Case Summary (BLD) | | | 11/24/2014 | | DONE |
|
|
|
|
Third Notice BLD | 7/18/2007 | 7/18/2007 | 7/26/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 6/21/2007 | 6/21/2007 | 7/18/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 5/24/2007 | 6/21/2007 | | DONE |
|
|
|
|
Permanent occupancy | | | 5/24/2007 | | DONE |
|
|
|
Perm. Occ. Cert. # 11632 issued 5-24-07 to T-Mobile Communications.
|
BLD-Final | 5/22/2007 | 5/22/2007 | 5/22/2007 | P | PASS |
Mike Jordan
|
|
|
rich; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Ok for perm occ. All issues resolved.
|
Permanent Occupancy | | 5/22/2007 | 5/22/2007 | | DONE |
|
|
|
|
FIRE-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
Temporary occupancy | | | 3/26/2007 | | DONE |
|
|
|
Temp. Occ. Cert. # 5559 issued 3-26-07 to T-Mobile Communications.
|
BLD-Final | 3/22/2007 | 3/23/2007 | 3/23/2007 | P | PART |
Mike Jordan
|
|
|
rich ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Temp. occ. granted. Needs to post HC signs and finish installing grab bars in restrooms. Replace door hardware on janitors closet to lever type. All ceiling grid issues have been resolved and is ok to cover.
|
FIRE-Final Inspection | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with dave hannimans permission until items as noted by mike timmermans inspection have been corrected for the fire alarm and suppression permits. Also the battery containment issues needs addressed.
|
BLD-Other | 3/21/2007 | 3/21/2007 | 3/21/2007 | P | FAIL |
Mike Jordan
|
|
|
Rich Ceiling ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus. Tile already in place. Noted upon further insp. that additional wires needed for diffusers, etc... Also needs rto remove wall angle used to attach runners and used approved connectors.
|
Code Occupancy Approval | 3/19/2007 | 3/19/2007 | 3/20/2007 | P | PASS |
Carol Montgomery
|
|
|
Meets compliance (insp. on 3-19-2007)
|
Code Occupancy Approval | 3/14/2007 | 3/16/2007 | 3/19/2007 | A | CANC |
Carol Montgomery
|
|
|
Rich called at approx. 4:00pm- NR
|
Code Occupancy Approval | 3/13/2007 | 3/13/2007 | 3/14/2007 | P | CANC |
Carol Montgomery
|
|
|
Called Rich. They have landscape in and fence posts up. Fence is not completed - so, they are not ready for inspection - schedule inspection for Friday (3-16-2007)
|
FIRE-Final Inspection | 2/22/2007 | 2/22/2007 | 2/22/2007 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was not for a final but for a cover inspection on part of the sprinkler piping. The sprinkler piping in the areas outside of the pre-action system areas are ok to cover.
|
BLD-Framing/Rough-in | 2/9/2007 | 2/9/2007 | 2/9/2007 | P | PASS |
Mike Jordan
|
|
|
rich; Phone #: ###-#### Internet Inspection Request from: Victoria Beall. On site to inspect truss penetration repair at 1hr fire barrier wall around battery room. All modifications were done in accordance with plans approved by G. Slane
|
Plan resubmittals received | | | 1/25/2007 | | |
|
|
|
Received 4 copies of page T2; given to Carl Westfall and George Slane.
|
Plan resubmittals received | | | 12/15/2006 | | |
|
|
|
received form from conger saucerman general cont (2) pages & "4" sheets of T2- plans taken to carl westfall
|
Plan Reviewer's activity | | | 12/15/2006 | | DONE |
|
|
|
Sent resubmitted drawings to George Slane, Building Official.
|
BLD-Framing/Rough-in | 11/27/2006 | 11/28/2006 | 11/28/2006 | A | FAIL |
Mike Jordan
|
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Wood truss and wood beam penetrations not allowed at 1hr fire barrier wall. Architect to provide UL approved listed assembly for wood truss and wood beam penetrations or provide detail to plan review for approval for aequate protection.
|
Print Occupancy Form | | | 11/6/2006 | | DONE |
|
|
|
|
Telephone call | | | 11/6/2006 | | DONE |
|
|
|
tlk to david sarver ###-#### that permit and fees are ready to be picked up but needs GC/RCE and RP
|
Permit Ready to Issue | | | 11/6/2006 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 11/6/2006 | | |
|
|
|
|
Plan resubmittals received | | | 11/3/2006 | | |
|
|
|
Received 1 cover letter, 2 copies of sheets T1, E1, E3 and taken to Carl Westfall
|
Routing - PLAN CHECK | 10/17/2006 | | 11/2/2006 | | PASS |
|
|
|
Drawings approved after resubmittal review.
|
Routing - PLANNING | 11/2/2006 | | 11/2/2006 | | PASS |
|
|
|
Approved per DRH06-00365
|
Routing - PLAN CHECK | 11/2/2006 | | 11/2/2006 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2006 | | DONE |
|
|
|
|
Plan assigned to (CJW) | 9/22/2006 | | 11/2/2006 | | PASS |
|
|
|
11/2/2006 16:22:15 CJW - activity updated through activity BLDA022 from case BLD06-02615.
|
Plan resubmittals received | | | 10/30/2006 | | DONE |
|
|
|
Received letter of transmittal,1 letter, 1 review, & 2 copys of sheets T1,A1,A3,A4,A6,E4,E5 taken to Carl W.
|
Routing - FIRE | 10/16/2006 | | 10/17/2006 | | PASS |
|
|
|
Attached review comments to plans.
|
1st review completed | | | 10/17/2006 | | FAIL |
|
|
|
Failed planning and plan check.
|
Routing - PLAN CHECK | 9/26/2006 | | 10/16/2006 | | FAIL |
|
|
|
The IBC plan review was started on October 13. 2006 and was finished on October 16, 2006. Revised drawings were required. See the plan review report.
|
Plan resubmittals received | | | 10/4/2006 | | |
|
|
|
Received 2 copies of sheets A0 from Planning & Zoning (Greg Johnson) and taken to Carl Westfall
|
Routing - Erosion and Sediment | 9/25/2006 | | 9/26/2006 | | PASS |
|
|
|
ESC plan waiver approved with attached conditions.
|
Routing - PLANNING | 9/26/2006 | | 9/26/2006 | | FAIL |
|
|
|
A revised site plan showing that conditions have been met must be submitted to Design Review. The revised site plan must also be included with building permit plans.
|
Routing - PUBLIC WORKS | 9/22/2006 | | 9/25/2006 | | PASS |
|
|
|
|
Application received | | | 9/12/2006 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/12/2006 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/12/2006 | | DONE |
|
|
|
Spoke with David Sarver and told him that the Lighting compliance may need corrected E-4, T-1 codes used for design Plumbing is blank, and fire code 2000///9/12/06 @ 9:00am BAS
|