Second Notice BLD | 2/3/2006 | 2/3/2006 | 2/7/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 1/12/2006 | 2/3/2006 | | DONE |
|
|
|
|
FIRE-Final Inspection | 1/11/2006 | 1/11/2006 | 1/11/2006 | A | PASS |
Forrest France
|
|
|
Fire life safety finaled, inspection passed.
|
FIRE-Alarm Testing | 1/11/2006 | 1/11/2006 | 1/11/2006 | A | PASS |
Forrest France
|
|
|
Duct smoke detector functioned correctly.
|
BLD-Final | 1/11/2006 | 1/11/2006 | 1/11/2006 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 1/11/2006 at 6:59:58 AM. Contact: ###-####.pending fire sign off.
|
Permanent Occupancy | | 1/11/2006 | 1/11/2006 | | DONE |
|
|
|
|
Permanent occupancy | | | 1/11/2006 | | DONE |
|
|
|
Perm. Occ. Cert. # 10867 isued 1-11-06 to Sport Clips.
|
BLD-Other | 12/29/2005 | 12/29/2005 | 12/29/2005 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/29/2005 at 10:53:06 AM. Contact: ###-####.ceilling ok
|
BLD-Framing/Rough-in | 12/5/2005 | 12/6/2005 | 12/6/2005 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/5/2005 at 1:20:32 PM. Contact: ###-####.
|
Issue PAID IN FULL permit | | | 12/2/2005 | | DONE |
|
|
|
|
Plan assigned to (JCB) | 10/20/2005 | | 12/1/2005 | | PASS |
|
|
|
12/1/2005 11:14:50 JCB - activity updated through activity BLDA022 from case BLD05-02892.
|
Routing - PLUMBING | 11/30/2005 | | 12/1/2005 | | PASS |
|
|
|
Design still wrong on Island vents so I attached a copy of UPC section 909 approved per 2003 UPC
|
Routing - PLAN CHECK | 12/1/2005 | | 12/1/2005 | | PASS |
|
|
|
Permit and plans approved and taken to front desk.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/1/2005 | | PASS |
|
|
|
|
Print Occupancy Form | | | 12/1/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/1/2005 | | DONE |
|
|
|
called ###-#### and left voicemessge for Chris that permit is ready and fees
|
1st review completed | | | 11/30/2005 | | FAIL |
|
|
|
failed plumbing
|
Routing - FIRE | 11/17/2005 | | 11/30/2005 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 11/28/2005 | | DONE |
|
|
|
Plumbing resubmittal sheets routed to Plumbing Division for review.
|
Plan resubmittals received | | | 11/22/2005 | | |
|
|
|
Received (2) copies of sheet A.3. Routed to Jason B.
|
Routing - PLUMBING | 11/14/2005 | | 11/17/2005 | | FAIL |
|
|
|
show waste and vent piping to hair sinks complying with UPC 909 Special venting for Island fixtures; Provide Plumbing Fixture Schedule; Show trap primer for Floor drain by water heater; specify DCVA backflow asembly for backflow valve. Fire next.
|
Telephone call | | | 11/14/2005 | | DONE |
|
|
|
Called and left message to architect to follow up on additional information that was to be provided last week.
|
Plan resubmittals received | | | 11/14/2005 | | DONE |
|
|
|
Received faxed information from architect. Will attach to plans and red-line plans.
|
Routing - PLAN CHECK | 10/24/2005 | | 11/14/2005 | | PEND |
|
|
|
When approved by Plumbing and Fire Dept. permit can be issued. Plans to route to Plumbing and then to Fire Dept.
|
Plan Reviewer's activity | | | 11/8/2005 | | DONE |
|
|
|
Plumbing Division has stated that they would like to review the plans. Will route to Plumbing after building review.
|
Routing - PUBLIC WORKS | 10/20/2005 | | 10/24/2005 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 10/20/2005 | | |
|
|
|
|
Application received | | | 10/14/2005 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/14/2005 | | |
|
|
|
|
Fee Review-notes | 10/14/2005 | 10/14/2005 | | | |
|
|
|
|