Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberBLD06-02622
StatusFinaled
Name ABERCROMBIE
Site Address 350 N MILWAUKEE ST Unit: 2147
Project NameBTS - #2147
Customer Number 
ePlanReviewNo
Description
CANYON CONTRACTING CORP RCT-18757 (ABERCROMBIE - BOISE TOWNE SQUARE - SPACE 2147) To remodel an existing 4,396 sq.ft. retail tenant on the 2nd level per approved plans. Work to include, construction of interior noncombustible partitions, construction of two new accessible restrooms, nonrated exit access corridor, storage room, retail space, fitting rooms, installation of new storefront framing, installation of new ceiling and realted lighting, installation of new HVAC system, smoke evacuation system was installed under prior permit by landlord, miscellaneous related interior finishes. This building is fully fire sprinklered any alterations to the fire sprinkler system shall be per NFPA #13 as regulated by the fire department. The smoke control system shall remain operational as originally installed under the 1985 UBC. Rmh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD3/21/20073/21/20073/23/2007 DONE
Second Notice has not been responded to.
Second Notice BLD3/8/20073/8/20073/21/2007 DONE
First Notice has not been responded to.
First Notice 2/9/20073/8/2007 DONE
BLD-Final2/8/20072/9/20072/9/2007PPASS
DetailsDave Hannah
Frank Please call first ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for perm occ
FIRE-Final Inspection2/8/20072/9/20072/9/2007APASS
DetailsTroy Cobbley
Life safety finaled
Permanent Occupancy 2/9/20072/9/2007 DONE
Details
Permanent occupancy  2/9/2007 DONE
Perm. Occ. Cert. # 11433 issued 2-9-07 to Abercrombie at Boise Towne Square.
FIRE-Final Inspection2/8/20072/8/20072/8/2007PFAIL
DetailsTroy Cobbley
need to repair the exit sign from retail into the rear corridor and get the new duct smoke detector to operate. The smoke evac system operated correctly.
BLD-Other1/24/20071/25/20071/25/2007APASS
DetailsMike Jordan
ceiling grid ok.
BLD-Other1/24/20071/24/20071/24/2007PCANC
DetailsTom Arcoraci
frank; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
BLD-Other1/18/20071/18/20071/18/2007PFAIL
DetailsMike Jordan
frank - abercrombe drop ceiling; Phone #: ###-#### Internet Inspection Request from: Victoria Beall. Wires exceed the 1:6 requirement.
BLD-Other1/2/20071/3/20071/3/2007APART
DetailsMike Jordan
partial ceiling inspection///Frank ###-####. Grid for hardlid. Back hallway only.
Override - Parcel Holds  1/2/2007  
BLD-Framing/Rough-in12/22/200612/26/200612/26/2006APART
DetailsJim Sly
###-#### frank
Support for hard lid ceiling OK OK to cover ceiling.
Override - Parcel Holds  12/22/2006  
Scheduled a ceiling inspection
Override - Parcel Holds  12/22/2006  
Scheduled a ceiling inspection
BLD-Framing/Rough-in12/7/200612/8/200612/8/2006APASS
DetailsMike Jordan
frank ###-#### Store front and south interior walls.
BLD-Framing/Rough-in11/28/200611/29/200611/29/2006APART
DetailsMike Jordan
frank - space 2147 ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. NOnload bearing inteerior framed walls.
BLD-Framing/Rough-in11/16/200611/17/200611/17/2006PPASS
DetailsMike Jordan
frank - note: fire wall - space 2147; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
BLD-Other11/15/200611/16/200611/16/2006APART
DetailsMike Jordan
frank Note: screw ins for 1 hr wall; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Screw pattern ok. Needs to provide UL listings and specs for fire caulking at penetrations.
Issue PAID IN FULL permit  11/15/2006 DONE
Plan assigned to (R_H)9/25/2006 11/14/2006 PASS
11/14/2006 06:33:17 RMH - activity updated through activity BLDA022 from case BLD06-02622.
Routing - PLAN CHECK11/13/2006 11/14/2006 PASS
PLANS/APPL TAKEN TO FRONT DESK  11/14/2006 DONE
Print Occupancy Form  11/14/2006 DONE
Telephone call  11/14/2006 DONE
tlk to stacey simpson ###-#### ext 236 that permit and fees are ready to be picked up but needs GC/RCE #
Permit Ready to Issue  11/14/2006 DONE
1st review completed  11/13/2006 PASS
Routing - FIRE11/8/2006 11/13/2006 PASS
Attached review comments to plans.
Routing - PLAN CHECK9/26/2006 11/8/2006 PEND
No corrections required by building department review. Routed plans to fire for review on 11/08/06
Case Summary (BLD)  11/8/2006 DONE
Routing - PUBLIC WORKS9/25/2006 9/26/2006 PASS
Application received  9/12/2006  
Plans ACCEPTED BY PLAN TECH  9/12/2006  
Recd Pcfee & Taken To Pln CK  9/12/2006 DONE