Permit Information
Permit NumberBLD06-03461
StatusFinaled
Name DON BUCKMASTER CONSTRUCTION
Site Address 1053 W AMITY RD
Project NameMCGUIRE BEARING
Customer Number 
ePlanReviewNo
Description
**(McQuire Bearing Company)** (Don Buckmaster RCE-2351) To remodel an existing 9,678 sq ft building used as a bearing factory by expanding into the adjacent machinery tenant space and create one 26,232 sq ft tenant space per approved plans. Work to include, remodel existing restroom to make one fully accessible unisex restroom, install new opening in CMU wall between the two space per attached engineering, relocate an existing spray booth and install new opening into room, anchor existing 10 foot high storage racking per engineering, This building is fully fire sprinkled any alterations or modifications to the sprinkler system WILL REQUIRE separate permit and shall be installed and maintained per NFPA #13 as regulated by the fire department. RMH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD7/18/20077/18/200710/29/2007 DONE
Second Notice has not been responded to.
Second Notice BLD7/5/20077/5/20077/18/2007 DONE
First Notice has not been responded to.
First Notice 6/21/20077/5/2007 DONE
BLD-Final6/7/20076/8/20076/12/2007PPASS
DetailsJim Storey
don; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
Permanent Occupancy 6/11/20076/11/2007 DONE
Details
Permanent occupancy UNPAID FEE  6/11/2007 DONE
Perm. Occ. Cert. # 11655 issued 6-11-07 to the McGuire Bearing Company.
FIRE-Final Inspection6/7/20076/7/20076/7/2007PPASS
DetailsForrest France
Correction notice items are complete, fire life safety inspection passed.
FIRE-Final Inspection6/6/20076/7/20076/7/2007AFAIL
DetailsForrest France
Wrong permit number called in for inspection, was intended for an FIR #.
BLD-Final3/19/20073/20/20073/20/2007PCANC
DetailsJim Storey
don; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
FIRE-Final Inspection3/19/20073/20/20073/20/2007AFAIL
DetailsForrest France
Need to provide a current annual inspection for the existing fire sprinkler system, provide protection for the spray booth per review notes, missing one PFE for the office area, provide approved door hardware at one restroom in the office, repair exit discharge light at one location, provide combo exit sign and emergency light at the SW warehouse exit door, remove door knob at passage door to one marked exit, blank wires and provide a cover for one open junction box as marked on plans.
BLD-Framing/Rough-in1/16/20071/17/20071/17/2007PPASS
DetailsJim Storey
don; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
Plan assigned to (R_H)12/11/200612/11/20061/10/2007 PASS
1/10/2007 09:32:44 RMH - activity updated through activity BLDA022 from case BLD06-03461.
Routing - PLAN CHECK12/15/2006 1/10/2007 PASS
Routing - PLAN CHECK12/20/2006 1/10/2007 PASS
Case Summary (BLD)  1/10/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  1/10/2007 DONE
Print Occupancy Form  1/10/2007 DONE
Issue PAID IN FULL permit  1/10/2007  
Plan resubmittals received  1/9/2007  
received "2" sets of plans with each sheet of A2.2, MO.O, MO.1, H1.O---plans taken to Ron Hill
Plan Reviewer's activity  12/20/2006 DONE
Visited site to confirm fire hydrant availability. Faxed updated review comments to architect.
Routing - FIRE12/20/2006 12/20/2006 PASS
Faxed updated review comments to architect. Attached updated review comments to plans.
Routing - FIRE12/12/2006 12/15/2006 FAIL
Faxed resubmittal items to architect. Attached review comments to plans.
1st review completed  12/15/2006 FAIL
Case Summary (BLD)  12/12/2006 DONE
Routing - PLAN CHECK12/8/2006 12/12/2006 FAIL
Faxed and mailed requirements to architect, on 12/12/06, routed plans to fire same day.
Plans ACCEPTED BY PLAN TECH  12/11/2006  
Recd Pcfee & Taken To Pln CK  12/11/2006  
Application received  12/8/2006