | | | 10/4/2005 | | |
|
|
|
Refer to BLD05-02204 for additional comments for routing.
|
Application received | | | 10/4/2005 | | |
|
|
|
|
Routing - PLANNING | 8/29/2005 | | 9/2/2005 | | FAIL |
|
|
|
Phasing application has not been submitted/approved. Original planning applications included office portion of development. Left phone message with John Price, architect, informing him of this action.
|
Routing - PLUMBING | 8/19/2005 | | 8/29/2005 | | PASS |
|
|
|
per plans and 2003 upc
|
Routing - Erosion and Sediment | 8/19/2005 | | 8/19/2005 | | PASS |
|
|
|
ESC plan approved with attached conditions--Under ESC05-00569.
|
Routing - PUBLIC WORKS | 8/17/2005 | | 8/19/2005 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 8/16/2005 | | 8/17/2005 | | PASS |
|
|
|
approved as tract a on ros 5113.
|