Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD06-02914
StatusFinaled
Name SAWTOOTH INVESTMENT LLC
Site Address 1199 W SHORELINE LN
Project NameRIVER PARK BLDG
Customer Number 
ePlanReviewNo
Description
(RCE-3673) (RIVER PARK BLDG - UPGRADE) To install 60 minute rated/450 degree temperature rated doors in the west end one-hour rated stair enclosure per an expired Upgrade Agreement on file for this building per approved plans. The doors will be installed at the access into the west stair enclosure on all floors and at the small closets within the west stair enclosure on all floors per previous Alternate Approval/Upgrade Agreement. These types of doors are to also be installed at the elevator openings on hold-open on all floors at the east end alternate approved stair on a FUTURE separate permit. This is a Scope of Work Permit. A Letter of Completion is to be issued when done. NOTE: This building is fully fire sprinklered for one-hour substitution. JCB
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  11/2/2007 DONE
customer called and asked for a copy of the permit
Third Notice BLD3/21/20073/21/20077/20/2007 DONE
Second Notice has not been responded to.
Telephone call  5/1/2007 DONE
left msg on voice mail for project manager to call re fv
Second Notice BLD3/8/20073/8/20073/21/2007 DONE
First Notice has not been responded to.
Letter of compliance  3/14/2007 DONE
Letter of Compliance issued 3-14-07
First Notice2/23/20072/23/20073/8/2007 DONE
DetailsDave Hannah
BLD-Final2/22/20072/23/20072/23/2007PPASS
DetailsDave Hannah
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
DOC - Permit Finaled2/23/20072/23/20072/23/2007PPASS
DetailsDave Hannah
ok for cert of comp
Telephone call  1/26/2007 DONE
Returned phone call of "Doc" Schleckeway concerning temperature rating for doors into stair enclosure. The upgrade agreement to bring the stair enclosures into code compliance was based on the UBC. Exception to this requirement for temperature transfer rating, 450 dgrees, under the IBC would require compliance of the building sprinkler system with the IBC. This would be quick-response heads for this light hazard occupancy. It is not known if this is the type of system originally installed and would have to be evaluated and upgraded if necessary to use sprinkler exceptions of IBC.
BLD-Other1/10/20071/11/20071/11/2007AFAIL
DetailsDave Hannah
mike - need structural inspection per Forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall need data on doors marked type B 1 1/2 hr cant tell if they are 450 temp
FIRE-Final Inspection1/9/20071/10/20071/10/2007APASS
DetailsForrest France
Life safety field inspection for the scope of work passed.
Issue PAID IN FULL permit  11/20/2006 DONE
Inspection Record Card- Bld  10/12/2006 DONE
Telephone call  10/12/2006 DONE
Left voice message for Bruce that permit is ready, Fees & GC info @ 10:44am on 10/12/06 BAS
Permit Ready to Issue  10/12/2006 DONE
Plan assigned to (JCB)10/10/2006 10/11/2006 PASS
10/11/2006 15:04:46 JCB - activity updated through activity BLDA022 from case BLD06-02914.
Routing - PLAN CHECK10/10/2006 10/11/2006 PASS
Permit and plans approved and taken to front desk.
PLANS/APPL TAKEN TO FRONT DESK  10/11/2006 PASS
Routing - FIRE10/11/2006 10/11/2006 DONE
Field verify IFC requirements.
1st review completed  10/11/2006 PASS
DetailsJason Blais
Telephone call  10/10/2006 DONE
Called Bruce Poe concerning the little closets within the west end stair enclosure. As part of the past approval these closet doors were to also have 60 minute rated/450 degree temperature rated doors. Bruce remembered this and agreed and then asked if I would red-line them on the plans.
Pending Assignment by MYS10/9/2006 10/10/2006 DONE
10/10/2006 09:31:32 MYS - activity updated through activity BLDA184 from case BLD06-02914.
Plans ACCEPTED BY PLAN TECH  10/10/2006  
Application received  10/9/2006  
Recd Pcfee & Taken To Pln CK  10/9/2006 DONE