Permit Information
Permit NumberBLD06-00205
StatusFinaled
Name ST LUKES REG MED CNTR
Site Address 190 E BANNOCK ST
Project NameST LUKES
Customer Number26-122
ePlanReviewNo
Description
(ST LUKES-ONE SOUTH-PHLEBOTOMY LAB) 7/13/06 - PLAN MODIFICATION SUBMITTED. MODIFICATION IS TO EXPAND THE AREA OF REMODEL OF ORIGINAL PERMIT BY 519 SQ. FT., FROM 2040 SQ. FT. TOO 2559 SQ. FT., TO THE NORTH & SOUTHWEST. Remodel of an existing 2,559 sq. ft. area for relocation of the Phlebotomy Lab per red-line notes on plans and all attached plan review conditions of all reviewing agencies as part of the approved plans. Work includes selective interior demolition; construction of non-combustible, fire-resistive walls to create blood draw areas, work, reception, Autology, temporary waiting,staff lounge/locker rooms and accessible route to all remodeled areas; construct two fully accessible restrooms and enlarge main waiting area; and upgrade electrical, plumbing, mechanical, fire suppression & alarm systems per tenant needs and minimum code compliance; modify suspended ceiling grid system, millwork & finishes. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Letter of compliance  8/14/2007 DONE
Letter of Complance issued 8-14-07
BLD-Final8/9/20078/13/20078/13/2007APASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/9/2007 at 3:13:04 PM. Contact: ###-####.
BLD-Final8/9/20078/9/20078/9/2007ANR
DetailsDave Hannah
Scheduled by a contractor via Hello! on 8/9/2007 at 6:43:21 AM. Contact: ###-####.
FIRE-Final Inspection8/8/20078/8/20078/8/2007APASS
DetailsForrest France
Final fire life safety inspection passed.
FIRE-Alarm Testing8/7/20078/8/20078/8/2007APASS
DetailsForrest France
Inspection intended for fire life safety.
BLD-Final7/18/20077/19/20077/20/2007ANR
DetailsDave Hannah
Scheduled by a contractor via Hello! on 7/18/2007 at 1:28:14 PM. Contact: ###-####. needs fire sprink and life saftey first
FIRE-Final Inspection7/18/20077/19/20077/19/2007AFAIL
DetailsTroy Cobbley
No inspection performed. Needs fire sprinkler final first.
BLD-Final4/26/20074/26/20074/26/2007PCANC
DetailsDave Hannah
Scheduled by a contractor via Hello! on 4/26/2007 at 6:24:04 AM. Contact: ###-####.
BLD-Final4/26/20074/26/20074/26/2007ANR
DetailsDave Hannah
Scheduled by a contractor via Hello! on 4/26/2007 at 6:24:04 AM. Contact: ###-####. needs fire life safty finals
FIRE-Final Inspection4/26/20074/26/20074/26/2007APART
DetailsForrest France
Need to complete related project permits pending completion of remodel work areas including the autology room for fire sprinkler and fire alarm as indicated on permit scope.
BLD-Wall cover3/7/20073/7/20073/7/2007APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 3/7/2007 at 6:40:18 AM. Contact: ###-####.
BLD-Aging Inspection7/27/20067/27/20067/31/2006 PASS
DetailsDave Hannah
Telephone call  7/26/2006 DONE
tlk to curtis that permit and fees are ready to be picked up
Override - Parcel Holds  7/26/2006  
Permit Ready to Issue  7/26/2006 DONE
(F) Reprint permit  7/26/2006 DONE
CHANGE STATUS TO (ISS)  7/26/2006 DONE
Plan assigned to (DRS)7/12/20067/12/20067/25/2006 PASS
7/25/2006 07:23:00 DRS - activity updated through activity BLDA022 from case BLD06-00205.
Routing - PLAN CHECK7/21/2006 7/25/2006 PASS
Plan Modification approved.
PLANS/APPL TAKEN TO FRONT DESK  7/25/2006 PASS
Plan Mod to permit desk for re-issue.
Override - Parcel Holds  7/25/2006  
Inspection Record Card- Bld  7/25/2006 DONE
Routing - FIRE7/18/2006 7/21/2006 PASS
Attached revised review comments to plans.
Routing - PLAN CHECK7/12/2006 7/18/2006 PEND
Routing to fire code analyst.
CHANGE STATUS TO (REV)  7/12/2006 DONE
Plan Modification
Plans ACCEPTED BY PLAN TECH  7/12/2006  
Plan Modification Accepted  7/11/2006  
The phlebotomy Lab has been shifted in order to provide additional seating in the admitting area, previous area was 2,040 new area is 2,559. please note the previous location of the smoke barrier has shifted slightly to accommodate the locker and break area. Although the areas ,design,and function of the tenant inprovement are very similar,all sheets are resubmitted to avoid confusion.
Issue & PRINT to be Invoiced  4/5/2006 DONE
Plan assigned to (DRS)2/6/2006 3/7/2006 PASS
3/7/2006 07:40:44 DRS - activity updated through activity BLDA022 from case BLD06-00205.
Routing - PLAN CHECK3/3/2006 3/7/2006 PASS
No further reviews required. routing to permit desk to issue.
PLANS/APPL TAKEN TO FRONT DESK  3/7/2006 PASS
Permit Ready to Issue  3/7/2006 DONE
Inspection Record Card- Bld  3/7/2006 DONE
Telephone call  3/7/2006 DONE
talked to curtis at ###-#### that permit is ready
Routing - PLUMBING3/2/2006 3/3/2006 PASS
per plans, resubmittal letter on lab sink backflow protection, and 120 deg. hot water to public lavs, and 2003 upc. no r.ps. required.
Routing - PLAN CHECK2/27/2006 3/2/2006 PEND
Received response to plumbing plan review from Josh Howa. Attaching response to plans and re-routing plans back to plumbing plan review.
Plan resubmittals received  3/2/2006 DONE
Received letter of transmittal, one plumbing review response letter and one copy of sheet LS-3 taken to Dan S. (:rad
Routing - FIRE2/23/2006 2/27/2006 PASS
Attached review comments to plans. Faxed review comments to architect.
1st review completed  2/27/2006 FAIL
Failed plumbing.
Routing - PLAN CHECK2/13/2006 2/23/2006 PEND
No resubmittals required. Routing to fire code analyst for review.
Routing - PLUMBING2/7/2006 2/13/2006 FAIL
120 deg. max hot water to public lavs. hot and cold water reduced pressure backflow preventors required at the sink in lab 15202. if any lab work is done in 15107 water lines must also be protected. eyewash at sink in 15202 must be potable water supplied. provide a location with drainage to accept discharge for r.p.s, above.
Routing - PUBLIC WORKS2/6/2006 2/7/2006 PASS
Plans ACCEPTED BY PLAN TECH  1/27/2006  
Application received  1/26/2006  
Fee Review-notes1/26/20061/26/2006