Second Notice BLD | 1/2/2009 | 1/2/2009 | 1/5/2009 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | 11/26/2008 | 11/26/2008 | 1/2/2009 | | DONE |
Tony Young
|
|
|
|
DOC - Permit Finaled | 11/26/2008 | 11/26/2008 | 11/26/2008 | P | PASS |
Tony Young
|
|
|
|
BLD-Final | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | PASS |
Tony Young
|
|
|
curt Phone #: ###-####
|
FIRE-Final Inspection | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 11/21/2008 | 11/24/2008 | 11/25/2008 | P | NR |
Tony Young
|
|
|
curt Phone #: ###-####
|
FIRE-Final Inspection | 11/20/2008 | 11/24/2008 | 11/24/2008 | A | DEFR |
Forrest France
|
|
|
Inspection rescheduled
|
BLD-Final | 11/20/2008 | 11/21/2008 | 11/21/2008 | P | NR |
Tony Young
|
|
|
curt Phone #: ###-#### need f/l/s 1st
|
Additional plans submitted | | | 4/21/2008 | | DONE |
|
|
|
Final inspection and approval reports by third parties received for smoke control and stair pressurization systems received. Documents attached.
|
FIRE-Final Inspection | 1/8/2008 | 1/9/2008 | 1/9/2008 | A | PART |
Forrest France
|
|
|
3rd floor fire life safety is satisfactory, noted the posted fire extinguishers are currently in process of re-certification to be completed promptly as discussed.
|
BLD-Other | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | PASS |
Tony Young
|
|
|
ceiling grid, kirt Phone #: ###-#### s/w 3 ok, pending trades
|
BLD-Final | 12/26/2007 | 12/28/2007 | 12/28/2007 | A | CANC |
Tony Young
|
|
|
kirt Phone #: ###-####
|
BLD-Other | 11/26/2007 | 11/27/2007 | 11/27/2007 | P | PART |
Tony Young
|
|
|
CURT NOTE: COVER Phone #: ###-#### north 1/2 of n/w corner ceiling ok to cover, 3rd floor
|
Override - Parcel Holds | 11/26/2007 | 1/1/1900 | 11/26/2007 | | |
|
|
|
GRID BEFORE COVER
|
BLD-Final | 11/7/2007 | 11/8/2007 | 11/8/2007 | A | PART |
Tony Young
|
|
|
curt - 3 ne Phone #: ###-#### this area ok
|
BLD-Final | 11/6/2007 | 11/7/2007 | 11/7/2007 | A | CANC |
Tony Young
|
|
|
curt Phone #: ###-####
|
BLD-Final | 11/7/2007 | 11/7/2007 | 11/7/2007 | P | NR |
Tony Young
|
|
|
curt Phone #: ###-####
|
BLD-Other | 10/31/2007 | 11/1/2007 | 11/1/2007 | A | PART |
Tony Young
|
|
|
justin - ceiling Phone #: ###-#### ceiling in north east corner ok
|
BLD-Framing/Rough-in | 10/25/2007 | 10/31/2007 | 10/31/2007 | P | CANC |
Tony Young
|
|
|
justin - ceiling Phone #: ###-#### out of time, resched for am
|
BLD-Other | 10/30/2007 | 10/30/2007 | 10/30/2007 | P | PART |
Tony Young
|
|
|
Justin, ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt 1/2 of quad ok
|
FIRE-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 | A | PART |
Forrest France
|
|
|
Fire life safety for the 3rd floor SE quadrant is acceptable.
|
FIRE-Final Inspection | 10/17/2007 | 10/19/2007 | 10/19/2007 | A | CANC |
Forrest France
|
|
|
Overbooked.
|
FIRE-Conference | 8/29/2007 | 9/4/2007 | 9/4/2007 | A | DONE |
Forrest France
|
|
|
Discussion regarding atrium smoke evac testing and stairwell pressure test.
|
FIRE-Final Inspection | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | DEFR |
Forrest France
|
|
|
Intended for BLD07-00352 first floor TI modifications.
|
BLD-Other | 7/19/2007 | 7/20/2007 | 7/20/2007 | A | PASS |
Dave Hannah
|
|
|
kirt Note: ceiling grid Phone #: ###-#### ok to cover after fire and mec oks
|
BLD-Other | 6/21/2007 | 6/22/2007 | 6/22/2007 | P | PASS |
Dave Hannah
|
|
|
curt - ceiling grid; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
BLD-Other | 6/4/2007 | 6/4/2007 | 6/4/2007 | P | PART |
Tony Young
|
|
|
curt - ceiling grid ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith north/west 1/2 quad ok 1st floor
|
BLD-Final | 6/1/2007 | 6/4/2007 | 6/4/2007 | A | CANC |
Tony Young
|
|
|
curt - ceiling grid ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Framing/Rough-in | 5/16/2007 | 5/17/2007 | 5/17/2007 | P | PART |
Dave Hannah
|
|
|
Grid ceiling inseption please--curt 1st floor NE quad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ceiling grid ok to cover ne 1/4 1st floor
|
BLD-Other | 5/10/2007 | 5/11/2007 | 5/15/2007 | P | PASS |
Dave Hannah
|
|
|
curt - final grid ceiling inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Other | 4/25/2007 | 4/27/2007 | 4/27/2007 | P | PART |
Dave Hannah
|
|
|
curt - above ceiling structure ; Phone #: ###-#### Internet Inspection Request from: Patricia 1st floor se quad ok to cover
|
BLD-Other | 1/23/2007 | 1/23/2007 | 1/23/2007 | P | PART |
Jim Sly
|
|
|
curt- above ceiling; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 4th Floor SW. Quad Ceiling OK
|
BLD-Other | 1/17/2007 | 1/18/2007 | 1/18/2007 | A | PART |
Dave Hannah
|
|
|
CURT - ABOVE CEILING INSPECTION; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover south east qud
|
BLD-Other | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | FAIL |
Dave Hannah
|
|
|
curt - note: above ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Victoria Beall needs to plump and add wires
|
BLD-Final | 12/26/2006 | 12/27/2006 | 12/27/2006 | A | PART |
Dave Hannah
|
|
|
curt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to occ second floor
|
FIRE-Final Inspection | 12/22/2006 | 12/22/2006 | 12/26/2006 | P | PART |
Forrest France
|
|
|
Corrections at the 2nd floor have been verified for completion, fire life safety is satisfactory for the second floor perimeter areas.
|
FIRE-Final Inspection | 12/11/2006 | 12/14/2006 | 12/14/2006 | P | FAIL |
Forrest France
|
|
|
Missing one row of fire sprinkler heads at the transition between the SE and SW quadrants, door hardware at the two restrooms in the NE quad is not approved, need to provide additional emergency lighting at the exits to the NW stair tower.
|
BLD-Other | 12/1/2006 | 12/4/2006 | 12/5/2006 | P | PART |
Dave Hannah
|
|
|
curt - ceiling tile ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover after all other trades sign off
|
BLD-Framing/Rough-in | 10/31/2006 | 11/1/2006 | 11/2/2006 | P | PART |
Dave Hannah
|
|
|
curt - note: above ceiling insp. approval for cover - as late as possible in the afternoon ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ceiling grid ok
|
BLD-Conference | 10/24/2006 | 10/25/2006 | 10/25/2006 | P | PASS |
Dave Hannah
|
|
|
kirt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wires for elec to ceiling grid
|
BLD-Final | 10/12/2006 | 10/13/2006 | 10/16/2006 | P | DEFR |
Dave Hannah
|
|
|
curt - note: partial ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to occ the se 1/4 of floor2
|
BLD-Other | 10/10/2006 | 10/11/2006 | 10/11/2006 | P | PART |
Dave Hannah
|
|
|
kirt Note: structural ceiling ins; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to drop in panels after elec oks
|
BLD-Final | 10/9/2006 | 10/10/2006 | 10/10/2006 | A | NR |
Dave Hannah
|
|
|
curt - partial ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Framing/Rough-in | 9/21/2006 | 9/22/2006 | 9/22/2006 | A | PART |
Tom Arcoraci
|
|
|
kirt Note: ceiling grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
BLD-Framing/Rough-in | 9/11/2006 | 9/12/2006 | 9/12/2006 | A | PART |
Dave Hannah
|
|
|
curt - steel stud; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley out fire cont house ok to cover ext
|
BLD-Footing | 8/30/2006 | 8/31/2006 | 8/31/2006 | A | PASS |
Dave Hannah
|
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Darla Downs fire control room
|
Issue PAID IN FULL permit | | | 8/22/2006 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/12/2006 | | 8/15/2006 | | PASS |
|
|
|
Permit and plans approved and taken to front desk.
|
Plan resubmittals received | | | 8/15/2006 | | DONE |
|
|
|
Fax resubmittals received for change in structural framing of Fire Command Center.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2006 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 8/15/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2006 | | DONE |
|
|
|
tlk to lance fish ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 8/15/2006 | | DONE |
|
|
|
|
Plan assigned to (JCB) | 4/28/2006 | | 8/15/2006 | | PASS |
|
|
|
8/15/2006 10:27:27 JCB - activity updated through activity BLDA022 from case BLD06-01188.
|
Routing - FIRE | 8/9/2006 | | 8/12/2006 | | PASS |
|
|
|
Attached review comments to plans.
|
Telephone call | | | 8/11/2006 | | DONE |
|
|
|
Called Lance Fish of ZGA to request an additional structural calc. for the changed roof structure construction on the Fire Command Center. He stated he will provide on Monday 8/14/06.
|
Plan resubmittals received | | | 8/10/2006 | | DONE |
|
|
|
Received transmittal letter, with details for A3,B3,E1 and keynotes from sheet A501 taken to Jason B.
|
Routing - PLANNING | 8/7/2006 | | 8/9/2006 | | PASS |
|
|
|
CZC06-00069 Josh Wilson
|
Routing - PLAN CHECK | 7/12/2006 | | 8/7/2006 | | FAIL |
|
|
|
One last item to address, Fire Command Center Roof-ceiling Assembly. Called architect and he will address. Plans to route to Planning and then to Fire Dept.
|
Plan resubmittals received | | | 7/31/2006 | | |
|
|
|
Received 2pg. letter to Jason Blais from Lance Fish, 5pg. response, 3pg. fire protection details, revised certificate of value, 5pg. Project Start Up for Special Inspections, 2pg. letter addressed to and signed by George Slane and Dave Hanneman from Lance Fish, 3 copies of full set of plans; taken to Jason Blais
|
Telephone call | | | 7/12/2006 | | DONE |
|
|
|
Called Mike Simmonds of ZGA Architects to go over some issues still needing to be addressed. I am still reviewing the resubmittals but let them know some of the issues so they can get a head start. He stated they will get working on the issues and to let him know of any other issues as I complete the review.
|
Routing - PLAN CHECK | 5/26/2006 | | 7/12/2006 | | FAIL |
|
|
|
Called Mike Simmonds of ZGA Architects to go over some issues still needing to be addressed. I am still reviewing the resubmittals but let them know some of the issues so they can get a head start. He stated they will get working on the issues and to let him know of any other issues as I complete the review.
|
Plan resubmittals received | | | 6/29/2006 | | |
|
|
|
Received transmittal letter, letter to Jason Blais from ZGA architects, 1pg.comments from Creighton Eng. on Atrium Exhaust, 1pg. comments from Creighton Eng. on Stair Pressurization, 3 copies of 7pg. structural calculations, 3 copies of the following: G-001, G-002, A-101, A-102, A-103, A-104, A-105, A-106, A-107, A-108, A-109, A-111, A-112, A-113, A-501, M101, M102, M201, M202, M301, M302, M601, M602, M603, M701, M801, E1.0DFC, E1.0DFD, E1.0FA, E1.0FB, E1.0FC, E1.0FD, E1.0PFA, E1.0P, E1.0PFB, E1.1DFA, E1.1DFB, E1.1FA, E1.1FB, E1.2DFA, E1.2DFB, E1.2FA, E1.2FB, E1.3DFA, E1.3DFB, E1.3FA, E1.3FB, E1.4DFA, E1.4DFB, E1.4FA, E1.4FB, E1.5DFA, E1.5DFB, E1.5FA, E1.5FB, E1.6DFA, E1.6DFB, E1.6FA, E1.6FB, E1.1LA, E1.1LB, E1.2LA, E1.2LB, E1.3LA, E1.3LB; taken to Jason Blais
|
Telephone call | | | 6/16/2006 | | DONE |
|
|
|
Talked with Lance Fish of ZGA Architects. They are still putting together a resubmittal package and the entire scope of work is still being determined. Some questions concerning the stairway pressurization and if a 2-hour enclosure is required around generator will be directed to the Fire Dept.
|
1st review completed | | | 5/26/2006 | | FAIL |
|
|
|
Failed in plan check and fire.
|
Meeting | | | 5/26/2006 | | DONE |
|
|
|
Met with Scott Schoenherr and several persons on the design and construction team. Went over several issues related to the permit. It was clear that some work will be removed, some might be added, and other work needed to be clarified. New plans with changes will be forthcoming. When new plans with changes are received a full building review and fire review will then be done.
|
Plan resubmittals requested | | | 5/26/2006 | | DONE |
|
|
|
Plan resubmittals requested in a meeting with the owner and design and construction team.
|
Routing - PLAN CHECK | 5/3/2006 | | 5/26/2006 | | FAIL |
|
|
|
The scope of work on these plans is going to be changed. A meeting occurred to address the changes and new plans will need to be submitted. A full review will occur when new plans are submitted. Plans will not route to Fire until new updated plans are provided.
|
Routing - FIRE | 5/26/2006 | | 5/26/2006 | | FAIL |
|
|
|
No Fire review conducted. The scope of work is being changed and new plans will be submitted. A Fire review will occur when new plans with changes are submitted.
|
Telephone call | | | 5/23/2006 | | DONE |
|
|
|
Talked with architect representative. He stated some work noted on the plans is to be removed from the project. Issues will need to be addressed at meeting on 5/26/06.
|
Telephone call | | | 5/22/2006 | | DONE |
|
|
|
Called building owner for some clarifications. He would like to meet. Will set up meeting for Friday 5/26.
|
Routing - PUBLIC WORKS | 5/2/2006 | | 5/3/2006 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN CHECK | | | 5/2/2006 | | DONE |
|
|
|
Sheets A-105 received and routing begun.
|
Plans ACCEPTED BY PLAN CHECK | | | 4/28/2006 | | HOLD |
|
|
|
Plans missing 3rd floor remodel sheets (A-105). Called architect to have him send 3 copies over. Cannot begin routing until plan sheets are received. Plans on hold in Marlene's cubicle.
|
Plan resubmittals received | | | 4/28/2006 | | |
|
|
|
recieved 2 letters of transmittal and 6 copies of A-105, taken to Marlene S.
|
Application received | | | 4/25/2006 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/25/2006 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 4/25/2006 | | |
|
|
|
|