Permit Information
Permit NumberBLD06-01463
StatusFinaled
Name KREIZENBECK CONSTRUCTORS
Site Address 10790 W FRANKLIN RD
Project NameIDAHO POWER
Customer Number 
ePlanReviewNo
Description
(RCE-764) (IDAHO POWER - ELEVATOR ADDITION) This building is NOT fire sprinklered. To construct an interior elevator to serve the 2nd story of an existing building. The 2nd story will be expanded by about 75 square feet. Work is to include concrete footings, a concrete foundation, a masonry shaft for the elevator, a steel column, steel beams, a concrete floor, interior nonbearing walls, tunneled 1-hr corridor, relocated corridor doors, and an elevator machine room. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Letter of compliance  8/7/2007 DONE
Letter of Compliance issued 8-7-07
BLD-Final8/3/20078/6/20078/6/2007APASS
DetailsMike Jordan
mark Phone #: ###-####. Final ok.
FIRE-Final Inspection8/3/20078/3/20078/6/2007PPASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection7/23/20077/23/20077/23/2007PFAIL
DetailsTroy Cobbley
The exit signs still do not operate on battery backup.
FIRE-Final Inspection7/16/20077/17/20077/17/2007AFAIL
DetailsTroy Cobbley
Repair the existing exit signs and emergency lights
BLD-Final7/13/20077/16/20077/16/2007ANR
DetailsMike Jordan
MARK Phone #: ###-####. Needs life/safety and mech final.
Telephone call  12/12/2006 DONE
At request of Dave Hanneman, I called Gerald Weaver to inquire more about a letter which Gerald wrote to Dave dated 12/8/06, regarding an unspecified "Idaho Power Project", which indicated the existing fire alarm panel needs to be replaced and requested approval "to upgrade the entire facility peripheral devices and bring the facility up to code as it pertains to the fire alarm system prior to the end of the calendar year 2008."
I determined the project relates to this building permit. He mentioned to me that he had written an earlier letter, which I determined was a letter dated 11/17 requesting approval to connect elevator function in one building to an alarm panel in another building. I had referred that letter to Mike Timmerman to discuss with the alarm contractor. Mike had done that and had indicated the proposal would not be acceptable and suggested they consider a different design approach which would not involve a fire alarm panel replacement. Gerald indicated the contractor did not feel that suggestion was feasible and therefore Gerald had written the 12/8 letter requesting to defer any required upgrades associated with a panel replacement until the end of 2008. I explained that we would need to have a letter which referenced this building address and permit number and which indicates specifically which code requirements they have determined cannot be met with the existing system if a new alarm panel were installed, in order for us to evaluate whether those requirements could be deferred. I also indicated that the request may need to acknowledge that the agreement will be recorded and that a bond may be required in the event the specified time frames for completion are not met, but that these conditions would be determined in further consultation with our Legal department. He agreed to discuss this with their alarm contractor and provide the additional information.
BLD-Wall cover11/28/200611/28/200611/28/2006PPASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 11/28/2006 at 9:28:03 AM. Contact: ###-####. Inspected completion of 1hr wall and ceiling assemblies at corridor on 1st and 2nd floors. Reviewed UL data for fire caulking sysytem being used. Fire caulking in progress, will inspect remainder on final.
BLD-Conference11/21/200611/21/200611/21/2006PPASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 11/21/2006 at 7:57:25 AM. Contact: ###-####. received and reviewed wp file for rated const. Ok to one side 1hr ceiling assembly down stairs. Inspected 5/8 type x at 2nd floor corridor walls and cewiling assembly.
BLD-Framing/Rough-in11/20/200611/20/200611/20/2006PPART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 11/20/2006 at 9:19:53 AM. Contact: ###-####. 1hr ceiling assembly in corridors. ok to one side. Needs to provide WP for one hour assembly and UL listings for penetrations.
BLD-Other9/22/20069/25/20069/25/2006APART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 9/22/2006 at 3:02:59 PM. Contact: ###-####. Elevator shaft (masonry) 0 to 8ft elev. Will require cleanouts. Also will have special insp.
BLD-Framing/Rough-in9/21/20069/22/20069/22/2006PCANC
DetailsMike Jordan
mark Note: rebar; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. cnc by contractor.
BLD-Conference9/18/20069/18/20069/18/2006PPASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 9/18/2006 at 8:21:46 AM. Contact: ###-####.
BLD-Foundation9/8/20069/8/20069/8/2006PPART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 9/8/2006 at 8:24:40 AM. Contact: ###-####.wip at elvator pit walls.
BLD-Footing9/6/20069/7/20069/7/2006PPASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 9/6/2006 at 4:29:42 PM. Contact: ###-####. elevator pit footing.
Issue PAID IN FULL permit  7/25/2006 DONE
Telephone call  7/7/2006  
tlk to gerry weaver ###-#### that permit and fees are ready to be picked up but needs GC and RCE #
Permit Ready to Issue  7/7/2006  
Plan assigned to (CJW)5/26/2006 7/6/2006 PASS
7/6/2006 14:59:20 CJW - activity updated through activity BLDA022 from case BLD06-01463.
Routing - FIRE7/3/2006 7/6/2006 PASS
Attached review comments to plans.
Routing - PLAN CHECK7/6/2006 7/6/2006  
PLANS/APPL TAKEN TO FRONT DESK  7/6/2006 DONE
Inspection Record Card- Bld  7/6/2006 DONE
Routing - PLAN CHECK6/20/2006 7/3/2006 PASS
(6-27-06) Resubmitted drawings were reviewed. Waiting for response from the Consultant Structural Engineer.

(7-3-06) Notified that the Consultant Structural Engineer was content with the submittal. Drawings approved.
Routing Off Site - STRUCTURAL6/26/2006 7/3/2006 PASS
Called Action Courier for pick up to Stapley///6/26/06 @ 3:05pm BAS

Drawings approved on July 3, 2006. CJW
Plan resubmittals received  6/23/2006 DONE
Received transmittal letter,1,revised structural calc & 3 copys of sheets A101,A301,S101,S201,M101,M102,E101,E102,E103 taken to Carl W.
1st review completed  6/20/2006 FAIL
Failed plan Check and Fire.
Routing - FIRE6/14/2006 6/20/2006 FAIL
Faxed resubmittal item to architect. Attached revie comments to plans.
Plan resubmittals received  6/14/2006 DONE
Received 1 transmittal letter,1 copy of demoed sheets 3,2,5,6,113,-end, 3 fire alarm cable-fpl& fpld, 1 copy of sheet 1 of 1,1 con't,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,22,23,24,25,26,27,28,29,30,31,32,33,34,35,36,37,38,39,40,41,42,43,44,45,46,47,48,49,50,51,52,53,54,55,56,57,58,59,60,a0.1,a0.2,a1.1,a1.2,a2.2,a3.1,a5.1 taken to Carl W.
Routing - PLAN CHECK5/30/2006 6/14/2006 FAIL
(6-9-06) Waiting for a copy of the original building drawings. Since this building was originally constructed in the County, Boise City does not have a copy of the original drawings. Those drawings are needed to complete the plan review.

(6-14-06) Reviewed the submitted copy of the original building drawings and was able to complete the plan review for the elevator addition. Revised drawings were required. See the plan review report.
Routing Off Site - STRUCTURAL5/26/2006 6/9/2006 FAIL
Called Action Courier to pick up and take to Stapley///5/26/06 @2:23pm BAS

(6-9-06) The structural review failed. An E-mail was received with a list of items to be addressed.
Routing - PUBLIC WORKS5/26/2006 5/30/2006 PASS
Recd Pcfee & Taken To Pln CK  5/23/2006  
Plans ACCEPTED BY PLAN TECH  5/23/2006 DONE
Application received  5/22/2006