Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD07-00665
StatusFinaled
Name LARRY SUNDELL
Site Address 1731 S ENTERTAINMENT AVE
Project NameMOSHI MOSHI
Customer Number 
ePlanReviewNo
Description
(MOSHI MOSHI RESTAURANT) Note: The building is fully sprinklered. To remodel an existing 6,726 sq.ft. restaurant (formerly Black Angus) for a new restaurant (Moshi Moshi) tenant per approved plans. Work includes selective demolition of non-bearing divider partitions; to construct new dividers, install four (4) booth seating units; two 16 seat Tepan-Yaki cooking/dining areas; a floor area of 440 sq. ft. for three accessible private Tatami Dining areas; open dining areas, two Type I Hoods with listed 1-hour rated Firemaster grease duct enclosure wrap, per ESR 2213 (attached) or equal; new interior decorative features and interior finishes. Existing HVAC & interior lighting to remain as-is per note from architect. An accessible route is required to be maintained to all areas of the building and accessible seating in the four different dining area noted above. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD10/30/200710/30/200712/27/2007 DONE
Second Notice has not been responded to.
Second Notice BLD10/1/200710/1/200710/30/2007 DONE
First Notice has not been responded to.
First Notice 9/10/200710/1/2007 DONE
Permanent Occupancy  9/10/2007 DONE
Case Summary (BLD)  7/10/2007  
BLD-Final6/28/20076/29/20076/29/2007APASS
DetailsMike Jordan
ok for perm occ.
Temporary occupancy  6/29/2007 DONE
Temp. Occ. Cert. # 5611 issued 6-29-07 to Moshi Moshi.
FIRE-Final Inspection6/27/20076/28/20076/28/2007PPASS
DetailsTroy Cobbley
life safety passed
Extend Permit 180 days6/28/20076/29/20076/28/2007ACANC
DetailsMike Jordan
BLD-Final6/28/20076/28/20076/28/2007PCANC
DetailsMike Jordan
BLD-Final6/27/20076/29/20076/28/2007ACANC
DetailsMike Jordan
mor Phone #: ###-####
BLD-Final6/25/20076/26/20076/26/2007PNR
DetailsJim Sly
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
Need Fire final.
FIRE-Final Inspection6/22/20076/25/20076/25/2007AFAIL
DetailsForrest France
Need to repair one emergency light at the main lobby, remove manual thumbturn at the office door, post the provided 2A10BC fire extinguisher on the wall as discussed, need to final the project related fire alarm permit prior to life safety final, noted slider doors at three private dining rooms may not meet hardware accessibility requirements as installed.
BLD-Final6/22/20076/25/20076/25/2007PNR
DetailsJim Sly
mor Phone #: ###-####
Need Fire final approval.
BLD-Foundation6/5/20076/5/20076/5/2007PDONE
DetailsMike Jordan
mor; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang. CONFERANCE
FIRE-Final Inspection5/16/20075/17/20075/17/2007AFAIL
DetailsTroy Cobbley
This project was not ready for inspection but I went over some of the required items with the owner. Fire sprinkler heads are overspaced. Fire extinguishers need to be installed. There are no appliances under the kitchen hood yet so the suppression system needs recertified and tested. Door hardware is not installed. Exit signs and emergency lights will need to be tested.
Telephone call  5/15/2007  
called ###-#### and spoke with Mor, told him I spoke with Dan Stuart and they do need CDHD to sign off on occupancy card before can obtain occupancy. At the time permit was issued, CDHD was not checked yes in the signatures. I told him to just write in an extra line on the card and have CDHD inspector sign off.
BLD-Framing/Rough-in5/11/20075/14/20075/14/2007APASS
DetailsMike Jordan
Mor ###-####. Framing for tatami rooms, and fountain bases. Also verified with contractor that one leaf of sliding doors must provide 32" clear width. Also went over ada requirements with owners.
Routing - PLAN CHECK4/30/2007 5/3/2007 PEND
Plan resubmittals of 5/2/07 inserted into original plan sheets. Items not correct were red-lined on plans and next to architects cover letter response and the plan review modified to reflect requirements. Copy of modified plan review faxed to Larry Sundell as notice of items remaining to be verified as correct in the field.Routing to fire code analyst for re-review.
Plan assigned to (DRS)4/18/2007 5/3/2007 PASS
5/3/2007 11:51:14 DRS - activity updated through activity BLDA022 from case BLD07-00665.
Routing - FIRE5/3/2007 5/3/2007 PASS
Attached updated review comments to plans.
Routing - PLAN CHECK5/3/2007 5/3/2007 PASS
Approved based on red-line notes on plans and all attached plan review commnets from all reviewing agencies. routing to permit desk to issue.
PLANS/APPL TAKEN TO FRONT DESK  5/3/2007 PASS
Print Occupancy Form  5/3/2007 DONE
Print Occupancy Form  5/3/2007 DONE
Telephone call  5/3/2007 DONE
t/c w larry sundell at ###-#### - permit ready and fees given - also need gc name and rce#
Permit Ready to Issue  5/3/2007 DONE
Issue PAID IN FULL permit  5/3/2007 DONE
Plan resubmittals received  5/2/2007  
Received 1 response letter from Larry Sundell, 2 copies of the following sheets-One, Two, Three, M-1 and taken to Dan Stuart
Routing - FIRE4/27/2007 4/30/2007 FAIL
Emailed resubmittal items to architect. Attempted to fax, although transmission was unsuccessful. Attached review comments to plans.
1st review completed  4/30/2007 FAIL
Plan resubmittals requested  4/27/2007 DONE
Fax to Larry Sundell of plan review items needing addressed or corrected on plans.
Routing - PLAN CHECK4/2/2007 4/27/2007 FAIL
Resubmittals required. Corrections faxed to Larry Sundell. Routing plans to fire code analyst.
Plan assigned to (CJW)3/28/2007 4/18/2007 DEFR
Reassigned to Dan Stuart by MSouthard.
Routing - PLUMBING3/29/2007 4/2/2007 PASS
per plans and 2003 upc
Routing - PLANNING3/29/2007 3/29/2007 PASS
Sarah Schafer Approved applicant is only requesting 189 parking spaces. When location was the Black Angus it was approved for 237 parking spaces.
Routing - PUBLIC WORKS3/28/2007 3/29/2007 PASS
Pending Assignment by MYS3/16/2007 3/28/2007 DONE
3/28/2007 12:05:49 MYS - activity updated through activity BLDA172 from case BLD07-00665.
Plans ACCEPTED BY PLAN TECH  3/16/2007  
Recd Pcfee & Taken To Pln CK  3/16/2007 DONE
Application received  3/16/2007