Third Notice BLD | 3/5/2008 | 3/5/2008 | 3/31/2008 | | DONE |
Cathy Brown
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 1/9/2008 | 1/9/2008 | 3/5/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 11/16/2007 | 1/9/2008 | | DONE |
|
|
|
|
BLD-Final | 11/15/2007 | 11/16/2007 | 11/16/2007 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/15/2007 at 8:05:12 AM. Contact: ###-####.
|
Permanent Occupancy UNPAID FEE | | | 11/16/2007 | | DONE |
|
|
|
|
Temporary Occupancy | 11/13/2007 | 2/11/2008 | 11/13/2007 | | DONE |
|
|
|
|
BLD-Final | 11/7/2007 | 11/9/2007 | 11/9/2007 | A | PART |
Jim Storey
|
|
|
howard Phone #: ###-#### need ada 7-9 tolitet papper/ saftey glazing doors.
|
Code Occupancy Approval | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | PASS |
Scott M.Brown
|
|
|
OK FOR FINAL
|
Code Occupancy Approval | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | CANC |
Scott M.Brown
|
|
|
OK FOR FINAL
|
PubWorks Occupancy Approval | 11/8/2007 | 11/8/2007 | 11/8/2007 | | DONE |
|
|
|
Recieved letter from engineer stating project was built as per plans. Final inspection D. Erskine.
|
FIRE-Final Inspection | 11/5/2007 | 11/7/2007 | 11/7/2007 | A | PASS |
Forrest France
|
|
|
Access gates approved per FD, door hardware at the main entry/exit installed while on site, life safety inspection completed acceptable per site visit by K. Roule.
|
FIRE-Conference | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | DONE |
Troy Cobbley
|
|
|
I went over life safety requirements with the builder. He stated that he was going to install two vehicle gates. One on the south side of the building and the other on the north. I told him he needs fire dept approval for this. I told him about none hardened locks and the opticom systems.
|
BLD-Other | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/30/2007 at 2:46:02 PM. Contact: ###-####.
|
BLD-Other | 10/29/2007 | 10/30/2007 | 10/30/2007 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/29/2007 at 11:48:04 AM. Contact: ###-####.ceilling ok pending others/ need 4 wall clips/fire stopping.
|
BLD-Wall cover | 10/22/2007 | 10/23/2007 | 10/23/2007 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/22/2007 at 12:39:43 PM. Contact: ###-####. c/n idems ok
|
BLD-Wall cover | 10/18/2007 | 10/18/2007 | 10/18/2007 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/18/2007 at 10:55:18 AM. Contact: ###-####. relocate heater box to exterior wall or reinspect for wall gyp protection/ top of first floor needs fire safing gyp atchment ok can verify at ceilling grid insp/ gas piping pending mech.
|
BLD-Framing/Rough-in | 10/16/2007 | 10/17/2007 | 10/17/2007 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/12/2007 at 2:52:59 PM. Contact: ###-####.engineering and ec report archived.
|
BLD-Framing/Rough-in | 10/15/2007 | 10/16/2007 | 10/16/2007 | P | DEFR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/12/2007 at 2:52:59 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 10/12/2007 | 10/15/2007 | 10/15/2007 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/12/2007 at 2:52:59 PM. Contact: ###-####.
|
BLD-Concrete | 10/4/2007 | 10/5/2007 | 10/8/2007 | P | PART |
Jim Storey
|
|
|
howard rebar - 2nd floor Phone #: ###-#### need engineering for floor change. si on site
|
BLD-Foundation | 8/29/2007 | 8/30/2007 | 8/30/2007 | P | PASS |
Jim Storey
|
|
|
rebar; Ben; Phone #: ###-#### Internet Inspection Request from: Hattie James
|
BLD-Footing | 8/6/2007 | 8/7/2007 | 8/7/2007 | P | PASS |
Jim Storey
|
|
|
ben Phone #: ###-####
|
(F) Reprint permit | | | 7/18/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/13/2007 | | DONE |
|
|
|
|
Telephone call | | | 6/21/2007 | | DONE |
|
|
|
t/c w clinton yaka at ###-#### - permit ready and fees given - also need ACHD receipt
|
Permit Ready to Issue | | | 6/21/2007 | | |
|
|
|
|
Print Occupancy Form | | | 6/20/2007 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 4/19/2007 | | 6/19/2007 | | PASS |
|
|
|
6/19/2007 16:20:37 JCM - activity updated through activity BLDA022 from case BLD07-00986.
|
Routing - FIRE | 6/18/2007 | | 6/19/2007 | | PASS |
|
|
|
Attached updated review comments to plans.
|
Telephone call | | | 6/19/2007 | | PEND |
|
|
|
Awaiting resubmitted civil sheet showing 2nd fire hydrant.
|
Plan resubmittals received | | | 6/19/2007 | | |
|
|
|
Received 1 cover transmittal, 1 response letter for fire from Lochsa Engineering (1PG), 3 copies of sheet C2.01 and taken to John Menard
|
Routing - PLAN CHECK | 6/19/2007 | | 6/19/2007 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/19/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/23/2007 | | 6/18/2007 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 6/18/2007 | | PASS |
|
|
|
Inserted revised plans, reviewed and approved structural and nonstructural revisions.
|
Plan resubmittals received | | | 6/14/2007 | | DONE |
|
|
|
received 1 transmittal, and 1 copy of sheets S0.1,S0.2S1.01,S1.02S-8 taken to John M.
|
Plan resubmittals received | | | 6/13/2007 | | DONE |
|
|
|
received 1 transmittal,and 2 copys of sheets A1.1,A1.2 taken to John M.
|
Plan resubmittals received | | | 6/5/2007 | | DONE |
|
|
|
received 1 transmittal,1 fire code response,1 bld comments response,2 plan check review comments/ structural calcs1 copy of sheets S-8,S0.1,S0.2,S0.3,S1.01,S1.02,S2.01,S2.02,S2.03,S2.03,S2.04,S2.05 AND 2 copys of sheets A1.1,A1.2,A1.4,A4.1,A7.2 taken to John M.
|
Routing - PLAN CHECK | 5/9/2007 | | 5/23/2007 | | |
|
|
|
|
Routing - PUBLIC WORKS | 5/23/2007 | | 5/23/2007 | | PASS |
|
|
|
|
Routing PW Sewer Rating | 5/23/2007 | | 5/23/2007 | | PASS |
|
|
|
No sewer available, requires a Wet Line Waiver to be returned to Public Works before issuing the Building permit. Can contact sewer rating at ###-####.
|
Routing PW Drainage | 5/23/2007 | | 5/23/2007 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 4/20/2007 | | 5/23/2007 | | PASS |
|
|
|
|
Routing PW Drainage | 4/20/2007 | | 5/23/2007 | | PASS |
|
|
|
Contact Brian Murphy ###-####
|
Routing PW Sewer Design | 4/24/2007 | | 5/23/2007 | | PASS |
|
|
|
ok, no sewer, requires a Wet Line Waiver
|
Routing - FIRE | 5/8/2007 | | 5/9/2007 | | FAIL |
|
|
|
Emailed and faxed resubmittal items to architect. Attached review comments to plans.
|
1st review completed | | | 5/9/2007 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 5/8/2007 | | DONE |
|
|
|
e-mailed the architect with a copy of the plan review requesting revisions.
|
Routing - PLAN CHECK | 5/4/2007 | | 5/8/2007 | | FAIL |
|
|
|
John Menard
|
Routing - PLANNING | 4/30/2007 | | 5/4/2007 | | PASS |
|
|
|
DRH07-00074 Greg Johnson
|
Routing - PLUMBING | 4/27/2007 | | 4/30/2007 | | PASS |
|
|
|
per plans and 2003 upc
|
Plan resubmittals requested | | | 4/30/2007 | | DONE |
|
|
|
Faxed the architect a copy of the comment list from the consulting structural eingineer requesting revisions.
|
Routing Off Site - STRUCTURAL | 4/19/2007 | | 4/27/2007 | | FAIL |
|
|
|
Received comment list from the consulting structural engineer requesting revisions.
|
Routing - Erosion and Sediment | 4/24/2007 | | 4/27/2007 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing PW Street Lights | 4/24/2007 | | 4/25/2007 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 4/19/2007 | | 4/20/2007 | | PASS |
|
|
|
|
Telephone call | | | 4/19/2007 | | |
|
|
|
called action couriers for pick up to off site engineering
|
Application received | | | 4/19/2007 | | |
|
|
|
|
Pending Assignment by MYS | 4/19/2007 | | 4/19/2007 | | DONE |
|
|
|
4/19/2007 10:39:33 JCM - activity updated through activity BLDA166 from case BLD07-00986.
|
Plans ACCEPTED BY PLAN TECH | | | 4/19/2007 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/19/2007 | | DONE |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 4/19/2007 | | |
|
|
|
|