Second Notice BLD | 6/21/2007 | 6/21/2007 | 7/18/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 5/24/2007 | 5/24/2007 | 6/21/2007 | | DONE |
Jim Storey
|
|
|
|
BLD-Final | 5/22/2007 | 5/24/2007 | 5/24/2007 | A | PASS |
Jim Storey
|
|
|
andy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
DOC - Permit Finaled | 5/24/2007 | 5/24/2007 | 5/24/2007 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 4/25/2007 | 4/26/2007 | 4/26/2007 | A | NR |
Jim Storey
|
|
|
Andy; Phone #: ###-#### Internet Inspection Request from: Victoria Beall fire
|
BLD-Aging Inspection | 4/17/2007 | 4/17/2007 | 4/17/2007 | | NR |
Jim Storey
|
|
|
talked with andy
|
BLD-Aging Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 | | NR |
Jim Storey
|
|
|
|
BLD-Aging Inspection | 10/23/2006 | 10/23/2006 | 10/23/2006 | | DEFR |
Jim Storey
|
|
|
need fire ncfi
|
BLD-Aging Inspection | 8/22/2006 | 8/22/2006 | 8/22/2006 | | PASS |
Jim Storey
|
|
|
wip
|
BLD-Conference | 6/19/2006 | 6/21/2006 | 6/21/2006 | A | PASS |
Jim Storey
|
|
|
Call when finished with Greg.Tkx, jgilmore; Phone #: ###-#### Internet Inspection Request from: Jim Gilmore
|
BLD-Conference | 5/26/2006 | 5/30/2006 | 5/30/2006 | A | PASS |
Jim Storey
|
|
|
Just want a conference for remodel. call Harry when done with Greg K. In the same area. Thank, Harry; Phone #: ###-#### Internet Inspection Request from: Harry Thompson
|
Issue & PRINT to be Invoiced | | | 4/28/2006 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 2/23/2006 | | 4/28/2006 | | PASS |
|
|
|
4/28/2006 11:23:29 JCM - activity updated through activity BLDA022 from case BLD06-00437.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/24/2006 | | DONE |
|
|
|
|
Routing - FIRE | 3/23/2006 | | 3/23/2006 | | PASS |
|
|
|
Plans reviewed on-site and approved subject to "red" annotations on plans, including exit signage, stairwell exit door location, EES strobe locations and smoke detectors at corridor doors, to be field verified by the PDS fire inspector. AS and FA plans are ready for review.
|
Plan Reviewer's activity | | | 3/16/2006 | | PASS |
|
|
|
Reviewed and approved plans in the City office for this project. JCM
|
1st review completed | | | 3/13/2006 | | FAIL |
|
|
|
Additional information requested before review can be done. JCM
|
Application received | | | 2/23/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|
Routing - FIRE | 2/23/2006 | | 2/3/2006 | | FAIL |
|
|
|
Paul to revise plans showing the exit plan and rated doors as required and address hazardous materials. Plans are to be submitted for in-office review due to complexity of proposed H-5 occupancy. FA plans not ready; need to be revised to include (e) and (n) emergency pulls at exits of the entire H-5 space, including portions of the H-5 space which were previously modified to eliminate an exit corridor.
|
Third Notice BLD | 7/18/2007 | 7/18/2007 | | | |
|
|
|
Second Notice has not been responded to.
|
Plan assigned from Web | 2/23/2006 | 3/5/2006 | | | |
|
|
|
|