Case Summary (BLD) | | | 8/21/2012 | | DONE |
|
|
|
|
BLD-Aging Inspection | 4/20/2010 | 4/20/2010 | 4/21/2010 | | DONE |
Tony Young
|
|
|
|
DOC - Permit Finaled | 4/21/2010 | 4/21/2010 | 4/21/2010 | P | PASS |
Tony Young
|
|
|
|
BLD-Final | 7/23/2007 | 7/23/2007 | 7/23/2007 | P | PASS |
Tony Young
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
BLD-Final | 7/17/2007 | 7/18/2007 | 7/19/2007 | P | NR |
Tony Young
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
FIRE-Final Inspection | 7/17/2007 | 7/18/2007 | 7/18/2007 | A | PASS |
Troy Cobbley
|
|
|
LIfe safety passed
|
BLD-Final | 6/28/2007 | 6/28/2007 | 6/28/2007 | P | PASS |
Tony Young
|
|
|
mike Phone #: ###-#### see fire inspection notes,, same
|
FIRE-Final Inspection | 6/26/2007 | 6/26/2007 | 6/26/2007 | P | PART |
Forrest France
|
|
|
Inspection for units 208, 209, 210, 211 on the west end of the building completed satisfactory, plastic cover and battery lid replaced on two SD while on site, noted the basement level storage areas will require smoke detectors and at least one fire extinguisher- see plan review notes and annotations, the remaining 8 units in this building are not yet completed for final.
|
BLD-Framing/Rough-in | 4/26/2007 | 4/27/2007 | 4/27/2007 | A | PASS |
Tony Young
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith basement ok
|
BLD-Other | 4/25/2007 | 4/25/2007 | 4/25/2007 | P | PART |
Tony Young
|
|
|
mike caulk and seal; Phone #: ###-#### Internet Inspection Request from: Victoria Beall basement ok to insulate,, will need fire dampers in ducts
|
BLD-Energy code compliance | 4/19/2007 | 4/19/2007 | 4/19/2007 | P | PASS |
Tony Young
|
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
|
CHANGE STATUS TO (ISS) | | | 4/16/2007 | | DONE |
|
|
|
|
(F) Reprint permit | | | 4/16/2007 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 4/12/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
Tony Young
|
|
|
Mike ###-#### for 212? -215
|
Plan assigned to (M_P) | 12/12/2006 | 12/12/2006 | 4/12/2007 | | PASS |
|
|
|
4/12/2007 09:22:03 M_P - activity updated through activity BLDA022 from case BLD06-01651.
|
Routing - PLAN CHECK | 3/7/2007 | | 4/12/2007 | | PASS |
|
|
|
PLAN MODIFICATION *
|
Override - Parcel Holds | | | 4/12/2007 | | |
|
|
|
|
Permit Ready to Issue | | | 4/12/2007 | | DONE |
|
|
|
|
Telephone call | | | 4/12/2007 | | DONE |
|
|
|
called ###-#### and told Ryan McCaene that permit is ready and fees due
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/12/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 4/12/2007 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 4/12/2007 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 4/12/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 4/12/2007 | | |
|
|
|
|
Inspection Record Card- Bld | | | 4/12/2007 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 4/12/2007 | | |
|
|
|
|
Routing - PLANNING Land Div | 4/11/2007 | | 4/11/2007 | | PASS |
|
|
|
Revised condominium drawings submitted that match the architectural drawings.
|
BLD-Energy code compliance | 3/27/2007 | 3/28/2007 | 3/28/2007 | A | PART |
Tony Young
|
|
|
This inspection is not for the plan mod part - Mike ###-#### quad 212-215 ok to cover
|
Override - Parcel Holds | | | 3/27/2007 | | |
|
|
|
|
BLD-Framing/Rough-in | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | PART |
Tony Young
|
|
|
###-#### mikeok pending mech rough to insulate,, 212-215
|
Override - Parcel Holds | | | 3/23/2007 | | |
|
|
|
|
BLD-Energy code compliance | 3/12/2007 | 3/13/2007 | 3/13/2007 | A | PASS |
Mike Jordan
|
|
|
inspection for basement ###-#### Mike
|
Override - Parcel Holds | | | 3/12/2007 | | |
|
|
|
|
BLD-Framing/Rough-in | 3/8/2007 | 3/8/2007 | 3/8/2007 | P | PART |
Tony Young
|
|
|
###-#### - mike 208-211 ok to insulate
|
Override - Parcel Holds | | | 3/8/2007 | | |
|
|
|
not modification
|
Routing - PLAN CHECK | 3/2/2007 | | 3/7/2007 | | PEND |
|
|
|
PLAN MODIFICATION Waiting for others to approve prior to issuing permit.
|
Routing - FIRE | 2/26/2007 | | 3/2/2007 | | PASS |
|
|
|
PLAN MODIFICATION - Attached updated review comments to plans.
|
Plan resubmittals received | | | 2/28/2007 | | |
|
|
|
Received cover transmittal letter and 3 copies of sheets a0.11, a2.12, a2.13, a2.14 and taken to Mike Phillips
|
Routing - PLAN CHECK | 1/16/2007 | | 2/26/2007 | | FAIL |
|
|
|
PLAN MODIFICATION * Plan review complete, called architect and requested additional information to be submitted to reflect extension onb hand rails and rise and run to meet code.
|
Case Summary (BLD) | | | 2/26/2007 | | |
|
|
|
|
Routing - PLANNING Land Div | 1/8/2007 | | 1/16/2007 | | FAIL |
|
|
|
Prior to issuance of building permit, revised condominium drawings are required that match the architectural drawings. Called Tim Fox on January 16, 2007 and he has not completed these drawings for Building #6.
|
Routing - PLAN CHECK | 12/22/2006 | | 1/8/2007 | | |
|
|
|
PLAN MODIFICATION Routing to Land Division.
|
Plan resubmittals received | | | 1/2/2007 | | |
|
|
|
Received 1pg. response letter and 3 copies of the following pages: a2.11, a2.12, a4.10, a4.11, a7.12; taken to Mike Phillips
|
Routing - PLANNING | 12/21/2006 | | 12/22/2006 | | PASS |
|
|
|
CUP03-00114-Cody R-With the exception of the sidewalk to the existing parking lot; planning approval is for interior work only; no increase in residential units approved or allowed.
|
Routing - PUBLIC WORKS | 12/21/2006 | | 12/21/2006 | | PASS |
|
|
|
PLAN MODIFICATION
|
Routing - PLANNING Land Div | 12/19/2006 | | 12/20/2006 | | FAIL |
|
|
|
Prior to issuance of building permit, revised condominium drawings are required that match architectural drawings.
|
Plan Modification Accepted | | | 12/12/2006 | | |
|
|
|
Plan modification accepted for Bld06-01651 (bldg. 6) to add the following spaces to existing basement: (3) non-habitable dwelling unit basement spaces, mechanical space and bicycle lock-up space. Each dwelling unit basement space will be supplied w/(1) window & an egress window well. The concrete walk on the west end of the building will be extended to the bicycle lock-up space. Three sets of plans submitted on sheets a0.11, a0.21, a2.11, a2.12, a2.13, a2.14, a4.10, a4.11, a7.11, a7.12, and structural design calculations; routed to Mike Phillips
|
BLD-Aging Inspection | 11/9/2006 | 11/9/2006 | 11/9/2006 | | PASS |
Tony Young
|
|
|
|
Override - Parcel Holds | | | 8/10/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/10/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 7/28/2006 | | |
|
|
|
|
Inspection Record Card- Bld | | | 7/28/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/28/2006 | | DONE |
|
|
|
tlk to ryan mccaene ###-#### that permit and fees are ready to be picked up but needs GC and RCE #
|
Override - Parcel Holds | | | 7/28/2006 | | |
|
|
|
|
Permit Ready to Issue | | | 7/28/2006 | | DONE |
|
|
|
|
Plan assigned to (M_P) | 6/9/2006 | | 7/27/2006 | | PASS |
|
|
|
7/27/2006 14:37:11 M_P - activity updated through activity BLDA022 from case BLD06-01651.
|
Routing - FIRE | 7/25/2006 | | 7/27/2006 | | PASS |
|
|
|
Attached review comments to plans.
|
1st review completed | | | 7/27/2006 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 7/27/2006 | | 7/27/2006 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/27/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 7/27/2006 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 7/27/2006 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 6/13/2006 | | 7/25/2006 | | PEND |
|
|
|
Waiting for others to approve prior to issuing permit.
|
Routing - PUBLIC WORKS | 6/9/2006 | | 6/13/2006 | | PASS |
|
|
|
|
Application received | | | 6/7/2006 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/7/2006 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/7/2006 | | |
|
|
|
|