Permit Information
Permit NumberBLD06-00213
StatusFinaled
Name COLD STONE CREAMERY
Site Address 276 N 8TH ST
Project NameIDAHO BLDG-1ST FLR
Customer Number 
ePlanReviewNo
Description
(COLD STONE CREAMERY)(IDAHO BLDG-1ST FLR) To build-out a 1,588 sq.ft. shell tenant space, created under BLD06-00012, for use as an ice cream shop with seating. Work includes construction of interior non-bearing walls & millwork to create seating, service, work and storage areas as shown on the approved plans to include red-lined notes on plans and all plan review conditions attached to plans by all reviewing agencies. This building is fully sprinklered per 1994 UCBC because it is too tall and has too many stories. To upgrade restrooms for accessibility; install a suspended ceiling grid system; and add electrical, plumbing, mechanical & sprinkler system upgrades to meet tenant needs and meet minimum current adopted codes. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  6/2/2010 DONE
Third Notice 7/22/20097/27/2009 DONE
DetailsRita DeYoung
Second Notice BLD3/4/20093/4/20097/22/2009 DONE
DetailsRita DeYoung
First Notice has not been responded to.
Third Notice 3/11/20093/11/2009 DONE
DetailsRita DeYoung
First Notice 1/30/20093/4/2009 DONE
DetailsRita DeYoung
Permanent Occupancy  1/30/2009 DONE
DetailsBarbara Stitt
BLD-Conference10/28/200810/29/200811/4/2008APASS
DetailsDave Hannah
Barb-Dave could you please look at this and see if it can be finaled now that Fire passed? Phone #: ###-#### ok for perm occ
FIRE-Final Inspection8/14/20088/15/20088/18/2008APASS
DetailsForrest France
Okay for life safety final.
BLD-Final8/11/20088/12/20088/14/2008ADEFR
DetailsForrest France
Barb----Dave this was given temp on 6-9-06 and I need to know if they did what was required to give them perm? See activity notes regarding inspection on 6-9-06. Please let me know...thanks Phone #: ###-#### sent to fire
Telephone call  6/16/2006 DONE
Phoned Tony at Radix (###-####) to inform him that he will need to get a FA permit to connect the two duct detectors to the FACP. I also informed him that a double fee (work without a permit) would be applied to the FA permit. I explained to Tony that a "hold" has been placed on this building pernit which will not allow a permanent CofO until the FA permit is finaled.
FIRE-Final Inspection6/8/20066/9/20066/9/2006PPASS
DetailsForrest France
Corrections have been completed, inspection passed.
BLD-Final6/8/20066/9/20066/9/2006PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 6/8/2006 at 9:47:32 PM. Contact: ###-####. ok for temp occ needs ada signage fixed and vill finish signed off
FIRE-Alarm Testing6/9/20066/9/20066/9/2006PCANC
DetailsForrest France
Duplicate inspection request.
BLD-Final6/7/20066/8/20066/9/2006ANR
DetailsDave Hannah
JEAN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Temporary occupancy  6/9/2006 DONE
Temp. Occ. Cert. # 5412 issued 6-9-06 to Cold Stone Creamery.
FIRE-Final Inspection6/7/20066/8/20066/8/2006AFAIL
DetailsForrest France
Project related fire sprinkler permit is not yet finaled, mechanical issues with respect to duct detectors are not resolved.
Telephone call  6/7/2006 DONE
Called and talked with roger albers concerning protection of duct penetrations at alley side of exterior wall at 276 N 8th Strre that will serve cold stone creamery. Original plan review comment had required protection of duct penetrations by 1-1/2 hour fire dampers per Sec. 716 2003 IBC. Resubmittals had been provided showing installation of Smoke/Fire dampers at those locations. This would require tie in of smoke detection system to activate smoke dampers into the existing alarm panel. There is no current way to tie smoke dampers into existing panel. Since on fire dampers are required I ask Roger if he would like to modify plans to show code compliance but deleting smoke dampers. He said yes and will e-mail me a statement to stating the same.
Additional plans submitted  6/7/2006 PASS
Received e-mail from Roger Albers deleting smoke dampers from duct penetrations at south side alley wall which only require fire dampers of 1-1/2 hour rating with fuse-able link. The fire dampers as specified on plan will remain as a requirement. Copy of e-mail attached to original plans with portions of sheet M4.0 showing changes.
Plan Reviewer's activity  6/7/2006 DONE
Copy of change removing smoke dampers from sheet M4.0 with e-mail from Roger Albers, Mechanical Engineer from Engineering Inc stating the same given to fire dept., Mary Froemke and copy with original plans to records.
Case Summary (BLD)  6/6/2006  
FIRE-Final Inspection6/2/20066/2/20066/2/2006PFAIL
DetailsForrest France
Some items on the previous correction notice have been completed, however the new duct smoke detectors installed at two locations are not connected to the building fire alarm system as required. This work will require a fire alarm permit to be issued prior to installation. Also need to provide proof of a current annual inspection by a qualified fire sprinkler contractor on the building sprinkler system.
BLD-Final6/2/20066/2/20066/2/2006ACANC
DetailsJim Storey
Scheduled by a contractor via Hello! on 6/2/2006 at 6:41:07 AM. Contact: ###-####.n/r
FIRE-Final Inspection6/2/20066/2/20066/2/2006AFAIL
DetailsForrest France
Missing required fire extinguisher, need to repair non-functional emergency light above the main entry, provide approved door hardware at the main entry/exit and the back door (remove manual thumbturns, door knob), provide signage above main entry/exit, provide means to test the two duct smoke detectors.
FIRE-Final Inspection5/31/20066/1/20066/2/2006PFAIL
DetailsForrest France
The project related fire sprinkler permit must be requested for final inspection and approved prior to life safety final.
BLD-Final5/31/20066/1/20066/1/2006PNR
DetailsTony Young
Scheduled by a contractor via Hello! on 5/31/2006 at 2:48:56 PM. Contact: ###-####.
BLD-Framing/Rough-in5/31/20065/31/20065/31/2006PPASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 5/26/2006 at 3:45:45 PM. Contact: ###-####. ok to drop in ceiling panels
BLD-Other5/26/20065/30/20065/31/2006PFAIL
DetailsDave Hannah
Scheduled by a contractor via Hello! on 5/26/2006 at 3:45:45 PM. Contact: ###-####.ceiling grid wires not 1 in 6
Meeting  5/31/2006 DONE
Per 5/31/06 email from Tom Gainor: I met with Joe Anders of Park Lane Management at the Idaho Building and gave him the copy of the comments on the smoke control system in the atrium.While I was there, Joe tested the system and it seemed to function, I just don't know if it works. There are two (2) 110 v a.c. smoke detectors: one in the lobby and one at the top of the atrium. When they activate, two of the front doors open and the fans above the atrium start. The smoke detectors are not connected to the building fire alarm system.
The front doors are locked electronically, and will open when the detectors activate, even after hours. Joe is going to give the printout to Ken Howell and advise him that we need an engineer's evaluation of the smoke control system.Tom G.
BLD-Framing/Rough-in5/3/20065/4/20065/4/2006APART
DetailsDave Hannah
jerry - ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles soffit ok received arch cals and detail for sofit
Override - Parcel Holds1/1/19001/1/19005/3/2006  
Case Summary (BLD)  5/3/2006  
BLD-Framing/Rough-in5/1/20065/2/20065/2/2006APART
DetailsDave Hannah
Jerry; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
Override - Parcel Holds1/1/19001/1/19005/1/2006  
Jerry - Radix has done the framing and not the ceiling per instructions ikc 5/1/06
BLD-Framing/Rough-in4/25/20064/25/20064/25/2006PPART
DetailsDave Hannah
jerry --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie floor pents ok
Override - Parcel Holds1/1/19001/1/19004/25/2006  
needs fr insp
BLD-Conference4/20/20064/20/20064/20/2006PPASS
DetailsDave Hannah
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Issue PAID IN FULL permit  4/12/2006  
Additional plans submitted  4/11/2006 DONE
Recieved copy of conditions from Ken Howell, building owner agreeing to upgrade & conditions. copy attached to plans.
PLANS/APPL TAKEN TO FRONT DESK  4/11/2006 PASS
To permit desk to issue.
Print Occupancy Form  4/11/2006  
Print Occupancy Form  4/11/2006  
Telephone call  4/11/2006 DONE
called Radix Const. at ###-#### and left message w/JoAnne that permit is ready
Permit Ready to Issue  4/11/2006 DONE
Plan assigned to (DRS)2/6/2006 4/11/2006 PASS
4/11/2006 12:06:40 DRS - activity updated through activity BLDA022 from case BLD06-00213.
Routing - PLAN CHECK3/15/2006 4/11/2006 PASS
DetailsDan Stuart
Additional plans submitted  4/5/2006 DONE
Received signed and dated copy of conditions for issuance of this building permit from Stuart dennis, owner of Cold Stone Creamery. Copy attached to plans.
Plan resubmittals received  4/4/2006 DONE
Received new lighting compliance certificate and description of plan lighting modifications. Red-lined corrections on plans and attached electrical engineers submittal.
Plan resubmittals requested  4/3/2006 DONE
Requested corrections for lighting fixture compliance from rod mulder.
Plan resubmittals received  3/24/2006  
Received 1 copy of response to plan review comments, 2 copies of the following A0.1, A1.0, A2.0, A3.0, A5.0, M0.0, M1.0, M2.0, M3.0, M4.0, E1.0, E2.0, E3.0 and taken to Dan S.
Plan resubmittals received  3/17/2006  
Received 1 copy of cover transmittal, 1 page of analysis of plumbing fixture requirements, 2 copies of A1.0, A2.0 and taken to Dan S.
Routing - FIRE3/15/2006 3/15/2006 PASS
Attached review comments to plans. Faxed review comments to architect. Current approved upgrade agreement signed by owner.
Plan Reviewer's activity  3/10/2006 DONE
Faxed updated fire review comments to architect.
1st review completed  3/8/2006 FAIL
Failed Plan Check and Fire.
Routing - FIRE3/7/2006 3/8/2006 FAIL
Review completed. Approval pending legal decision on whether this permit may be issued with the unsigned fire alarm upgrade issues.
Plan resubmittals requested  3/7/2006 DONE
Faxed and e-mailed copy of plan review conditions to Gene Ulmer.
Print Pending Permit.LaserJet4  3/7/2006  
Case Summary (BLD)  3/7/2006  
Routing - PLAN CHECK2/14/2006 3/7/2006 FAIL
Copy of plan review conditions needing addressed by the architect were faxed and e-mailed to Gene Ulmer @ geneu@radixconstruction.com. Routing plans to fire code anlyst while waiting for response.
Routing - PLUMBING2/6/2006 2/14/2006 PASS
floor sinks must not be within cabinets or under equipment.
Routing - PUBLIC WORKS2/7/2006 2/9/2006 PASS
Pending Assignment by MYS1/26/2006 2/6/2006 DONE
2/6/2006 11:26:04 MYS - activity updated through activity BLDA168 from case BLD06-00213.
Plans ACCEPTED BY PLAN TECH  1/30/2006  
Application received  1/26/2006  
Recd Pcfee & Taken To Pln CK  1/26/2006  
Fee Review-notes1/26/20061/26/2006