Letter of compliance | | | 12/15/2005 | | DONE |
|
|
|
Letter of Compliance issued 12-15-05.
|
BLD-Final | 12/14/2005 | 12/14/2005 | 12/14/2005 | P | PASS |
Mike Jordan
|
|
|
hilary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. ok for perm occ.
|
FIRE-Final Inspection | 12/13/2005 | 12/14/2005 | 12/14/2005 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Routing - FIRE | 12/2/2005 | | 12/12/2005 | | PASS |
Bill Alexander
|
|
|
The system design is approved for current occupancy requested rack use.
Received letter from De Best Fire Protection:
Origignal system design was: .315/2113-ft/2
Incorporating Tyco Model EC-25 EC Area/Density Heads, spaced a maximum of 14'-0" by 14'-0" with 214 degree F temp. (classified as High Temp) for Class IV commodities to a maximum 20'-0". The roof deck is 25'-10" with a commoditiy clearance of 8'-10". Origignal water supply used in the design was 75 psi datic, 20 residual @ 2,800 gpm flow dated 12/23/2003.
|
BLD-Final | 12/2/2005 | 12/5/2005 | 12/5/2005 | A | PART |
Jim Sly
|
|
|
hillary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Hold downs appear OK. Fire on Temp. OK to (perm) Final when Fire Dept finals. Call Hillary and see if she needs C of C, or just final in computer.
|
FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 | A | PART |
Forrest France
|
|
|
hilary - ###-#### A letter has been provided regarding the density available for the racking installation.
|
FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 12/1/2005 | A | CANC |
Forrest France
|
|
|
No time for inspection.
|
BLD-Final | 11/15/2005 | 11/17/2005 | 11/17/2005 | P | CANC |
Mike Jordan
|
|
|
hilary; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. fire/life finaled failed.
|
FIRE-Final Inspection | 11/15/2005 | 11/17/2005 | 11/17/2005 | A | FAIL |
Troy Cobbley
|
|
|
hilary; Phone #: ###-#### Provide verification that the overhead sprinkler system is adequate for the racks and commodities installed per the fire dept racking review comments. Provide height limit signs for the maximum storage height.
|
Issue PAID IN FULL permit | | | 11/8/2005 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 10/20/2005 | | 11/7/2005 | | PASS |
|
|
|
11/7/2005 13:00:33 CJW - activity updated through activity BLDA022 from case BLD05-02852.
|
Routing - FIRE | 11/3/2005 | | 11/7/2005 | | PASS |
|
|
|
Bill Alexander-Per some verification required in the review comments.
|
Routing - PLAN CHECK | 11/7/2005 | | 11/7/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 11/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/7/2005 | | DONE |
|
|
|
called ###-#### (Bill Bode) and ###-#### (Jerry Ricketts) and left voicemessage for both that permit is ready and fees
|
1st review completed | | | 11/7/2005 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/20/2005 | | 11/3/2005 | | PASS |
|
|
|
IBC plan review started on November 2 and finished the next day. The drawings and supporting engineering were approved.
|
Plans ACCEPTED BY PLAN TECH | | | 10/17/2005 | | |
|
|
|
|
Application received | | | 10/12/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/12/2005 | | |
|
|
|
|
Fee Review-notes | 10/12/2005 | 10/12/2005 | | | |
|
|
|
|