DOC - Permit Expired | 4/14/2011 | 4/14/2011 | 4/14/2011 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 4/11/2011 | 4/11/2011 | 4/14/2011 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 12/22/2010 | 12/22/2010 | 12/28/2010 | | DEFR |
Dave Hannah
|
|
|
|
BLD-Conference | 8/25/2010 | 8/25/2010 | 8/25/2010 | A | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 8/24/2010 | 8/24/2010 | 8/25/2010 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 6/23/2010 | 6/23/2010 | 6/23/2010 | | PASS |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 1/25/2008 | 1/25/2008 | 1/25/2008 | P | PART |
Dave Hannah
|
|
|
Randy This inspection is also for celing grid Phone #: ###-#### ok in office area needs clips or spraeder bars around perm
|
BLD-Other | 1/22/2008 | 1/22/2008 | 1/22/2008 | P | PASS |
Jim Sly
|
|
|
bryan Note: ceiling grid Phone #: ###-#### Corridor grid OK
|
FIRE-Conference | 1/14/2008 | 1/14/2008 | 1/14/2008 | P | DONE |
Forrest France
|
|
|
Conference completed.Look at old sky lights that are no longer in use before closing up.no Sprinklers required.
|
BLD-Framing/Rough-in | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Mike Jordan
|
|
|
bill - skylight Phone #: ###-####
|
BLD-Framing/Rough-in | 12/28/2007 | 12/31/2007 | 12/31/2007 | A | PASS |
Dave Hannah
|
|
|
bryan Phone #: ###-####
|
Issue PAID IN FULL permit | | | 12/12/2007 | | |
|
|
|
|
Plan assigned to (R_H) | 5/1/2007 | | 12/10/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 6/14/2007 | | 12/10/2007 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/10/2007 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/10/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/10/2007 | | DONE |
|
|
|
left vm for corey nelson - ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 12/10/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/7/2007 | | |
|
|
|
Received two copies of pages A0.0, A0.1, A0.2, A1.0, A2.0, A3.0, A4.0, A4.1, A5.0, S0.1, S1.01, S2.01; taken to Ron Hill
|
Plan resubmittals received | | | 12/4/2007 | | |
|
|
|
Received response to plan review comments (1 pg.) and two copies of A3.0; taken to Ron Hill
|
Plan Reviewer's activity | | | 10/23/2007 | | FAIL |
|
|
|
Reviewed 10/10/07 alternative design request letter from architect, Cory Nelson, Modus Architecture. The alternative design request is to allow the use of IBC 707.2 Exception 2, Item 2.1 as an alternate for providing 1-hour opening protection on an existing skylight below a proposed new exterior exit stair.
Fire does not feel this proposal is acceptable. The cited Code section stipulates that it is "for an escalator opening which is not a portion of the means of egress". This cited section should therefore not be applied to this situation, which is a required means of egress. Sprinklers are already a requirement for this building, so sprinklers do not constitute an equivalent alternative to the required 1-hour construction. Adding additional sprinklers would not improve the effectiveness or reliability of the existing sprinkler protection. Advised Cory of this decision by phone, 10/23/07; he understands and will use a different design approach.
|
Telephone call | | | 10/19/2007 | | DONE |
|
|
|
Telcon from Cory at Modus Architects, inquiring on status of an alternative design proposal, which George Slane told him had been directed to "Fire". I have not seen it, and nothing has been entered into Activities about such a proposal, so I referred him back to George.
|
Plan resubmittals received | | | 10/3/2007 | | DONE |
|
|
|
received 1 comments and 3 copys of sheets A0.0,A0.2,A1.0,A2.0,A3.0,A4.0 taken to Ron H.
|
Routing - FIRE | 6/11/2007 | | 6/14/2007 | | PASS |
|
|
|
Attached IFC Review comments to plans.
|
1st review completed | | | 6/14/2007 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 5/1/2007 | | 6/11/2007 | | FAIL |
|
|
|
|
(F) Reprint permit | | | 6/6/2007 | | |
|
|
|
|
Pending Assignment by MYS | 4/19/2007 | | 5/1/2007 | | DONE |
|
|
|
5/1/2007 16:31:17 MYS - activity updated through activity BLDA175 from case BLD07-00994.
|
Recd Pcfee & Taken To Pln CK | | | 4/19/2007 | | |
|
|
|
|
Application received | | | 4/19/2007 | | |
|
|
|
|
BLD-Conference | 6/23/2010 | 6/23/2010 | | P | |
Dave Hannah
|
|
|
|