BLD-Conference | 10/14/2009 | 10/14/2009 | 10/14/2009 | P | DONE |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 10/14/2009 | 10/14/2009 | 10/14/2009 | P | PASS |
Mike Jordan
|
|
|
No inspections were called in and cold not get anyone to return my phone calls. Permit is expired.
|
BLD-Conference | 6/24/2008 | 6/24/2008 | 6/25/2008 | P | PASS |
Mike Jordan
|
|
|
called and left message with Blaine at Idaho material handling. No call back.
|
BLD-Aging Inspection | 8/27/2007 | 8/27/2007 | 8/27/2007 | | NR |
Mike Jordan
|
|
|
|
Issue PAID IN FULL permit | | | 5/18/2007 | | DONE |
|
|
|
|
Telephone call | | | 5/16/2007 | | DONE |
|
|
|
called idaho material handling at ###-#### & will call me back
|
Routing - FIRE | 3/21/2007 | | 3/26/2007 | | PASS |
|
|
|
Attached IFC review comments to plans.
|
Plan assigned to (DRS) | 3/13/2007 | | 3/26/2007 | | PASS |
|
|
|
3/26/2007 11:50:22 DRS - activity updated through activity BLDA022 from case BLD07-00515.
|
1st review completed | | | 3/26/2007 | | FAIL |
|
|
|
Failed plan check.
|
Routing - PLAN CHECK | 3/26/2007 | | 3/26/2007 | | PASS |
|
|
|
Approved as noted on plans and attached plan review conditions.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/26/2007 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 3/26/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (RDY) | | | 3/26/2007 | | DONE |
|
|
|
|
Telephone call | | | 3/26/2007 | | DONE |
|
|
|
Called Blane permit ready and fee given ///dld
|
Routing - PLAN CHECK | 3/13/2007 | | 3/21/2007 | | FAIL |
|
|
|
Waiting for letter from engineer concerning concrete anchor, ESR 1917. Routing to fire code analyst for review.
|
Telephone call | | | 3/21/2007 | | DONE |
|
|
|
Phone call to Ben Riehl concerning the Hilti anchor assembly specified on plans. The ESR report indicates the anchor is approved for use in masonry but not concrete. We discussed ESR 1917, Hilti KB-TZ which is approved for concrete and does require special inspection. Ben is sending letter indicating change to plans and I will red-line plans and attach copy of his letter.
|
Plan resubmittals received | | | 3/21/2007 | | DONE |
|
|
|
Received letter from Ben Reihl concerning compliance with 2003 IBC for concrete anchors approved for such use as being ESR 1915, Hilti KB-TZ. The system originally listed, KB-III is listed for use in masonry only per report ESR 1385. I have red-lined plans to reference the Hilti KB-TZ, ESR 1917 as the applicable report and the need for special inspection per the report in accordancewith Sec. 1704 IBC.
|
Pending Assignment by MYS | 3/1/2007 | | 3/13/2007 | | DONE |
|
|
|
3/13/2007 11:39:13 MYS - activity updated through activity BLDA168 from case BLD07-00515.
|
Recd Pcfee & Taken To Pln CK | | | 3/1/2007 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/1/2007 | | |
|
|
|
|
Application received | | | 3/1/2007 | | |
|
|
|
|